Installation Instructions

Document No. 129-390


November 4, 2003

Metal Flush Mount Room Temperature


Sensor

Product Description Installation


1. Connect the field wires to the sensor lead wires
These Metal Flush Mount Room Temperature using the wire nuts provided. See Figure 1.
Sensors are self-contained, non-intrusive and WALL
tamper-resistant. They are available in both 10K SENSOR
ohm and 100K ohm thermistors, and 1000 ohm COVER PLATE

RTD. SECURITY
SCREWS (2)
UTILITY
BOX

Product Numbers
540-984 10K ohm thermistor (Type II) FIELD WIRING
536-984 100K ohm thermistor (TO CONTROLLER)

544-973 1K ohm RTD


Required Tools
• 5/64-inch hex head Allen Wrench
• Wire strippers/cutters
SEN0341R1

Expected Installation Time


SENSOR
ASSEMBLY
Figure 1. Installing the Sensor.
5 minutes
2. Push all wires into the utility box.
Prerequisites
3. Use the hex head Allen wrench to mount the
• 2-inch × 4-inch utility box, installed per sensor assembly to the utility box with the two
Mounting Instructions. security screws provided.
• Field wiring pulled to the utility box. 4. Connect the field wires to the appropriate
Mounting Instructions (Utility Box) controller termination point. See Figure 2.

Select a location for the sensor based on the The installation is now complete.
SENSING
following guidelines: SENSOR ELEMENT
• Locate sensor near the middle of an inside INPUT
wall, approximately five feet (1.5 m) from the COMMON
SEN0342R1

SHIELD
floor. FIELD
WIRING
• Do not mount: Figure 2. Wiring.
− in direct sunlight or drafts, or near
diffusers NOTE: 1. Some Siemens Building Technologies
− behind doors or drapes controllers may require a shield
termination.
− on walls used as return air plenums.
2. For individual panel wiring details, see
the appropriate hardware manual.
Item Number 129-390, Rev. 011

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and
models as design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their
respective owners. © 2003 Siemens Building Technologies, Inc.

Siemens Building Technologies, Inc. Your feedback is important to us. If you have Document No. 129-390
1000 Deerfield Parkway comments about this document, please send Printed in the U.S.A.
Buffalo Grove, IL 60089-4513 them to technical.editor@siemens.com Page 1 of 1
U.S.A.

You might also like