distance relay micromho setting cal.

Tanta ----- ELAATAF circuit 1

C.T.R 1200 In 1
P.T.R 2200 Un 100
ZONES SEC. PRIM. ko 0.7
Z1 11.78182 21.6 ǿ 82.447
Z2 16.06364 29.45 L KM 90
Z3 36.98182 67.8 UZ 0.545455
Z3R 2.945455 5.4
Z5 36.98182 67.8
Z5R 2.945455 5.4
Z6 47.50909 87.1
Z6R 9.136364 16.75
ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 11.78182

K14 1

k11+k12+13 2.455

k11 2 k12 0.4 k13 0.055

check z1 11.784

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 16.06364

K24 1

k21+k22 3.346591

k21 3 k22 0.35


checkz2 16.08

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 36.98182

k33 1

k31+k32 7.704545
k31 7 k32 0.7
z3 check 36.96
ZONE 3 R MULTIPLECATION FACTORS

Z3R= K33*K34*ZPH 2.945455


K34 0.613636 K34 0.6

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2

POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.07377 k54 0.1

k50 = (k51+k52)*k53*zph K50 = 19.96364 K53 1

Z5 = 2*(1-K54)K50 K53(K51+K52)= 4.159091


K51 4 K52 0.16

check z5 36.98182

Z5R =2*K54*K50 2.945455

Z6= K50.(0.3+2(1-K54)) 42.97091 Z6+Z6R=1.3(Z5+Z5R)

Z6R =K50(0.3+2K54) 8.934545 CHECK 1.3


TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.36 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06
MUTUAL IMPEDANCE
K6 0 K7 0 K8 0

NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 2 8 on on on on on off
K12 0.4 4 on on on on off off
K13 0.055 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 3
k22 0.35
k24 1

option select
K31 7 xy number 0 3
K32 0.7 scheme type POR 3PH TRIP
K33 1 a/b 1
K34 0.6 zph 0
zn 3.36
k21 3 zm 0
k22 0.35 pph theta 4.8
k24 1 gr theta 82.447
mut theta 82.447
distance relay micromho setting cal.
Tanta ----- ETYA circuit 2

C.T.R 800 In 1
P.T.R 1200 Un 110

ZONES SEC. PRIM. ko 0.75


Z1 7.866667 11.8 ǿ 82.447
Z2 11.33333 17 L KM 34.95
Z3 33.33333 50 uz 0.666667
Z3R 2.446667 3.67
Z5 33.33333 50
Z5R 2.446667 3.67

ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k2/ In 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 7.866667

K14 1

k11+k12+13 1.639

k11 1 k12 0.6 k13 0.036

check z1 7.8528

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 11.33333

K24 1

k21+k22 2.361111

k21 2 k22 0.73


checkz2 13.104

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 33.33333

k33 1

k31+k32 6.944444
k31 6 k32 0.628
z3 check 31.8144

ZONE 3 R MULTIPLECATION FACTORS


Z3R= K33*K34*ZPH 2.446667
K34 0.509722 K34 0.5

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2

POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.068381 k54 0.1

k50 = (k51+k52)*k53*zph K50 = 17.89 K53 1

Z5 = 2*(1-K54)K50 K53(K51+K52)= 3.727083


K51 3 K52 0.52

check z5 33.33333

Z5R =2*K54*K50 2.446667

Z6= K50.(0.3+2(1-K54)) 38.70033 Z6+Z6R=1.3(Z5+Z5R)

Z6R =K50(0.3+2K54) 7.813667 CHECK 1.3


TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.6 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06
MUTUAL IMPEDANCE
K6 0 K7 0 K8 0

NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 1 8 on on on on on off
K12 0.6 4 on on on on off off
K13 0.036 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 2
k22 0.73
k24 1

option select
K31 6 xy number 0 3
K32 0.628 scheme type POR 3PH TRIP
K33 1 a/b 1
K34 0.5 zph 0
zn 3.6
k21 2 zm 0
k22 0.73 pph theta 4.8
k24 1 gr theta 82.447
mut theta 82.447
distance relay micromho setting cal.
tanta ----- nubaria circuit

c.t.r 1200 In 5
p.t.r 2200 Un 100
zones ko 0.7
Z1 14.16 ǿ 82
Z2 22.5 L KM 59
Z3 40 uz 0.545455
Z3R 2.5
Z5 40
Z5R 2.5

ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 7.723636
K14 1
k11+k12+13 1.609

k11 1 k12 0.6 k13 0.009

check z1 7.7232

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 12.27273
K24 1
k21+k22 2.556818
k21 2 k22 0.56
checkz2 12.288

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 21.81818


k33 1
k31+k32 4.545455
k31 4 k32 0.55
z3 check 21.84

ZONE 3 reverse MULTIPLECATION FACTORS

Z3R= K33*K34*ZPH 1.363636


K34 0.284091 K34 0.5 check 1.363636

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2


POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.058824 k54 0.1


k50 = (k51+k52)*k53*zph K50 = 11.59091 K53 1
Z5 = 2*(1-K54)K50 K53(K51+K52)= 2.414773
K51 2 K52 0.42
check z5 21.81818
Z5R =2*K54*K50 1.363636
Z6= K50.(0.3+2(1-K54)) 25.29545 Z6+Z6R=1.3(Z5+Z5R)
Z6R =K50(0.3+2K54) 4.840909 CHECK 1.3
TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.36 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06

MUTUAL IMPEDANCE
K6 0 K7 0 K8 0
NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 1 8 on on on on on off
K12 0.6 4 on on on on off off
K13 0.009 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 2
k22 0.56
k24 1
option select
K31 4 xy number 0 3
K32 0.55 scheme type POR 3PH TRIP
K33 1
K34 0.5
a/b 1
zph 4.8
zn 3.36
zm 0
pph theta 82
gr theta 82
mut theta 82
distance relay micromho setting cal.
tanta ----- quasna circuit

c.t.r 1200 In 5 uz 0.545455


p.t.r 2200 Un 100
zones ko 0.7
Z1 4.843636 ǿ 82
Z2 8.476364 L KM 37
Z3 21.81818
Z3R 1.210909
Z5 21.81818
Z5R 1.210909

ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 4.843636
K14 1
k11+k12+13 1.009

k11 1 k12 0 k13 0.01

check z1 4.848

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 8.476364
K24 1
k21+k22 1.765909
k21 1 k22 0.77
checkz2 8.496

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 21.81818


k33 1
k31+k32 4.545455
k31 4 k32 0.55
z3 check 21.84

ZONE 3 reverse MULTIPLECATION FACTORS

Z3R= K33*K34*ZPH 1.210909


K34 0.252273 K34 0.25

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2


POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.052582 k54 0.1


k50 = (k51+k52)*k53*zph K50 = 11.51455 K53 1
Z5 = 2*(1-K54)K50 K53(K51+K52)= 2.398864
K51 2 K52 0.4
check z5 21.81818
Z5R =2*K54*K50 1.210909
Z6= K50.(0.3+2(1-K54)) 25.27255 Z6+Z6R=1.3(Z5+Z5R)
Z6R =K50(0.3+2K54) 4.665273 CHECK 1.3
TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.36 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06

MUTUAL IMPEDANCE
K6 0 K7 0 K8 0
NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 1 8 on on on on on off
K12 0 4 on on on on off off
K13 0.01 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 1
k22 0.77
k24 1

option select
K31 4 xy number 0 3
K32 0.55 scheme type POR 3PH TRIP
K33 1
K34 0.25
a/b 1
zph 4.8
zn 3.36
zm 0
pph theta 82
gr theta 82
mut theta 82
distance relay micromho setting cal.
tanta ----- el mehalla circuit

c.t.r 1200 In 5
p.t.r 2200 Un 100
zones ko 0.7
Z1 4.450909 ǿ 82
Z2 7.134545 Lkm 34
Z3 21.81818 uz 0.545455
Z3R 1.363636
Z5 21.81818
Z5R 1.363636

ZONE 1 MULTIPLECATION FACTORS

ZPH 4.8 0.8 set k1+k2 to 4.8 if zone setting is above 4.8 ohms
zph = k1+k 4.8 and 0.96 for 5 amp
k1 4
k2 0.8
Z1 = (K11+K12+13)*K14*ZPH 4.450909
K14 1
k11+k12+13 0.927

k11 0.9 k12 0.03 k13 0

check z1 4.464

ZONE2 MULTIPLECATION FACTORS

Z2 = (K21+K22)K24*ZPH 7.134545
K24 1
k21+k22 1.486364
k21 1 k22 0.49
checkz2 7.152

ZONE 3 forward MULTIPLECATION FACTORS

z3f= (k31+k32)k33zph 21.81818


k33 1
k31+k32 4.545455
k31 4 k32 0.55
z3 check 21.84

ZONE 3 reverse MULTIPLECATION FACTORS

Z3R= K33*K34*ZPH 1.363636


K34 0.284091 K34 0.28

ZONE EXT. SETTING

Z1ext = Z1(K15+K16) 120% Z1 K15 1 K16 0.2


POWER SWING BLOCKING SETTING

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

K54 = Z5R /(Z5+Z5R) i.e Z3R/(Z3R+Z3)

k54 = 0.058824 k54 0.1


k50 = (k51+k52)*k53*zph K50 = 11.59091 K53 1
Z5 = 2*(1-K54)K50 K53(K51+K52)= 2.414773
K51 4 K52 0.43
check z5 21.81818
Z5R =2*K54*K50 1.363636
Z6= K50.(0.3+2(1-K54)) 25.29545 Z6+Z6R=1.3(Z5+Z5R)
Z6R =K50(0.3+2K54) 4.840909 CHECK 1.3
TZ6 40 msec
a/b 1
earth fault comp. factor

KO = ZN / ZPH ZN = 3.36 ZN = (K3+K4+K5)/IN


K3 3 K4 0.3 K5 0.06

MUTUAL IMPEDANCE
K6 0 K7 0 K8 0
NUBARIA
C.T.R 1200 LK7 OFF enable Z1 trip
V.T.R 2200 LK6 OFF z3 time delayed tripping operative
K1 4 LK5 OFF weak infeed aided trip inhibited
K2 0.8 LK4 ON indication will be rest on power on
LK3 ON block A/R for backupcleared fault also for z1&zext
K3 3 LK2 ON current rever guard inoperative in OPR scheme
K4 0.3 LK1 OFF weak infeed aided trip inhibited
K5 0.06 LK0 OFF current & distance compartor controlled SOTF trip
switches T2phsec T2G T3PH T3G TP Td
K6 0 128 off off off off off off
K7 0 64 off off off off off off
K8 0 32 on on on on off on
16 off off off off off on
K11 0.9 8 on on on on on off
K12 0.03 4 on on on on off off
K13 0 2 off off off off off off
K14 1 1 on on on on off on
value 0.45 0.45 0.9 0.9 0.08 0.098
K15 1
K16 0.2

k21 1
k22 0.49
k24 1

option select
K31 4 xy number 0 3
K32 0.55 scheme type POR 3PH TRIP
K33 1
K34 0.28
a/b 1
zph 4.8
zn 3.36
zm 0
pph theta 82
gr theta 82
mut theta 82