General
Specifications UT35A/UT32A
Digital Indicating Controllers
GS 05P01D31-01EN [Style: S2]

n Overview
The UT35A/UT32A digital indicating controllers employ
an easy-to-read, 14-segment large color LCD display,
along with navigation keys, thus greatly increasing
the monitoring and operating capabilities. A ladder
sequence function is included as standard. The short
depth of the controller helps save instrument panel
space. The UT35A/UT32A also support open networks
such as Ethernet communication.

n Features
• A 14-segment, active (PV display color changing
function) color LCD display is employed.
Two five-digit, high-resolution displays are possible.
Alphabet letters can be displayed in an easy-to-read UT35A UT32A
manner. The guide display shows parameter names.
• Easy to operate Table of Number of Inputs and Outputs
Navigation keys (SET/ENTER and Up/Down/Left/
Model and Number Number Number Number of
Right arrow keys) are employed to facilitate making suffix code of analog of analog of contact contact
settings. (See the input output input output
• 65 mm depth model code) points points (*1) points points (*3)
The small depth enables the mounting in a thin and UT35A
small instrumented panel. -×0× 1 1 2 3
-×1× 1 1 4 5
• Ladder sequence function is included as standard.
-×2× 1 1 (*2) 7 8
This function allows for creating a simple sequence UT32A
control. Dedicated LL50A Parameter Setting Software -×0× 1 1 2 3
(sold separatly) allows for performing programming -×1× 1 1 2 3
-×2× 1 1 (*2) 4 5
using a ladder language.
• Various built-in open network functions such as Eth- *1: Excluding control output
ernet are available. *2: In the case of cooling control output is analog output, it
can not be used for transmission output.
Easy connection with various vendors’ PLCs is possible.
*3: Excluding control output relays
• Quick setting function
Setting only the minimum necessary parameters for
operation is possible.
• Equipped with a multitude of functions
Universal I/O are included as standard. PID control,
heating/cooling control, etc. are available.

n Functional Specifications n Control Computation Function


Control Specifications (1) Types of control
(1) Control Mode • PID control
Single-loop control • ON/OFF control (*4)
• Two-position two-level control (*5)
• Heating and cooling control (*5)
(2) Control period *4: Not selectable for Position proportional type
*5: Selectable for heating and cooling control
200 ms

Yokogawa Electric Corporation GS 05P01D31-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan 1st Edition Nov.30, 2009 (KP)
Tel.: 81-422-52-7179 Fax.: 81-422-52-6619 2nd Edition Jun.11, 2010 (KP)
<<Contents>> <<Index>> 
(2) Control Computation Function Alarm Functions
(a) Target setting point and the number of PID param- • Types of Alarm
eter groups
PV (measured value) high/low limit alarm
Respectively, four sets of target setpoints, alarm Measured value Deviation high/low limit alarm
setpoints, and PID parameters can be set. alarm Deviation high and low limits alarm
(b) Selecting the PID parameter group Deviation alarm Deviation within high and low limits alarm
The following PID parameter groups can be selected. Rate-of-change Analog input PV high/low limit alarm
• Target setpoint number (SPNO) (The PID number alarm Feedback input high/low limit alarm
can be set arbitrarily.) PV rate-of-change alarm
• Measured input zone PID SP (setpoint) high/low limit alarm
Target SP high/low limit alarm
• Target setpoint zone PID Target SP deviation high/low limit alarm
• Reached target setpoint zone PID Setpoint alarm Target SP deviation high and low limits
(c) Auto-tuning alarm
• Tuning results can be selected from two options, Target SP deviation within high and low
Normal or Stable. limits alarm
• Tuning output limit can be set. (It cannot be used in Control output high/low limit alarm
Output alarm
heating/cooling control.) Cooling control output high/low limit alarm
(d) “Super” function: Overshoot-suppressing function Heater disconnection alarm (for /HA option)
Other alarms Self-diagnosis alarm
(e) “Super 2” function: Hunting-suppressing function FAIL
(f) STOP preset output function
(g) Input ERROR preset output function • Alarm Functions
(h) MANUAL preset output function Alarm stand-by action
Alarm output Alarm latch (forced reset) function
action Alarm hysteresis
(3) Operation Mode Switching Alarm ON/OFF delay timer
Operation mode AUTO/MANUAL and RUN/STOP switching Number of alarm
4
REMOTE/LOCAL switching (only model settings
switching with communication option) Number of alarm
Up to 8 (differs by model code)
output points
(4) Control Parameter Setting Range Contact I/O Function
Proportional
0.1 to 999.9% This function allows for allocating the input error
band
condition, operation condition, alarm condition or other
Integral time 1 to 6000 sec. or OFF (using manual reset)
conditions to the contact input and contact output.
Derivative time 1 to 6000 sec. or OFF
ON/OFF control AUTO/MANUAL switching
hysteresis (one 0.0 to 100.0% of measured input range REMOTE/LOCAL switching (only model
or two hysteresis width with communication option)
points) STOP/START switching
Preset output -5.0 to 105.0% (however, 0 mA or less Switching to AUTO
value cannot be output) Switching to MANUAL
High/low output -5.0 to 105.0% Switching to REMOTE (only model with
limiter Low limit setpoint < high limit setpoint communication option)
When manual control is carried out with Contact input
Tight shut Switching to LOCAL (only model with
4 to 20 mA output, control output can be communication option)
function reduced to about 0 mA.
AUTO-TUNING START/STOP switching
Rate-of-change
0.1 to 100.0%/sec., OFF LCD backlight ON/OFF switching
limiter of output
Message interrupt displays 1 through 4
For heating and cooling control: -100.0 to
Output 50.0% SP number specification
deadband For position proportional control: 1.0 to PID number specification
10.0% Manual preset output number specification
Alarms 1 through 4
(5) Ladder computation period Contact output
Status output
Ladder computation period is the same as control
period. Ladder Sequence Function
(1) Number of I/O Points
UT35A UT32A
Number of digital input points Up to 7 Up to 4
Number of digital output points Up to 8 Up to 5
This is limited by the number of contact I/O signal
points. (See the model code.)

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 
(2) Types of Command (3) Sequence Device
Number of Types of device Number of points
Remark
commands Input relay 7 (max)
Number of basic Digital I/O
Load, AND, OR, Timer, Output relay 8 (max)
13
command types Counter, etc. M relay (bit data) 256
Comparison, reverse, DAT register (data) 28
Number of appli- addition/subtraction/ Internal device
P register (parameter) 10
cation command 73 multiplication/division, logic
types operation, high/low limiter, K register (constant) 30
etc. Special device Special relay (bit data) 12
Process data and process relay can be used besides
the above-mentioned.
(4) Program capacity
Max Program capacity: 300 steps *
*: Available number of steps differs according to the
parameters and using command.
Communication Function
Communication
Function Method Interface Targets Max connection
Data
Server Ethernet PLC and others 2 connections
Modbus/TCP A standard industry protocol RS-485:
Ethernet
allowing communications Gateway UT55A/UT52A 31 units
+RS-485
between the controller and UT35A/UT32A (*1)
devices such as PCs, PLCs, PLC and others,
Modbus and DCSs. Slave RS-485 UT55A/UT52A 31 units
(RTU/ASCII) UT35A/UT32A (*2)
Number of nodes:
Slave RS-485 PLC and others 126
PROFIBUS-DP 31 Units
Modbus master UT55A/UT52A
Used for communication RS-485 (Main Controller
function UT35A/UT32A
between PLCs and is included.)
remote I/O, enabling high- Number of nodes:
speed data transmission. Slave RS-485 PLC and others 42 (Remote device)
CC-Link 31 Units
Modbus master UT55A/UT52A/
RS-485 (Main Controller PV, SP, OUT,
function UT35A/UT32A ALM etc
is included.)
A protocol allowing multiple Read/Write: 4
controllers to send and RS-485 UT55A/UT52A units
Peer to peer receive data between Multi-drop (2 wire UT35A/UT32A Read only : 28
one another. The Ladder only) units
Program is used.
A protocol to coordinate the
Coordinated operation of two or more UT55A/UT52A Master : 1 unit
Master/Slave RS-485
Communication instruments controlling the UT35A/UT32A (*2) Slave : 31 units
same process.
The proprietary Yokogawa
protocol allowing
PC link PC and others,
communications to PCs,
PLCs and touch panels. Slave RS-485 UT55A/UT52A 31units
UT35A/UT32A (*2)
A protocol to communicate
Ladder to PLCs.
*1: UT digital indicating controller, Signal conditioner JUXTA, Power monitor POWERCERT can be connected.
*2: UT digital indication controllers can be connected.
Physical interface
Ethernet Standard : IEEE802.3 (10BASE-T, 100BASE-TX)
Max segment length : 100m
Max. Connecting Configguration : Cascade Max. 4 level (10BASE-T), Max. 2 level (100BASE-TX)
RS-485 Standard : EIA RS-485
Communication method : Two-wire harf-duplex or four-wire harf-duplex, start-stop synchoronization,
and non-procedural
Baud rate : 600,1200,2400,4800,9600,19200 or 38400bps Peer to peer communication is only 19200bps
Maximum communication distance : 1200m
Terminating resistor : 220Ω (External)
PROFIBUS-DP Standard : Field bus (IEC61158)
Corresponding version : DP V0
Baud rate : 9.6k, 19.2k, 45.45k, 93.75k, 187.5k, 0.5M, 1.5M, 3M, 6M, 12M, AUTO (*3)
Communication distance : 1200m (9.6k to 93.75k) 1000m (187.5k)
400m (0.5M) 200m (1.5M)
100m (3M to 12M)
*3: AUTO automatically sets the baud rate to that of the host controller (PROFIBUS-DP master).
CC-Link Supported on version : Remote device (Ver.1.10, Ver.2.00)
Baud rate : 156k, 625k, 2.5M, 5M, 10M bps
Transmission distance : 1.2km (156k bps), 600m (625k bps), 200m (2.5M bps), 150m (5M bps),
100m (10M bps)
When used optical repeater : 7.6 km (156k) to 4.3 km (10M)

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 
n Hardware Specifications The accuracy is that in the standard operating condi-
tions: 23 ±2°C, 55 ±10%RH, and power frequency at
Display Specifications 50/60 Hz.
• PV display *1: ±0.3°C and ±1 digit in the range between 0 and 100°C
5-digit, 14-segment active color LCD (white/red) ±0.5°C ±1 digit in the range between -100 and 200°C
Character height: 21.5 mm for UT35A and 13.0 mm *2: W-5% Re/W-26% Re (Hoskins Mfg.Co.),����������
ASTM
���������
E988
for UT32A • Applicable standards: JIS, IEC and DIN (ITS-90) for ther-
• Data display mocouples and resistance-temperature detectors (RTD)
5-digit, 11-segment color LCD (orange) • Input sampling period: Synchronized to control period
• Bar graph display • Burnout detection
12-segment color LCD (orange) Upscale and downscale of function, and OFF can
be specified for the standard signal of thermocou-
Universal Input Specifications
ple and resistance-temperature detector (RTD).
• Number of input points: 1 For integrated signal input, 0.1 V or 0.4 mA or less
• Types of input, instrument range, and measurement is judged as a burnout.
accuracy (see the table below) • Input bias current: 0.05 μA (for thermocouple and
Instrument range resistance-temperature detector (RTD))
Types of input Accuracy
°C °F • Resistance-temperature detector (RTD) measured
-270.0 to 1370.0°C -450.0 to 2500.0°F ±0.1% of instrument
range ±1 digit for 0°C
current: About 0.16 mA
K -270.0 to 1000.0°C -450.0 to 2300.0°F
-200.0 to 500.0°C -200.0 to 1000.0°F or more • Input resistance
J -200.0 to 1200.0°C -300.0 to 2300.0°F ±0.2% of instrument 1 MΩ or more for thermocouple/mV input
-270.0 to 400.0°C -450.0 to 750.0°F range ±1 digit for less
than 0°C About 1 MΩ for voltage input
However, ±2% of About 250 Ω for current input (with built-in shunt
instrument range
±1 digit for less than
resistance)
T
0.0 to 400.0°C -200.0 to 750.0°F -200°C of thermocouple • Allowable signal source resistance
K ±1% of instrument
range ±1 digit for less
250 Ω or less for thermocouple/mV input
than -200°C of thermo- Effect of signal source resistance: 0.1 μV/Ω or less
couple T 2 kΩ or less for DC voltage input
±0.15% of instrument
range ±1 digit for 400°C Effect of signal source resistance: about
B 0.0 to 1800.0°C 32 to 3300°F
or more 0.01%/100 Ω
±5% of instrument
range ±1 digit for less
• Allowable wiring resistance
than 400°C Up to 150 Ω per line for resistance-temperature
S 0.0 to 1700.0°C 32 to 3100°F ±0.15% of instrument detector (RTD) input (conductor resistance
Thermocouple

R 0.0 to 1700.0°C 32 to 3100°F range ±1 digit


±0.1% of instrument between the three lines shall be equal)
range ±1 digit Effect of wiring resistance: ±0.1°C/10 Ω
N -200.0 to 1300.0°C -300.0 to 2400.0°F ±0.25% of instrument
range ±1 digit for less
• Allowable input voltage/current
than 0°C ±10 V DC for thermocouple/mV/mA or resistance-
E -270.0 to 1000.0°C -450.0 to 1800.0°F ±0.1% of instrument
range ±1 digit for 0°C
temperature detector (RTD) input
L -200.0 to 900.0°C -300.0 to 1600.0°F
-200.0 to 400.0°C -300.0 to 750.0°F or more ±20 V DC for V input
±0.2% of instrument ±40 mA DC for mA input
range ±1 digit for less
than 0°C • Noise reduction ratio
U
0.0 to 400.0°C -200.0 to 1000.0°F However, ±1.5% of 40 dB or more (at 50/60 Hz) in normal mode
instrument range ±1 digit
for less than -200.0°C of
120 dB or more (at 50/60 Hz) in common mode
thermocouple E • Reference junction compensation error
W (*2) 0.0 to 2300.0°C 32 to 4200°F
±0.2% of instrument ±1.0°C (15 to 35°C)
range ±1 digit
Platinel ±0.1% of instrument ±1.5°C (-10 to 5°C and 35 to 50°C)
0.0 to 1390.0°C 32.0 to 2500.0°F
2 range ±1 digit
±0.5% of instrument
range ±1 digit for 800°C
PR20-40 0.0 to 1900.0°C 32 to 3400°F or more
Accuracy not guaran-
teed for less than 800°C
W97
±0.2% of instrument
Re3-W75 0.0 to 2000.0°C 32 to 3600°F
range ±1 digit
Re25
±0.1% of instrument
-200.0 to 500.0°C -300.0 to 1000.0°F
detector (RTD) 3-wire
Resistance-temperature

range ±1 digit (*1)


JPt100
±0.1% of instrument
-150.00 to 150.00°C -200.0 to 300.0°F
range ±1 digit
-200.0 to 850.0°C -300.0 to 1560.0°F ±0.1% of instrument
-200.0 to 500.0°C -300.0 to 1000.0°F range ±1 digit (*1)

Pt100
±0.1% of instrument
-150.00 to 150.00°C -200.0 to 300.0°F
range ±1 digit

0.400 to 2.0000 V -
Standard
1.000 to 5.000 V -
signal
4.00 to 20.00 mA -
±0.1% of instrument
0.000 to 2.000 V -
range ±1 digit
DC voltage 0.00 to 10.00 V -
-10.00 to 20.00 mV -
DC current 0.00 to 20.00 mA -

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 
Analog Output Specifications Position Proportional Output Specifications
• Number of points • Position signal input
Control output (heating-side output): 1 point Slide resistance: 100 Ω to 2.5 kΩ of total resistance
(standard), which is shared with transmission 100% side and slide line: with disconnection
output detection
Cooling-side output: 1 point, which is 0% side: without disconnection detection
shared with transmission output Current input: 4 to 20 mA DC (with disconnection
• Output functions detection)
Current output or voltage pulse output • Sampling period: 50 ms
• Current output • Measurement resolution: 0.1% of input span
4 to 20 mA DC or 0 to 20 mA DC/load resistance • Position proportional relay output
600 Ω or less UT35A: Two 1a-contact points , 3 A at 250 V
• Current output accuracy AC or 3A at 30 V DC (resistance load)
±0.1% of span (however, ±5% of span for 1 mA UT32A: Two 1a-contact points , 3 A at 240 V
or less) AC or 3A at 30 V DC (resistance load)
The accuracy is that in the standard operating *: This cannot be used for a small load of 10 mA or less.
conditions: 23 ±2°C, 55 ±10%RH, and power Retransmission Output Specifications
frequency at 50/60 Hz
• Number of points: 1 point (standard), which is shared
• Voltage pulse output
with 15 V DC loop power supply
Application: time proportional output
Additional 1 points when analog control output are
ON voltage: 12 V or more/load resistance of 600
not used
Ω or more
• Output function: current output
OFF voltage: 0.1 V DC or less
4 to 20 mA DC or 0 to 20 mA DC/load
Time resolution: 10 ms or 0.1% of output value,
resistance 600 Ω or less
whichever is larger
• Current output accuracy: ±0.1% of span (however,
Relay Contact Output Specifications ±5% of span for 1 mA or less)
• Types of contact and number of points The accuracy is that in the basic operating
Control relay output: one 1c-contact point conditions: 23 ±2°C, 55 ±10%RH, and power
Control output of heating and cooling control: frequency at 50/60 Hz
2 1a-contact points 15V DC Loop Power Supply Specifications
Alarm output: 3 1a-contact points (Common is • Number of points: 1 point (standard), which is shared
separated) with retransmission output
• Contact rating Control output (1 point) can also be used.
1c-contact: 3 A at 250 V AC or 3 A at 30 V DC • Supply voltage: 14.5 to 18.0 V DC
(resistance load) • Maximum supply current: about 21 mA (with short-cir-
1a-contact: cuit current limiting circuit)
For alarm output: 1 A at 240 V AC or 1 A at
30 V DC (resistance load) Contact Input Specifications
For output of heating and cooling control • Number of points: 2 points (standard)
relay output: 3 A at For the maximum number of points, see the
240 V AC or 3 A at 30 V DC (resistance load) model and suffix code table.
*: This cannot be used for a small load of 10 mA or less. • Input type: no-voltage contact input or transistor con-
• Application: time proportional output, alarm output, tact input
FAIL output, etc. • Input contact capacity: 12 V DC, 10 mA or more
• Time resolution for control output: 10 ms or 0.1% of Be sure to use a contact with a minimum ON
output value, whichever is larger current of 1 mA or more
Step Response Time Specifications • ON/OFF detection
For no-voltage contact input:
1s
Contact resistance 1 kΩ or less in ON state
(Response time at 63% of transmission output when a Contact resistance 50 kΩ or more in OFF state
change is made stepwise in the range between 10 and Transistor contact input:
90% of input span) 2 V or less in ON state
Leak current 100 μ A or less in OFF state
• Status detection minimum hold time: control period
+ 50 ms
• Application: SP switching, operation mode switching,
event input
Transistor Contact Output Specifications
• Number of points: see the model and suffix code table
• Output form: open collector (sink current)
• Output contact capacity: Up to 24 V DC, 50 mA
• Output time resolution: min 200 ms

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 
Heater Break Alarm Specifications (for /HA Option) Power Supply Specifications and Isolation
• Function: Measures the heater current using an • Power supply
external current transformer (CT) and generates a Rated voltage: 100 to 240 V AC (+10%/-15%), 50/60 Hz
heater break alarm when the measured value is less 24 V AC/DC (+10%/-15%) (When the
than the disconnection detection value. /DC option is specified)
• Number of input points: 2 points • Power consumption: UT35A: 18 VA (For the /DC
• Number of output points: 2 points (transistor contract option. DC: 9 VA, AC: 14 VA)
output) UT32A: 15 VA (For the /DC
• CT input resistance: about 9.4 Ω option. DC: 7 VA, AC: 11 VA)
• CT input range: 0.0 to 0.1 Arms (0.12 Arms or more • Storage: Nonvolatile memory
cannot be applied) • Allowable power interruption time: 20 ms (at 100 V AC)
• Heater current alarm setting range: OFF, 0.1 to 300.0 • Withstanding voltage
Arms 2300 V AC for 1 minute between primary and
Heater current measured value display range: 0.0 to secondary terminals
360.0 Arms 1500 V AC for 1 minute between primary terminals
*: The CT ratio can be set. CT ratio setting range: 1 to 3300 500 V AC for 1 minute between secondary
• Recommended CT: CT from URD Co. Ltd. terminals
CTL-6-S-H: CT ratio 800, measurable current (Primary terminals = Power (*) and relay output
range: 0.1 to 80.0 Arms terminals, Secondary terminals = Analog I/O signal
CTL-12L-30: CT ratio 3000, measurable current terminals, contact input terminals, communication
range: 0.1 to 180.0 Arms terminals, and functional grounding terminals.)
• Heater current measurement period: 200 ms *: Power terminals for 24 V AC/DC models are the
• Heater current measurement accuracy: ±5% of CT secondary terminals.
input range span ±1 digit (CT error is not included) • Insulation resistance
• Heater current detection resolution: Within 1/250 of Between power supply terminals and a grounding
CT input range span terminal: 20 MΩ or more at 500 V DC
• Disconnection detection ON time: Minimum 200 ms. • Isolation specifications
(for time proportional output)
PV (universal) input terminal
24 V DC Loop Power Supply Specifications
Control and transmission (analog) output terminal
(for /LP Option) (not isolated between the analog output terminals)
• Application: Power is supplied to the 2-wire transmitter. Valve position (feedback) input terminal

• Supply voltage: 21.6 to 28.0 V DC Control relay (c-contact or 2 a-contact) output terminal
• Rated current: 4 to 20 mA DC Alarm-1 relay (a-contact) output terminal
• Maximum supply current: About 30 mA (with short-cir- Alarm-2 relay (a-contact) output terminal Internal Power
cuit current limiting circuit) circuits supply
Alarm-3 relay (a-contact) output terminal
Safety and EMC Standards Position proportional relay output terminal
• Safety: Contact input terminal (All)
Compliant with IEC/EN61010-1 (CE), approved by RS485 communication terminal (2 ports)
CAN/CSA C22.2 No. 61010-1 (CSA), UL61010-1. 24 V DC loop power supply terminal
Installation category: CAT. II
Contact output (transistor) terminal
Pollution degree: 2
Measurement category: I (CAT. I) Ethernet/PROFIBUS-DP/CC-Link communication terminal

Rated measurement input voltage: Max. 10 V DC Current transformer input terminal


Rated transient overvoltage: 1500 V (*) The circuits divided by lines are insulated mutually.
*: This is a reference safety standard value for measure-
ment category I of IEC/EN/CSA/UL61010-1. This value is Environmental Conditions
not necessarily a guarantee of instrument performance.
• EMC standards: Normal operating conditions
Compliant with • Ambient temperature: -10 to 50°C (-10 to 40°C for
CE marking side-by-side mounting of controllers)
EN 61326-1 Class A, Table 2 (For use in industrial • Ambient humidity: 20 to 90% RH (no condensation)
locations), • Magnetic field: 400 A/m or less
EN 61326-2-3 • Continuous vibration (at 5 to 9 Hz) Half amplitude of
EN 55011 Class A, Group 1 1.5 mm or less
EN 61000-3-2 Class A (at 9 to 150 Hz) 4.9 m/s2 or less, 1 oct/min for 90 min-
EN 61000-3-3 utes each in the three axis directions
C-tick mark • Rapid vibration: 14.7 m/s2, 15 s or less
EN 55011 Class A, Group 1 • Impact: 98 m/s2 or less, 11 msec.
The instrument continues to operate at a measure • Installation altitude: 2,000 m or less above sea level
ment accuracy of within ±20% of the range during • Warm-up time: 30 minutes or more after the power is
testing. turned on
• RoHS regulation: Compliant • Start-up time within 10 s

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 
Transportation and Storage Conditions For RTD input:
• Temperature: -25 to 70°C ±0.05°C/°C (ambient temperature) or less
• Temperature change rate: 20°C per hour or less For current input:
• Humidity: 5 to 95%RH (no condensation) ±0.01% of F.S. (instrument range)/°C
For analog output:
Effects of Operating Conditions ±0.02% of F.S./°C or less
• Effect of ambient temperature • Effect of power supply fluctuation:
For voltage or TC input: For analog input: ±0.05% of F.S. (instrument range)
±1 μ V/°C or ±0.01% of F.S. (instrument range)/ or less
°C, whichever is greater For analog output: ±0.05% of F.S. or less
(Each within rated voltage range)

n Block Diagram
Single Loop Control
Equipped as standard
Equipped as standard.
PV input Contact inputs

PV DI1 DI2

Input type IN

Input unit UNIT

Input range/scale RH, RL SDP SH, SL

Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameters Setting Software User’s Manual.

PV input bias BS Communication


SPNO SP
PV input filter FL
Ratio bias computation RT RBS Target setpoints 1 to 4
REMOTE LOCAL
R/L

SP limiter SPH, SPL

SP ramp rate UPR, DNR TMU

PV display SP display
Control computation

CNT ALG

Output limiter OH, OL


Input error preset output EPO
Normal
When sensor burnout occurs
Manual preset output MPON

Manual operation

Output limiter OH, OL OLMT


MAN AUTO
A/M AUTO (ON)/MAN (OFF) switch
Preset output PO

STOP RUN
S/R STOP (ON)/RUN (OFF) switch

* After the control output terminal is specified by the parameter OT,


Output terminal assignment OT other current output terminals can be used as retransmission output.

OUT retransmission output Equipped as standard Equipped as standard


O1RS RET retransmission output Alarm
RTS

Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.

For optional suffix code /LP For optional suffix code /HA
24 V loop Heater break alarm
power supply
(PV high limit)

(PV high limit)


(PV low limit)
Alarm 1

Alarm 3
Alarm 2

LPS OUT OUT RET AL1 AL2 AL3 HAL1 HAL2

Heater break Heater break


Relay Current or voltage pulse Current alarm 1 alarm 2
(Current when retransmission output)
Terminal Parameter Function
Legend
Analog signal Contact signal Front panel key

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 
n Terminal Arrangement
Terminal Arrangement for UT35A Single Loop Control
(Equipped
Control output OUT PV input PV as standard) Retransmission output RET (Equipped as standard)
(Suffix code: Type1=-0)
Relay contact output Factory default: PV input TC input RTD input Retransmission output 15 V DC loop power supply Can be used for 15 V DC loop
type is undefined. power supply when not used for
Terminal wiring differs in Heating/cooling Default: PV
NC 101 A 201 retransmission retransmission output.
control and Position proportional control.
202 205 205
Refer to the terminals of Position 4-20 mA DC or 14.5-18.0 V DC
NO 102 b 202 0-20 mA DC (Max. 21 mA DC)
proportional control output and 203 206 206
Heating/cooling control output below. Load resistance 600 Ω or less
COM 103 B 203
Factory default: Control output is relay. Default: 4-20 mA DC
Contact rating: 250 V AC, 3 A Current (mA) input Voltage (mV, V) input
30 V DC, 3 A (resistance load)
Cooling-side control output RET/OUT2
203 202 (Suffix code: Type 1=-2)
Current/voltage pulse output
Can not be used for retransmission output or
Heating/cooling control output 204 203
205 15 V DC loop power supply when
0-20 mA DC, current/voltage pulse output is used.
Heating/cooling relay contact output (Suffix code: Type 1=-2) 4-20 mA DC,
Voltage pulse (12V) Can be used for retransmission output or 15 V
OUT2 Cooling NO
-side 101 E4-terminal area E1-terminal area 206 DC loop power supply when control output is
101 501 401 301 201 not used.
Heating NO Current output range can be changed.
OUT -side 102 -112 -512 -412 -306 -212
101 501 401 301 201
COM 103
Contact rating: 240 V AC, 3 A 102 502 302 202
30 V DC, 3 A (resistance load)
103 503 303 203
Control output OUT (Suffix code: Type1=-0, -1 or -2)
Current/voltage pulse output Retransmission output 15 V DC loop power supply
104 504 304 204
Default: Undefined
105 505 305 205 207
0-20 mA DC, 207 207
4-20 mA DC, 0-20 mA DC, 14.5-18.0 V DC
106 506 306 206 Voltage pulse (12 V) 4-20 mA DC (Max. 21 mA DC)
208 208 208
107 507 407 207
Default: 4-20 mA DC
108 508 408 208
(Equipped Can be used for retransmission output or 15 V DC loop power supply when
Contact output ALM as standard) 109 509 409 current/voltage pulse output is not used for control output.
Current output range can be changed.
External contact output (relay) 110 510 410 210 In Position proportional type, can be used for retransmission output or 15 V
Alarm-3 output UT DC loop power supply.
(PV high limit) 104 111 511 411 211
AL3
112 512 412 212
105 Contact input
Common
DI (Equipped as standard)
Alarm-2 output
( PV low limit)
106 External contact input
AL2 E3-terminal area No-voltage
contact UT Transistor UT
+5V
Common 107 contact DI2
STOP when DI2=ON 210 DI2 210
Alarm-1 output RUN when DI2=OFF +5V
108
(PV high limit) DI1
AL1 AUTO when DI1=ON 211 DI1 211
109 MAN when DI1=OFF
Common COM
Relay contact rating: 240 V AC, 1 A
Position proportional control output VALV Common
212 COM 212
30 V DC, 1 A (resistance load) Relay contact output Feedback input (Suffix code: Type1=-1) Contact rating: 12 V DC, 10 mA or more
HIGH 100% Function can be assigned to the terminals with no function.
(direct) 507 510

Power supply LOW


(reverse) 508 511
100-240 V AC power supply 24 V AC/DC power supply COM 509 0% 512
Heater break alarm HBA (Optional suffix code /HA)
N N Heater current detection input
110 110 Contact rating: 250 V AC, 3A Resistance: 100 Ω to 2.5 kΩ External contact output (transistor)
30 V DC, 3 A UT
L L
111 (resistance load) Feedback input Heater break alarm-1 HAL1 507 510
111 output
Current (mA) CT1
input + 510 Heater break alarm-2
511
112 112 HAL2 508 CT2
output
511 512
Allowable range: (24 V AC/DC power supply: Optional suffix code /DC) Common COM 509 COM
100-240 V AC (±10%)
(free voltage) - 512
50/60 Hz shared Transistor contact rating: 24 V DC, 50 mA
When feedback input is current

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 
E4-terminal area E1-terminal area
301-306 E1-Terminal Area 501-506 E4-Terminal Area
101 501 401 301 201
-112 -512 -412 -306 -212
101 501 401 301 201 Contact input DI (Suffix code: Type 2=2) Contact output DO (Suffix code: Type 2=2)
102 502 302 202 External contact input External contact output
No-voltage UT UT UT
103 503 303 203 contact Transistor contact
COM Factory default: No function DO45 501
104 504 304 204 Common 301 COM 301
+5V
DI11 Factory default: No function DO44 502
105 505 305 205 Factory default: No function 302 DI11 302
+5V
106 506 306 206 DI12 Factory default: No function DO43 503
Factory default: No function 303 DI12 303
+5V
107 507 407 207 DI13
Factory default: No function 304 DI13 304 Factory default: No function DO42 504
108 508 408 208 +5V
DI14
Factory default: No function 305 DI14 305 Factory default: No function DO41 505
109 509 409 +5V
DI15
110 510 410 210 Factory default: No function 306 DI15 306 Common COM 506
111 511 411 211 Contact rating: 12 V DC, 10 mA or more Function can be assigned to the Transistor contact rating: 24 V DC, 50 mA
112 terminals with no function. Function can be assigned
512 412 212
to the terminals with no
function.

E3-terminal area Contact input / Contact output DI/DO (Suffix code: Type 2=1)
External contact input
No-voltage
contact
UT Transistor contact UT 24 V DC loop power supply
COM
Common 301 COM 301
+5V
24 V DC loop power supply
LPS24
DI11 (Optional suffix code /LP)
Factory default: No function 302 DI11 302
+5V + 505
DI12 21.6-28.0 V DC
Factory default: No function 303 DI12 303 (Max. 30 mA DC)
− 506
Contact rating: 12 V DC, 10 mA or more

External contact output Function can be


assigned to the
UT terminals with no
Factory default: No function DO12 304
function.

Factory default: No function DO11 305

Common COM 306

Transistor contact rating: 24 V DC, 50 mA

401-412 E3-Terminal Area

RS-485 communication RS485 Ethernet communication (with gateway function)


RS-485 (Suffix code: 10BASE-T/100BASE-TX ETHR
Type 3=1) RJ45 connector (Suffix code: Type 3=2)
SDB(+) 407

SDA(-) 408
Upper side LED (baud rate)
SG 409 Color Amber
Lit 100M bps
RDB(+) 410 Unlit 10M bps RS-485
Lower side LED (link activity)
RDA(-) 411 RSB(+) 407
Color Green
Lit Linked RSA(-) 408
Blink Active
Unlit Link failure SG 409

PROFIBUS-DP communication (with Modbus master) CC-Link communication (with Modbus master)
VP
PROF DA CC-L
1 Data 390Ω 1
CHK line (Suffix code: Type 3=4) CHK 110Ω (Suffix code: Type 3=3)
2 RxD/TxD-P 2
RDY DB
3 Data 220Ω If the UT is located at the end 3 If the UT is located at
ERR line RxD/TxD-N of a segment for the L ERR the end of a segment
4 4
PROFIBUS
390Ω L RUN for the CC-Link
5 5
communication wiring,
DGND communication wiring,
terminating resistors are terminating resistors
Pin Signal name Description Pin Signal name Description
separately needed. are separately needed.
1 VP +5V bus power These are to be prepared by 1 FG Flame ground These are to be
Data signal users. (390 Ω: 2 pcs. 220 Ω: 2 SLD Shield prepared by users.
2 RxD/TxD-P
(positive data receive/transmit) 1 pc., or an active 3 DG RX/TX signal ground (110 Ω: 1 pc.)
Data signal terminator.) 4 DB RX/TX - signal
3 RxD/TxD-N
(negative data recive/transmit) 5 DA RX/TX + signal
4 DGND Signal ground
LED Lit Unlit
5 SHIELD Shield ground
CHK User profile error/
(red) Address error Normal
LED Lit Unlit
RS-485 RS-485
CHK
(red) User profile error Normal L ERR Communication failure
RSB(+) 407 Normal RSB(+) 407
Normal No power, or (red) (CRC error)
RDY Communicating Communication
(green) successfully failure RSA(-) 408 RSA(-) 408
No carrier
L RUN Normal detected/
ERR Not connected, or
communication Normal SG 409 (green) Communicating successfully Communication SG 409
(red)
failure (flashing) timeout

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 10
Terminal Arrangement for UT32A Single Loop Control
Control output OUT PV input PV (Equipped
as standard) Retransmission output RET (Equipped as standard)
(Suffix code: Type1=-0) Factory default:
Relay contact output TC input RTD input Retransmission output 15 V DC loop power supply Can be used for 15 V DC loop
Terminal wiring differs in Heating/cooling PV input type is power supply when not used for
Default:
NC 101 control and Position proportional control. undefined. A 201 PV retransmission retransmission output.
Refer to the terminals of Position 202 205 205
NO 102 b 202 4-20 mA DC or 14.5-18.0 V DC
proportional control output and 0-20 mA DC (Max. 21 mA DC)
203 206 206
Heating/cooling control output below.
COM 103 B 203 Load resistance 600 Ω or less
Factory default: Control output is relay. Default: 4-20 mA DC
Contact rating: 250 V AC, 3 A Current (mA) input Voltage (mV, V) input
30 V DC, 3 A (resistance load)
Cooling-side control output RET/OUT2
203 202 (Suffix code: Type 1=-2)
Current/voltage pulse output
204 203 Can not be used for retransmission output or 15 V
205 DC loop power suppy when current/voltage pulse
0-20 mA DC,
4-20 mA DC, output is used for control output.
Heating/cooling control output E1-terminal area Voltage pulse (12 V)
206
Can be used for retransmission output or 15 V DC
loop power suppy when control output is not used.
Heating/cooling relay contact output (Suffix code: Type 1=-2) 101 301 201 Current output range can be changed.
Cooling NO -112 -312 -212
OUT2 -side 101
101 301 201
Heating NO
OUT -side 102
102 302 202
COM 103 103 303 203 Control output OUT (Suffix code: Type1=-0, -1 or -2)
Contact rating: 240 V AC, 3 A 104 304 204 Current/voltage pulse output Retransmission output 15 V DC loop power supply
30 V DC, 3 A (resistance load)
Default: Undefined
105 305 205 207
0-20 mA DC, 207 207
106 306 206 4-20 mA DC, 0-20 mA DC, 14.5-18.0 V DC
Voltage pulse (12 V) 4-20 mA DC (Max. 21 mA DC)
208 208
107 307 207 208
Default: 4-20 mA DC
108 308 208
Can be used for retransmission output or 15 V DC loop power suppy when
Contact output ALM (Equipped
as standard)
109 309 current/voltage pulse output is not used for control output.
Current output range can be changed.
External contact output (relay) 110 310 210
In Position proportional type, can be used for retransmission output or 15 V DC
Alarm-3 output UT 111 311 211 loop power supply.
(PV high limit) 104
AL3 112 312 212
Common 105
Alarm-2 output Contact input DI (Equipped as standard)
(PV low limit) 106
AL2 External contact input
Common 107 No-voltage
UT Transistor UT
contact contact +5V
Alarm-1 output STOP when DI2=ON DI2
108 210 DI2 210
(PV high limit) RUN when DI2=OFF +5V
AL1 DI1
AUTO when DI1=ON 211 DI1 211
Common 109 Position proportional control output VALV MAN when DI1=OFF
COM
Relay contact rating: 240 V AC, 1 A Relay contact output Feedback input (Suffix code: Type1=-1) 212 COM 212
30 V DC, 1 A (resistance load) Common
HIGH 100%
(direct) 101 310
Contact rating: 12 V DC, 10 mA or more
Power supply LOW
(reverse) 102 311 Function can be assigned to the terminals with no function.

100-240 V AC power supply 24 V AC/DC power supply (24 V AC/DC power supply: COM 103 0% 312
N N
Optional suffix code /DC) Heater break alarm HBA (Optional suffix code /HA)
110 Contact rating: 240 V AC, 3A Resistance: 100 Ω to 2.5 kΩ
110
30 V DC, 3 A External contact output (transistor) Heater current detection input
L L (resistance load)
111 111 Feedback input UT
Current (mA) Heater break alarm-1 HAL1 307 310
input 310 output CT1
112 112
Heater break alarm-2
311
HAL2 308 CT2
Allowable range: 311 output
100-240 V AC (±10%) 312
Common COM 309 COM
(free voltage) 312
50/60 Hz shared
When feedback input is current Transistor contact rating: 24 V DC, 50 mA

301-306 E1-Terminal Area

RS-485 communication RS485 24 V DC loop power supply


RS-485 (Suffix code: 24 V DC loop power supply
LPS24
Type 2=1) (Suffix code: Type 2=0 and
SDB(+) 301
305 optional suffix code /LP)
21.6-28.0 V DC
SDA(-) 302 (Max. 30 mA DC)
306
SG 303

RDB(+) 304

RDA(-) 305

Contact input / Contact output DI/DO (Suffix code: Type 2=2)


External contact input
No-voltage UT Transistor UT
contact contact
COM
Common 301 COM 301
+5V
DI11
Factory default: No function 302 DI11 302
+5V
DI12
Factory default: No function 303 DI12 303
Contact rating: 12 V DC, 10 mA or more

External contact output Function can be


assigned to the
UT terminals with no
Factory default: No function DO12 304
function.

Factory default: No function DO11 305

Common COM 306

Transistor contact rating: 24 V DC, 50 mA

RS-485 communication/24 V DC loop power supply


RS-485 24 V DC loop power supply RS485/LPS24
RSB(+) 301
(Suffix code: Type 2=1 and
21.6-28.0 V DC
305 optional suffix code /LP)
RSA(-) 302 (Max. 30 mA DC)
306
SG 303

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 11
n External Dimensions and Panel Cutout Dimensions
UT35A
Unit: mm
11
96 65 Bracket
Terminal cover (option)
20

105.2
91.6
94.6
96
Bracket
1 to 10 mm (panel thickness)
• General mounting • Side-by-side close mounting
117 min. [(N-1)×96+92] +0.8
0

92 +0.8
0

(53) 145
min.
“N” stands for the number of controllers to be
installed.
92+0.8
0 However, the measured value applies if N≥5.
Normal tolerance:
92+0.8
0 (25) ±(value of JIS B 0401-1998 tolerance class IT18)/2

UT32A
Unit: mm
11
48 65 Bracket Terminal cover (option)
20
105.2
91.6
94.6
96

Bracket
1 to 10 mm (panel thickness)
• General mounting • Side-by-side close mounting
70 min. [(N-1)×48+45] +0.6
0
+0.8
92 0

145
(53) min.
“N” stands for the number of controllers to be
installed.
92 +0.8
0
However, the measured value applies if N≥5.
Normal tolerance:
45+0.6
0 (25) ±(value of JIS B 0401-1998 tolerance class IT18)/2

n Construction, Mounting, and Wiring UT32A: 48 (width) x 96 (height) x 65 (depth from the
• Dust-proof and drip-proof: IP56 (Front panel) (Except panel surface)
for side-by-side close mounting)/NEMA4 * • Mounting: Direct panel mounting; mounting bracket,
*: Hose down test only one each for upper and lower mounting
• Material: Polycarbonate resin (Flame retardancy: UL94 V-0) • Panel cutout dimensions (mm):
• Case color: Light gray UT35A: 92+0.8/0 (width) x 92+0.8/0 (height)
• Weight: 0.5 kg or less UT32A: 45+0.6/0 (width) x 92+0.8/0 (height)
• External dimensions (mm): • Mounting position: Up to 30 degrees above the hori-
UT35A: 96 (width) x 96 (height) x 65 (depth from the zontal. No downward titling allowed.
panel surface) • Wiring: M3 screw terminal with square washer (signal
wiring and power)

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00
<<Contents>> <<Index>> 12
n Model and Suffix Code
Optional
Model Suffix code suffix Description
code
Digital Indicating Controller (provided with retransmission output or 15 V DC loop power
UT35A
supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC)
-0 Standard type
Type 1:
-1 Position proportional type
Basic control
-2 Heating/cooling type
0 None
Type 2:
1 2 additional DIs, 2 additional DOs
Functions
2 5 additional DIs, 5 additional DOs
0 None
1 RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)
Type 3:
2 Ethernet communication (with serial gateway function)
Open networks
3 CC-Link communication
4 PROFIBUS-DP communication
-1 English
-2 German
Display language (*1)
-3 French
-4 Spanish
0 White (Light gray)
Case color
1 Black (Light charcoal gray)
Fixed code -00 Always "-00"
/LP 24 V DC loop power supply (*2)
/HA Heater break alarm (*3)
Optional suffix codes
/DC Power supply 24 V AC/DC
/CT Coating (*4)
*1: English, German, French, and Spanish can be displayed as the guide display.
*2: The /LP option can be specified in the combination of Type 2 code (any of "0" or "1") and Type 3 code (any of "0" or "1".)
*3: The /HA option can be specified when the Type 1 code is "-0" or "-2."
*4: When the /CT option is specified, the UT35A does not conform to the safety standards (UL and CSA) and CE marking.

Optional
Model Suffix code suffix Description
code
Digital Indicating Controller (provided with retransmission output or 15 V DC loop power
UT32A
supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC)
-0 Standard type
Type 1:
-1 Position proportional type
Basic control
-2 Heating/cooling type
0 None
Type 2:
1 RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) (*2)
Functions
2 2 additional DIs and 2 additional DOs
Type 3:
0 None
Open networks
-1 English
-2 German
Display language (*1)
-3 French
-4 Spanish
0 White (Light gray)
Case color
1 Black (Light charcoal gray)
Fixed code -00 Always "-00"
/LP 24 V DC loop power supply (*2)
/HA Heater break alarm (*3)
Optional suffix codes
/DC Power supply 24 V AC/DC
/CT Coating (*4)
*1: English, German, French, and Spanish can be displayed as the guide display.
*2: The /LP option can be specified in the combination of Type 1 code (any of "-0" or "-1") and Type 2 code (any of "0" or "1.") Ad-
ditionally, when the Type 2 code is "1", the RS-485 communication is 2-wire system.
*3: The /HA option can be specified when the Type 1 code is "-0" or "-2."
*4: When the /CT option is specified, the UT32A does not conform to the safety standards (UL and CSA) and CE marking.

n Items to be specified when ordering n Special Order Items


Model and suffix codes, whether User’s Manual and Model code Suffix code Description
QIC required. LL50A -00 Parameter Setting Software

n Standard accessories
Brackets (mounting hardware), Unit label, Operation
Guide

n Accessory
Name Model Description
UTAP001 For UT35A
Terminal cover
UTAP002 For UT32A
User’s Manual
UTAP003
(CD-ROM)

All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation GS 05P01D31-01EN Jun.11, 2010-00