You are on page 1of 1

CLIENT : A&B DEVELOPMENT CORP .

CONST MANAGEMENT: DUFFILL WATTS & TSE LTD


Add: 149B, Truong Dinh, Ward 9, District 3, HCMC M&E CONSULTANT : INDOCHINE ENGINEERING LTD.
T: +84 8 35260801 F : +84 8 35260800 SERVICE: M&E WORKS
W: www.searefico.com E:hcm@searefico.com
PROJECT: A&B TOWER

REQUEST FOR INFORMATION


REQUESTED BY From : SEAREFICO RFI number : RFI-MEP-07

To : DWT Date issued : 26 Nov 2008

Subject : Provide live weight load information

Details :

As raised at the M&E Coordination Meeting No 4, please kindly provide


information on the allowed load of basement slab and of above basement
slabs i.e kg/m2. We need those info to prepare the method of statement
to move the heavy equipment into the plantrooms. Thank you.

Attachments (if any) :

Date information requested by : Signed :

RESPONSE BY From : DWT

To : SEAREFICO

Details : BASEMENT 500KG/M2

GROUND TO LEVEL 24
200KG/M2

ROOF PLANTROOM 750KG/M2

Date of information response : 7 January 2009 Signed :

RFI CLEARANCE Name : Position : Construction manager

Signed : Date :

Duffill Watts & Tse Ltd, 11b Ngo Van Nam Street, Quality Forms / Request for Approval / QFC 205
District 1, Ho Chi Minh City, Vietnam Revision 3 - 08 March 2006