You are on page 1of 12

EMUA HUAWEI

Protocol Setting of the 4-bit DIP Switch of the


Type SW_ADDR
GSM/CDM 0001
A
WCDMA 0010

0 ON
1 OFF

ON

1 2 3 4
INSTALLATION OF EMUA

DC-PDU

Power utk EMUA dikonek pada port Spare pada DC-PDU

Kabel monitor alarm di konek pada UPEU port MON1

Kabel monitor alarm di konek pada UPEU port MON1


Type : EMUA
Sensor Alarm Box EMU EAC Extended Boolean
LSA Box
DIP Switch Port No. (BTS
Port No. Alarm Description Physical port Scripts)
Number Position
7 Rectifier Failure S1 SW12A_1 disesuaikan 0
4 Heat Detector Active S2 SW12A_2 disesuaikan 1
6 Door Open S3 SW12A_3 disesuaikan 2
1 PLN Power Failure S4 SW12A_4 disesuaikan 3
5 Smoke Alarm S5 SW12A_5 disesuaikan 4
8 DC power too low S7 SW12A_7 disesuaikan 6
2 DC Fan active S8 SW12A_8 disesuaikan 7
Temperature & Humadity DEFAULT SWTHE 1 & 2 ON
Infrared DEFAULT SWBKE_3 OFF
Waterlog DEFAULT SWBKE_1 OFF
3 AC #1
S6 SW12A_6 disesuaikan
9 AC #2
Smoke Alarm DEFAULT SWBKE_2 ON
Access Equipment DEFAULT SWBKE_4 ON
script:
set cbtsenvswtextport:btsid=xxx,portid=0,opmode=def,alminfo="Rectifier Failure",confirm=y;

set cbtsenvswtextport:btsid=xxx,portid=1,opmode=def,alminfo="Heat Detector Active",confirm=y;

set cbtsenvswtextport:btsid=xxx,portid=2,opmode=def,alminfo="Door Open",confirm=y;

set cbtsenvswtextport:btsid=xxx,portid=3,opmode=def,alminfo="PLN Power Failure",confirm=y;

set cbtsenvswtextport:btsid=xxx,portid=4,opmode=def,alminfo="Smoke alarm",confirm=y;

set cbtsenvswtextport:btsid=xxx,portid=6,opmode=def,alminfo="DC Power Too Low",confirm=y;

set cbtsenvswtextport:btsid=xxx,portid=7,opmode=def,alminfo="DC FAN Active",confirm=y;

S4
S8
S6
S2
S5
S3
S1
S7
Sensor Relay SW_BKE DIP switch status DIP switch status
Water Log Sensor NC SW_BKE_1 OFF enable ON disable
Smoke Detect Alarm NC SW_BKE_2 ON enable
Infrared NC SW_BKE_3 OFF enable ON disable
Door Open NC SW_BKE_4 ON enable OFF disable
Water Log

dari kiri kekanan:

putih, hijau, merah, konek ke water sensor


Temperature & Humadity

T+ T- RH+ RH-
Infra Red

_ + R

TAMP NC
PS48180-1800-X6

2
Jumper
2
3

3
LSA Box Port 7

For Implementation Only used 4 Relays. There are :

Relay 1 : Power Failure / AC Mains LSA Box Port No 8


Relay 2 : High / Under Voltage
Relay 3 : Rectifier Failure / Rectifier module broken
Relay 4 : BLVD

Censors EAC Box


LSA Box
Relay DIP Switch
Port No. Alarm Description Port
Position Number Position
7 Rectifier Failure NC S1 SW12 A1 up
8 DC Power Too Low NC S7 SW12 A7 up