Project : 1X60MW Krishna Godavari Power Project

Client : Krishna Godavari Power Utilities Ltd


Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
1.0 Pre – Treatment Filters

1.0 Manufacturer

Country of origin

Number of Units
Water throughput rate per
unit
Maximum m3/h
Design m3/h
Minimum m3/h
Type of vessel/tank
construction
Materials of vessel/tank
construction
Thickness of vessel/tank mm
lining
Dimensions
straight side length mm
straight side thickness mm
dished end thickness mm
Diameter mm
overall height above floor mm

Design pressure bar g

Design code

Inlet pressure
maximum (dirty) bar g
minimum (clean) bar g
Pressure drop in service at
design rate, including
top/bottom
distributors
maximum (dirty) bar g
minimum (clean) bar g
Filter bed surface area per m2
unit
Filtration service rate
Maximum m3/m2/h

Page 1 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Design m3/m2/h
Minimum m3/m2/h
Service period between h
cycles
Wash cycle

Drain down duration min

Air scour
Pressure mbar g
Rate Nm3/m2/
min

Duration min

Backwash
Quantity m3
Rate Nm3/m2/
min
Duration min
Water source

Rinse
Quantity m3
Rate Nm3/m2/
min
Duration min
Water source

Filtered water used per m3


wash
Waste water per wash m3

Inlet distributor
Type

Materials of construction

Under drain system


Type

Materials of construction

Page 2 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Surface wash system
Type

Materials of construction

Air distribution system


Type

Materials of construction

Type of filter material

Depth of filter mm
Size of grading of filter mm
material
Type of supporting bed
material
Supplier of supporting bed
material
Depths/size grading of mm
support bed material
2.0 Pre-Treatment of raw water

Coagulant

Name
Chemical formula as
supplied
Concentration as supplied –
wt/wt or wt/vol.
Concentration as injected.
wt/wt or wt/vol.
Consumption per unit
Maximum kg/h
Design kg/h
Minimum kg/h

Dosing rate
Maximum mg/l
Design mg/l
Minimum mg/l

Injection point location


Contact time before
flocculating chamber
a) Maximum s

Page 3 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
b) Design s

c) Minimum s

3.0 Cation Exchangers


Manufacturer

Country of origin

Number of Units
Water throughput rate per
unit
Maximum m3/h
Design m3/h
Minimum m3/h
Materials of vessel
construction
Materials of vessel lining

Thickness of vessel lining mm

Dimensions
Straight side length mm
Straight side thickness mm
Dished end thickness mm
Diameter mm
Overall height above floor mm

Design pressure bar g

Design code
Ion exchange bed surface m2
area per unit
Ion exchange bed depths mm

Total resin volume m3

Active resign volume m2


Ion exchange resin
designation
Service rate
Maximum m3/m2/h
Design m3/m2/h

Page 4 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Minimum m3/m2/h
Pressure drop in service at
design rate including
mbar
top/bottom
distributors
Design net output between
m3
regeneration
Service period between
regeneration cycles
Maximum flow h
Design flow h
Minimum flow h
Type of regeneration
procedure
Regeneration Cycle:

Air Scour
Pressure mbar g
Quantity Nm3
Rate Nm3/m2/
min
Duration min

1st backwash
Quantity m3
Rate Nm3/m2/
min
Duration Min
Water source

1st Acid Injection


Acid

Acid strength %wt/vol


Quantity of acid/resin g/l
Quantity of solution m3
Rate Nm3/m2/
min
Duration min

Page 5 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Water source

2nd Acid Injection


Acid strength %wt/vol
Quantity of acid @ 100% kg
Quantity of acid/resin g/l
Quantity of solution m3
Rate Nm3/m2/
min
Duration min

Water source

Displacement
Quantity m3
Rate Nm3/m2/
min
Duration min
Water source

Rinse
Quantity m3
Rate Nm3/m2/
min
Duration min
Water source

Total time for regeneration min


cycle
Total quantity of water used
per regeneration
cycle
Source/quantity /m3
Source/quantity /m3
Total wastewater per m3
regeneration cycle
Inlet distributor
Type

Page 6 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Materials of construction

Under drain system


Type

Materials of construction

Acid injection system


Type

Materials of construction

Acid draw off system


Type

Materials of construction

Air distributor system


Type

Materials of construction

Resin compaction system


Type

Materials of construction

Resin traps
Number off

Location

Shell material

Diameter mm
Design pressure bar g
Design code

Strainer mesh size mm

4.0 Cation Exchangers – Resin


Performance Particulars
Manufacturer of resin
Design Capacity g. CaCO3
per litre

Useful life years

Attrition loss per annum:-

Page 7 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Up to 6 years % vol
After 6 years % vol
Capacity loss per annum at
design regeneration
levels
Up to 6 years g. CaCO3
per litre
After 6 years g. CaCO3
per litre

Guaranteed life of resin years

5.0 Anion Exchangers

Manufacturer

Country of origin

Number of Units
Water throughput rate per
unit
Maximum m3/h
Design m3/h
Minimum m3/h
Materials of vessel
construction
Materials of vessel lining

Thickness of vessel lining mm

Dimensions
straight side length mm
straight side thickness mm
dished end thickness mm
diameter mm
overall height above floor mm

Design pressure bar g

Design code
Ion exchange bed surface m2
area per unit
Ion exchange bed depths mm

Total resin volume m3

Page 8 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Active resign volume m3
Ion exchange resin
designation
Service rate
Maximum m3/m2/h
Design m3/m2/h
Minimum m3/m2/h
Pressure drop in service at
design rate including
mbar
top/bottom
distributors
Design net output between
m3
regeneration
Service period between
regeneration cycles
Maximum flow

Design flow

Minimum flow

Type of regeneration
procedure
Regeneration Cycle:

Air Scour
Pressure mbar g
Quantity Nm3
Rate Nm3/m2/
min

1st backwash
Quantity m3
Rate Nm3/m3/
min
Duration min
Water source

1st Alkali Injection


Alkali

Alkali strength % wt/vol.


Quantity of alkali kg.

Page 9 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Quantity of alkali/resin g/l
Quantity of solution m3
Rate Nm3/m2/
min
Duration min
Water source

Displacement
Quantity m3
Rate Nm3/m3/
min
Duration min
Water source

2nd Backwash
Quantity m3
Rate m3/m3/mi
n
Duration min
Water source

Rinse
Quantity m3
Rate m3/m2/mi
n
Duration min
Water source

Total time for regeneration min


cycle
Total quantity of water used
per regeneration
cycle
Source/quantity /m3
Source/quantity /m3
Total wastewater per m3
regeneration cycle
Inlet distribution
Type

Page 10 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Materials of construction

Under drain system


Type

Materials of construction

Alkali injection system


Type

Materials of construction

Alkali draw off system


Type

Materials of construction

Air distributor system


Type

Materials of construction

Resin compaction system


Type

Materials of construction

Resin traps
Number off

Location

Shell material

Diameter mm
Design pressure Bar g
Design code

Strainer mesh size mm

6.0 Anion Units – Resin


Performance Particulars
Manufacturer of resin

g. CaCO3
Design Capacity
per litre

Useful life years

Attrition loss per annum:-

Page 11 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Up to 6 years % vol.
After 6 years % vol.
Capacity loss per annum at
design regeneration
levels
Up to 6 years g. CaCO3
per litre
After 6 years g. CaCO3
per litre

Guaranteed life of resin years

7.0 Mixed Bed Exchangers

Manufacturer

Country of origin

Number of Units
Water throughput rate per
unit
Maximum m3/h
Design m3/h
Minimum m3/h
Materials of vessel
construction
Materials of vessel lining

Thickness of vessel lining mm

Dimensions
straight side length mm
straight side thickness mm
dished end thickness mm
diameter mm
overall height above floor mm

Design pressure bar g

Design code
Ion exchange bed surface m2
area per unit
Ion exchange bed depths
anion resin mm

Page 12 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
cation resin mm
inert resin mm

Total resin volume m3

Active resin volume m3


Ion exchange resin
designation
Anion

Cation

Inert

Service rate
Combined

Maximum m3/m3/h
Design m3/m3/h
Minimum m3/m3/h
Anion

Maximum m3/m3/h
Design m3/m3/h
Minimum m3/m3/h
Cation

Maximum m3/m3/h
Design m3/m3/h
Minimum m3/m3/h
Pressure drop in service at
design rate including
mbar
top/bottom
distributors
Design net output between
m3
regeneration
Service period between
regeneration cycles
Maximum flow h
Design flow h
Minimum flow h
Type of regeneration
procedure

Page 13 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Regeneration Cycle:

Drain down duration min

Air Scour
Pressure mbar g
Quantity m3
Rate m3/m3/mi
n
Duration min
Water source

Backwash
Quantity m3
Rate m3/m3/mi
n
Duration min
Water source

Alkali Injection
Alkali

Alkali strength % wt/vol.


Quantity of alkali kg.
Quantity of alkali/resin g/l
Quantity of solution m3
Rate m3/m3/mi
n
Water source

1st Alkali rinse


Quantity m3
Rate m3/m3/mi
n
Duration min
Water source

2nd Alkali rinse


Quantity m3

Page 14 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Rate m3/m3/mi
n
Duration min

Acid Injection
Acid

Acid strength % wt/vol.


Quantity of acid kg.
Quantity of acid/resin g/l
Quantity of solution m3
Rate m3/m3/mi
n
Duration min
Water source

1st Acid Rinse


Quantity m3
Rate m3/m3/mi
n
Duration min
Water source

2nd Acid Rinse


Quantity m3
Rate m3/m3/mi
n
Duration min
Water source

Drain down duration min

Air Mix
Pressure

Quantity m3
Rate

Duration min

Unit refill

Page 15 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Quantity m3
Rate m3/m3/mi
n
Duration min
Water source

Final Rinse
Quantity m3
Rate m3/m3/mi
n
Duration min
Water source

Total time for regeneration min


cycle
Total quantity of water used
per regeneration
cycle
Source/quantity /m3
Source/quantity /m3
Total wastewater per m3
regeneration cycle
Inlet distribution
Type

Materials of construction

Under drain system


Type

Materials of construction

Alkali injection system


Type

Materials of construction

Alkali draw off/acid


injection system
Type

Materials of construction

Air distributor system


Type

Page 16 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Materials of construction

Resin compaction system


Type

Materials of construction

Resin traps
Number off

Location

Shell material

Diameter mm
Design pressure mbar g
Design code

Strainer mesh size mm

8.0 Mixed Bed Exchangers – Resin


Performance Particulars
Manufacturer of resin

g. CaCO3
Design Capacity
per litre

Useful life years

Attrition loss per annum:-


Up to 4 years % vol.
After 4 years % vol.
Capacity loss per annum at
design regeneration
levels
g. CaCO3
Up to 4 years per litre
total base

g. CaCO3
Up to 4 years per litre
strong

g. CaCO3
After 4 years per litre
total

Page 17 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
g. CaCO3
per litre
After 4 years
strong
base

Guaranteed life of resin Years

9.0 Regeneration and Waste


Effluent Particulars
Weight of 100% acid
used/m3 net to kg
service
Weight of 100% alkali
used/m3 net to kg
service
Amount of waste effluent
m3
developed
Typical chemical analysis of
% wt/vol.
waste effluent
Na2SO4 PPM
Na Cl

Ca SO4

Ca SO2

Mg SO4

Mg Cl4

10.0 Ejectors

Number off

Manufacturer

Material

Type

Design Code

Design Pressure bar g

Size mm
Internal Corrosion
Treatment
11.0 Regeneration, Hold and Waste
Tanks
Type/V/H/R

Number off

Dimensions

Page 18 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Diameter mm
Straight side length mm
Straight side thickness mm
Dished end thickness mm
Base thickness mm
Roof thickness mm
Height of top above floor mm
level
Type of vessel/tank
construction
Materials of vessel lining mm

Chemical handled

Effective working capacity

Mixer
Type

Material of construction

Speed rpm
Reduction gear box type kW
Note:-
V-Vertical Cylindrical
H-Horizontal Cylindrical
R-Rectangular
Filter Backwash Pump

12.0 Degassed Water Pumps

Manufacturer

Type and Model Number

Number of Pumps

Number of Stages

Speed rpm
Discharge capacity at duty m3/hr
point
Generated head at duty m
point
N.P.S.H. required at duty
m
point

Page 19 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Power absorbed at duty
kW
point
Rated power of motor kW
Pump efficiency at duty
%
point
Overall pump & motor
efficiency at duty %
point
Minimum flow rate m3/h

Suction branch bore mm

Discharge branch bore mm

Flange specification/rating
Weight of pump set
kg
complete
13.0 Waste Regeneration Pumps

Manufacturer

Type and Model Number

Number of Pumps

Number of Stages

Speed rpm
Discharge capacity at duty m3/hr
point
Generated head at duty m
point
N.P.S.H. required at duty
m
point
Power absorbed at duty
kW
point
Rated power of motor kW
Pump efficiency at duty
%
point
Overall pump & motor
efficiency at duty %
point
Minimum flow rate m3/h

14.0 Degasser Blower

Type / manufacturer

No. of sets

Capacity Nm3/h

Page 20 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

SL NO VENDOR TO
DESCRIPTION UNITS QTY
FURNISH
Discharge pressure bar g

Rate power of driver kW

Type of suction filter

Multi-grade filter
Technical Specification
Type : Cylindrical, vertical, mild steel

Page 21 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

Vessel design standard : IS 2825 or ASME Sec. VIII Div.1

Capacity of each filter : To be sized for continuous clarified water


Pump rated flow connected to the respective
stream with not more than ¼ hr back wash per
day.

Maximum operating Pressure : 5 kg/cm² (g)

Design Temperature : 50°C

Material of construction : As per IS 2062

Minimum shell thickness : 6 mm + corrosion allowance

Corrosion Allowance : 3 mm

Minimum free board : 50%

Water outlet Turbity : max. 1.00 NTU

Internal coating : Two coats of epoxy

External coating : Two coats of enamel

Dished end : Semi ellipsoidal

Man hole : One

Backwash : Once in 12 hrs backwash

Filter air blowers

Quantity : Two (2) sets blowers for filter air scouring


Capacity : As required (each 100% duty)
Type : Motor driven

b) Filter backwash pump

Quantity : Two (2) pumps


Capacity : As required against 10m head (each 100%
duty)
Type : Horizontal, motor driven

a) Filter water tank of appropriate capacity for backwashing of filters.

Page 22 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

Ultra Filtration

MOC : PAN / PS
Design flux, lt/m2/hr : 80

Reverse Osmosis

MOC : Polyamide
Design flux, lt/m2/hr : 25

Mixed bed Ion Exchanger


Design : IS 2825 or Sec VIII Div.1

Type : Vertical, dished end (Semi ellipsoidal)


, steel welded vessel

No. of units : One for each stream

Design Pressure : 6.5 kg/cm² (g)

Temperature : 50°C

Internal Rubber lining : 4.5 mm thk (1.5 x 3 layers)


As per IS 4682 Part – I

External surface : Two coat of epoxy paint

Free board : 120%

Resin type : Cation and anion resin as required for


SAC & SBA exchanger

Method of regeneration : Silica leakage <0.02 ppm as SiO2


Regeneration water requirement : Conductivity <0.2 micro Siemens/cm
Guaranteed effluent quality : pH – 6.8 to 7.2

Accessories / Instruments
Material of construction : IS 2062

Minimum shell thickness : 6 mm

Pressure required at the outlet


of MB : 2.5 kg/cm² (g)

Resin derating 10%

Page 23 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

Quantity 3
Capacity 4.5 cu.m / hr
Regeneration Co / Counter current after
48 Hours
Surface flow rate,  45
M 3 /M 2 hr
Free board 100%
Material of Carbon steel, IS: 2062, rubber lined as per IS:
Construction 4682, Part-I,
4.5 mm thick min.
Accessories Inspection window, sight glass, resin trap,
manhole,
frontal piping with valves

Resin type Strong acid cation and


strong base anion
Type-I

11.4.6 Mixed bed blower

Type : Rotary, twin lobe, motor driven

No. of units : Two

Head & flow : Bidder to specify.

Material of construction : CI

The blower and motor shall be mounted on a common base frame.


Degasser
Type : Forced draft

No. of units : One for each stream

Capacity of each tower : Supplier to specify

Design Pressure : Atmospheric

Temperature : 50°C

Material of construction : Carbon steel

Internal Rubber lining : 4.5 mm thk (1.5 x 3 layers as per


IS 4682 Part-I)

External surface : Two coat of epoxy paint

Packing : Polypropylene rasching rings or

Page 24 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

Pall rings

Minimum air requirement : Supplier to specify

Guaranteed effluent quality : Supplier to specify

Minimum shell thickness : 6 mm

Mounting / foundation
Requirement : preferably mounted on top of permeate
water tank

11.4.4 Degasser blower


Type : Horizontal, Centrifugal, motor driven

No. of blowers : Two (one working & one standby)

Air flow rate of each blower : As per degasser requirement

Head (minimum) : 5% margin shall be added on the


Maximum Dynamic head required.

Material of construction of blower: Carbon steel

Intake filters, dampers, doors Etc.: Carbon steel

The blower and motor shall be mounted on a common base frame. If blowers are
belt driven minimum no. belt -3nos shall be used.

UF-RO-MB Plant

The scheme and the capacity of the plant is indicated below:

UF-RO-MB Plant

Net output per cycle, 216 (Tenderer to confirm)


per stream, cu m

Service cycle 48 hrs service + 4 hrs regeneration


for MB

Description of Three (3) streams of MGF–Ultra


Scheme Filtration RO-Degasser-MB (2W +
1S)

3.2 UF Permeate

Page 25 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

Colloidal silica rejection at U.F outlet, 95 (min.)


%
Suspended solids, PPM NIL
SDI <3
U.F Recovery, % 90 (min.)

R.O Permeate

Colloidal silica, ppm Nil


TDS, ppm < 20 ppm
RO recovery 75%(min)

Degasser Tower

CO 2 as CaCO 3 at outlet < 5 ppm max.

DM Water Quality shall be

The quality of DM water at mixed bed outlet shall be as follows :

Conductivity, s/cm 0.2 max. at 25 degree C


Silica as SiO 2 , ppm 0.02 ( Max.)
(Reactive & non reactive)
pH 6.8 to 7.2
Iron, PPM NIL
Copper, PPM NIL
Total CO 2 , PPM NIL
Free chlorine, PPM NIL
Oil, PPM NIL
Total suspended solids, ppm NIL

RO/DM plant operation shall be PLC based with manual operated valves.

Page 26 of 27
Project : 1X60MW Krishna Godavari Power Project
Client : Krishna Godavari Power Utilities Ltd
Document Title : Data Sheet for Water treatment plant
Document Number : Rev. No P

Page 27 of 27