Pressure-Relief Damper
Halton BRD pressure-relief dampers are used in offshore and • Closed damper fullfils the leakage requirement of NORSOK.
marine applications to prevent backflow through ventilation Leakage class of closed damper according to EN 1751 class 2
ductwork system. The Halton pressure relief dampers do not (VTT test report no. RTE4306/04)
need an actuator or motor. The BRD dampers can be installed • Blades linked and open in parallel
in rectangular or circular ducts horizontally or vertically. Opening • Opening pressure adjusted by changing the position of
pressure can easily be set by adjusting weight of each damper/ counterweight(s)
installation. Weights are included in the delivery. Pressure relief • Opening pressure range between 30 Pa and 150 Pa (up to 300
dampers can be supplied with non-standard dimensions on Pa optional)
request. • Counterweights included
• Standard construction places weights on the right hand side,
• Fixed frame in painted, galvanized or stainless steel. Blades of weights on the left hand side available as an option
galvanized or stainless steel. • Final adjustment of counterweights carried out during
• Models for horizontal or vertical installation commissioning
• Blades contain silicone seal to lower the leakage through • Maximum duct pressure for damper construction 5000 Pa and
blades maximum air velocity 15 m/s. In case of high duct pressure,
• ATEX approved contact Halton Marine for finding the most suitable solution.
185 IF H=200
20 IF H>200
WIDTH+4 130
nx150 nx150 Min 50
27
nx150 Min 50
HEIGHT+58
HEIGHT+58
HEIGHT+4
HEIGHT+4
AIRFLOW
nx150150
252 (442)*
10
150
185 IF H=200
185 IF H=200
20 IF H>200
20 IF H>200
WIDTH+58 130
nx150 nx150 Min 50
Min 50
DIAMETER-2
HEIGHT+58
nx150
AIRFLOW AIRFLOW
DIAMETER-2
HEIGHT+58
nx150
operation area
185 IF H=200
20 IF H>200
AIRFLOW
364 (454*)
190 * THIS DIMENSION AS OPTION 190
WHEN ACTUATING MECHANISM
NEEDS TO BE INSIDE DAMPER
DEPTH