You are on page 1of 55

Post installed rebar

connections

Post installed rebar connections


Basics of post installed rebar connections
Hilti HIT-RE 500 post installed rebar
Hilti HIT-HY 150 post installed rebar
Hilti HIT- HY 150 MAX post installed rebar

6 / 2010 677
Basics of post installed
rebar connections

Basics of post installed rebar connections


1 Applications
1.1 Advantages of post-installed rebar connections
With the use of the Hilti-HIT injection systems it is possible to connect new reinforcement to
existing structures with maximum confidence and flexibility.
• design flexibility • reliable like cast in • horizontal, vertical and
overhead
• form work • defined load • simple, high confidence
simplification characteristics application

1.2 Application examples


Post installed rebar connections are widely used within the construction industry in a wide range
of applications, which vary from new construction projects, to structure upgrades and
infrastructure requalifications.

Post-installed rebar connections in new construction projects


Diaphragm walls Slab connections

Misplaced bars Vertical/horizontal connections

678 6 / 2010
Basics of post installed
rebar connections

Post-installed rebar connections in structure updgrades


Wall strenghtening New slab constructions

Joint strenghtening Cantilevers/balconies

Post-installed rebar connections in infrastructure requalifications


Slab widening Structural upgrade

Slab strenghtening Side-walk upgrade

6 / 2010 679
Basics of post installed
rebar connections

2 Rebar basics
2.1 Definition of rebar
Rebar is standing for REinforcement BAR. At Hilti the word is used for a reinforcement bar
inserted into a borehole filled with Hilti HIT in reinforced concrete structures, in other words for
post-installed reinforcement. Post-installed reinforcement can be split up into four different main
applications:
• Good detailing practice
• Shear studs
• Rebar as structural rebar
• Rebar as an anchor

In the course of the Anchor FTM the focus will be on the last two types of applications.
Chapter 3, “Adhesive Anchoring Systems”, deals with rebar as an anchor. The current chapter
focuses on rebar as structural rebar, where the reinforcement is purely loaded in the longitudinal
direction.

lv
l0

lbd

≥ 10 ds
lbd

Figure 2.1: Example of structural rebar application

Structural rebar is characterized by very high loads. The reinforcement is often loaded up to
steel yielding. The concrete structure (connection) shows a good serviceability. The
deformations are small and due to this the crack width and therefore the influences by the
environment (corrosion) are limited. The concrete connections behave as a monolithic structure
or in other words as if the concrete was poured in one go. The high loads which can occur in
either the anchorage or the splice can lead to an embedment length up to 15 till 80 times the
diameter of the reinforcement.
The design can be done according to two design concepts;
• Structural code, for instance EC2 EN 1992-1-1:2004 chapter 8.4 anchorage of
longitudinal reinforcement, based on approvals (e.g. ETA according to EOTA TR023)
See paragraph 4 of this chapter for an overview of the approvals
• Hilti HIT-Rebar design concept, based on the American Standard (ACI 318-08), where
the allowable bond stress is controlled by splitting / spalling behaviour.

For this type of connections an engineer is usually involved in the design.

680 6 / 2010
Basics of post installed
rebar connections

2.2 Rebar as an anchor


Rebar as an anchor is characterized by the fact it is not possible to splice the reinforcement
(due to e.g. lack of useable reinforcement). The loads are typically smaller as in the case of
structural rebar and the serviceability is slightly lower. The anchor failure modes like concrete
cone failure or combined concrete cone and pull-out failure are considered in this application
according to standard anchor design.
For this type of connections an engineer is usually involved in the design.

2.3 Cast-in ribbed bars


Generally, for load transfer in reinforced concrete only tensile or compressive forces in bars are
considered.
For ribbed bars, the load transfer in concrete is governed by the bearing of the ribs against the
concrete (figure 2.3.a). The force reaction in the concrete is assumed to form a compressive
strut in the direction of 45°.
For higher bond stress values, the concentrated bearing forces in front of the ribs cause the
formation of cone-shaped cracks starting at the crest of the ribs. The resulting concrete keys
between the ribs transfer the bearing forces into the surrounding concrete, but the wedging
action of the ribs remains limited. In this stage the displacement of the bar with respect to the
concrete (slip) consists of bending of the keys and crushing of the concrete in front of the ribs.
The bearing forces, which are inclined with respect to the bar axis, can be decomposed into
directions parallel and perpendicular to the bar axis. The sum of the parallel components equals
the bond force, whereas the radial components induce circumferential tensile stresses in the
surrounding concrete, which may result in longitudinal radial (splitting / spalling) cracks.

Figure 2.3.a: Load transfer from ribbed bars into concrete

Two failure modes can be considered:


a) Bond failure (fig. 2.3.a):
If the confinement (concrete cover, transverse reinforcement) is sufficient to prevent splitting of
the concrete cover, bond failure is caused by pull-out of the bar. In that case the concrete keys
are sheared off and a sliding plane around the bar is created. Thus, the force transfer
mechanism changes from rib bearing to friction. The shear resistance of the keys can be
considered as a criterion for this transition. It is attended by a considerable reduction of the
bond stress. Under continued loading the sliding surface is smoothed due to wear and
compaction, which will result in a further decrease of the bond stress, similar to the case of plain
bars.

6 / 2010 681
Basics of post installed
rebar connections

b) Splitting failure (fig. 2.3.b):


If the radial cracks propagate through the entire cover, bond
splitting failure is decisive. In that case the maximum bond stress
follows from the maximum concrete confinement, which is
reached when the radial cracks have penetrated the cover for
about 70%. Further crack propagation results in a decrease of
the confining stresses. At reaching the outer surface these Figure 2.3.b
stresses are strongly reduced, which results in a sudden drop of
the bond stress.

2.4 Lapped bar splices


2.4.1 Model for load transfer at lapped bar splices
The load transfer between bars is performed by means of compressive struts in the concrete
(fig. 2.4.1). A 45° truss model is assumed. The resulting perpendicular forces act in a similar
way as the splitting forces. The splitting forces normally are taken up by the transverse
reinforcement. Small splitting forces are attributed to the tensile capacity of the concrete. The
amount of the transverse or tie reinforcement necessary is specified in the design codes.

Figure 2.4.1: Load transfer at lap splices

2.4.2 Influence of spacing and cover on splitting and spalling of concrete


In most cases the reinforcement bars are placed close to the surface of the concrete member to
achieve good crack distribution and economical bending capacity. For splices at wide spacing
(normally in slabs, fig. 2.4.2a), the bearing capacity of the concrete depends only on the
thickness of the concrete cover. At narrow spacing (normally in beams, fig. 2.4.2.b) the bearing
capacity depends on the spacing and on the thickness of the cover. In the design codes the
reduction of bearing capacity of the cover is taken into account by means of multiplying factors
for the splice length.

Figure 2.4.2.a Figure 2.4.2.b


Splitting Spalling

2.4.3 Bond behaviour of post-installed ribbed bars


The load transfer for post-installed bars is similar to cast in bars if the stiffness of the overall
load transfer mechanism is similar to the cast-in system. The efficiency depends on the strength
682 6 / 2010
Basics of post installed
rebar connections

of the adhesive mortar against the concentrated load near the ribs and on the capacity of load
transfer at the interface of the drilled hole.
In many cases the bond values of post-installed bars are higher compared to cast in bars due to
better performance of the adhesive mortar. But for small edge distance and/or narrow spacing
splitting or spalling forces become decisive due to the low tensile capacity of the concrete.

3 Design basics
3.1 Rebar design methods

Post-installed reinforcement connections can basically be designed in compliance with the


national codes. Hilti is offering two design methods of which one is based on the Eurocode 2
(EC2 EN 1992-1-1:2004) and the other one on the American Standard (ACI 318-08). The most
important characteristics will be explained in the following paragraphs.

3.2 Rebar design according to EC2/ETA approach

The new technical report EOTA – TR 023 (Assessment of post-installed rebar connections)
establishes a common method to qualify chemical anchors in compliance with EC2. Chemical
anchors must comply with a predefined step-diagram for the different concrete classes (Figure
3.2: Chemical anchors without limitations). In general it shall be shown by the tests as described
in the TR 023 that the post-installed rebar systems can develop the same design values of bond
resistance with the same safety margin as cast-in place rebars according to EC2. In EC2 no
requirements for testing are given, but the values for fbd are published.
These values are valid for worst case conditions, minimum concrete cover, minimum spacing
and minimum transverse reinforcement.
In Figure 3.2 a comparison is given which bond resistance in the tests and evaluation according
TR 023 have to be reached (on y- axis) to show equivalence with the values fbd (on x- axis).
A European Technical Approvals according to the EOTA TR023 allows a design according to
EC2. However a design for fire resistance, fatigue, dynamic or seismic loading are excluded.
The ETA for Rebar proves that approved systems are robust and durable. Influences of bad
cleaning, wet holes, creep, freeze/thaw, durability, corrosion resistance, installation directions
are tested within the approval.
The post-installed rebar connections assessed according to TR 023 shall be designed as
straight cast-in reinforcement according to EC2 using the values of the design bond resistance
fbd for deformed bars. The definition of the bond region in EC2 is valid also for post-installed
reinforcement. The conditions in EC2 concerning detailing (e.g. concrete cover in respect to
bond and corrosion resistance, bar spacing, transverse reinforcement) shall be complied with.

6 / 2010 683
Basics of post installed
rebar connections

Figure 3.2: Chemical anchors without limitations from EOTA TR023

The following additional provisions have to be taken into account.


• To prevent damage of the concrete during drilling the following requirements have to be
met:
cmin = 30 + 0,06lv ≥ 2ds (mm) for hammer drilled holes, with ds being the
diameter of the rebar
cmin = 50 + 0,08lv ≥ 2ds (mm) for compressed air drilled holes
The factors 0,06 and 0,08 take into account the possible deviations during the drilling
process. This value might be smaller if special drilling aid devices are used.
• Minimum clear spacing between two post-installed rebars a = 40 mm ≥4ds
• To account for potentially different behaviour of post-installed and cast-in rebars in
cracked concrete, in general, the minimum embedment length lb,min and l0,min given in
EC2 for anchorages and overlap splices shall be increased by a factor of 1,5. This
increase may be neglected if it can be shown that the bond strength of the selected post-
installed rebars and cast-in rebars in cracked concrete (w = 0,3 mm) is similar. In this
case the influence of cracks openings (crack movement tests) can be neglected because
for rebar connections several rebars are present (redundant fastening) and not all of the
rebars will be situated in a longitudinal crack.
The transfer of shear forces between new and old concrete shall be designed according to EC2.
See also paragraph 3.4 “strut-and-tie model”.
The reader is referred to the paragraph 4 “EC2 Design” for more detail about this design
concept.

684 6 / 2010
Basics of post installed
rebar connections

3.3 Hilti HIT-Rebar design and ACI 318-08 approach

The American Standard ACI (American Concrete Institute) 318-08 gives an explicit formula for
the design of anchorages and splices that considers splitting and spalling as a function of
concrete cover and bar spacing. This function is adapted and extended for post-installed
reinforcement for the Hilti HIT-Rebar design concept. The embedment length of an anchorage
or splice is defined as a function of concrete strength, the bar diameter, the minimum edge
distance or spacing and a coefficient taking into account the transverse reinforcement.
In figure 3.3 a typical design bond stress fbd curve as a function of the minimum edge
distance/spacing distance, cd is shown for a concrete class C20/25 and for a rebar with a
diameter of 12 mm (EC2/ETA approach). In this figure the equivalent design bond stresses
resulting from the ACI and the EC2/ETA approaches are plotted to illustrate the two methods
(the design bond stresses shown in the figure shall not be used for design purposes). The
reduction of anchoring length allowed by ACI and EC2/ETA in specific conditions can be
assimilated to an increase of the equivalent design bond stress if cd changes within certain
limits. The equivalent design bond stress is defined by an inclined line and it increases with
larger values of cd. The increase in the design bond stress is limited by the maximum pull-out
bond stress, which is a value which is given by the standards in the case of a cast-in
reinforcement. For post-installed reinforcement, the maximum design bond stress is a function
of the bonding agent and not necessarily equals that of cast-in bars. Thus, the limitation for
bond failure in the code has been replaced by the specific design bond stress of the bonding
agent for the specific application conditions and the splitting function has been adapted
according to the tests.

8.0
7.0 6.9 N/mm2
6.0
5.0
fbd

4.0
3.0 3.3 N/mm2
2.0 cd = min(a/2, c, c1)
1.0
0.0
0 10 20 30 40 50 60 70 80 90 100 110
cd,min ACI 318-08 approach
cd
C20/25, Ø = 12 mm EC2/ETA approach

Figure 3.3: equivalent design bond stress f bd as a function of cd., derived from reduction of anchoring lenght
according to ACI 318-08 and EC2/ETA.

6 / 2010 685
Basics of post installed
rebar connections

Interaction of concrete cover and transverse reinforcement (splitting reinforcement)

Tests show that transverse reinforcement improves the splitting capacity. Transverse
reinforcement can be taken into account by adding a substitute value for the cover.
The ACI 318-08 code explicitly takes into account the influence of transverse reinforcement able
to prevent splitting by means of the “transverse reinforcement index” Ktr.
c + K tr A tr ⋅ f yt c + K tr
f bd = f ck ⋅ K tr = ; ≤ 2.5 for cast - in bars
4 ⋅φ ⋅ξ ; 10.34 ⋅ s ⋅ n φ

with: Atr total cross-sectional area of all transverse reinforcement that is within the spacing
s and that crosses the potential plane of splitting through the reinforcement being
developed [mm2]
fyt yield strength of transverse reinforcement [N/mm2]
s maximum spacing of transverse reinforcement within b, center to center [mm]
n number of bars being developed along the plane of splitting [-]
ξ substitute for various adjustment factors

Hilti HIT-Rebar design concept

c + K tr
for ≤ 2.5 (post-installed reinforcement and cast-in reinforcement):
φ
f ck c + K tr
f bd = ⋅
4⋅γ φ

c + K tr
for > 2.5 (bonded-in bars only):
φ
f ck   c + K tr 
f bd = ⋅ 2.5 + 0.75 ⋅  − 2.5  
4⋅γ   φ 
where:
fbd design bond strength
φ nominal bar size
fck characteristic concrete cylinder strength
c = cd = min(a/2, c, c1)
Ktr see above
γ bar size factor

For more detailed Information see: Kunz, J.; Münger, F.: “Splitting- and bond failure of post-installed rebar splices
and anchoring.”; Bond in Concrete – from research to standards, Proceedings of the 3rd International Symposium
held at the Budapest University of Technology and Economics, Budapest, Hungary, 20 to 22 November 2002,
p.447 -454. (Copy available from Hilti Technical Service)

686 6 / 2010
Basics of post installed
rebar connections

3.4 Strut-and-tie model


Crack limitation Compression cord and strut
The tensile bearing capacity of (concrete)
concrete is very low compared to
its compressive strength. For this
Joint to be
reason tensile forces are attributed roughened
to the steel reinforcement of the
concrete member. The
reinforcement should be
adequately anchored in the nodes Tension cord Tension ties
{Clause 6.5.3(2), EC2: EN 1992-1-
1:2004}. Figure 3.4: Strut-and-tie-model
A strut-and-tie model is used to calculate the load path in reinforced concrete members. Where
a non-linear strain distribution exists (e.g. supports) strut-and-tie models may be used {Clause
6.5.1(1), EC2: EN 1992-1-1:2004}.
Strut-and-tie models consist of struts representing compressive stress fields, of ties
representing the reinforcement and of the connecting nodes. The forces in the elements of a
strut-and-tie model should be determined by maintaining the equilibrium with the applied loads
in ultimate limit state. The ties of a strut-and-tie model should coincide in position and direction
with the corresponding reinforcement {Clause 5.6.4, EC2: EN 1992-1-1:2004 Analysis with strut
and tie models}.

3.5 Joint to be roughened

The model of inclined compressive struts is used to transfer the shear forces through the
construction joint at the interface between concrete cast at different times. Therefore a rough
interface is required to provide sufficient cohesion in the construction joint {Clause 6.2.5(2),
EC2: EN 1992-1-1:2004}. Rough means a surface with at least 3 mm roughness (Rt > 3 mm),
achieved by raking, exposing the aggregate or other methods giving an equivalent behaviour.

3.6 Anchorage of reinforcement

The reinforcement has to be anchored at places where it is no longer needed. These situations
may occur:
• when the load path of the tensile force has ended (e.g. support, figure 3.6.a)
• at curtailment of reinforcement (see figure 3.6.b)
• compression bar anchorage (see figure 3.6.c).

6 / 2010 687
Basics of post installed
rebar connections

Figure 3.6.b: Figure 3.6.c:


Figure 3.6.a: Tensile force has ended Compression
Support, truss

3.7 Lapped splice of reinforcement

Lapped splices are used to achieve continuity in the tensile tie of the truss
model at construction joints. The load from one bar to the other is transferred
by means of compressive struts in the concrete. A 45°-truss model is
assumed.
The resulting splitting force (design bond stress) is limited to a value
depending on the surface characteristics of the reinforcement, the tensile
strength of the concrete and confinement of surrounding concrete. This
depends on sufficient concrete cover, spacing of bar, transverse pressure
and by the transverse reinforcement {Clause 6.6, EC2: EN 1992-1-1:2004}. Figure 3.7: Lapped splice

4 EC2 design
4.1 General
The actual position of the reinforcement in the existing structure shall be determined on the basis of the
construction documentation and taken into account when designing. The transfer of shear forces between new
concrete and existing structure shall be designed according to EC2 EN 1992-1-1:2004. See also paragraph 3.4
“Strut-and-tie model” The joints for concreting must be roughened to at least such an extent that aggregate
protrude. See also paragraph 3.5 “Joint to be roughened”.

The design of post-installed rebar connections and determination of the internal section forces to be transferred in
the construction joint shall be verified in accordance with EC2 EN 1992-1-1:2004. When ascertaining the tensile
force in the rebar, allowance shall be made for the statically effective height of the bonded-in reinforcement. See
also paragraph 5.2 “Example with overlap joint”

688 6 / 2010
Basics of post installed
rebar connections

4.2 Determination of the basic anchorage length


The calculation of the required anchorage length shall take into consideration the type of steel and bond properties
of the reinforcement.

The required basic anchorage length lb,rqd shall be determined in accordance with clause 8.4.3, EC2:
EN1992-1-1:2004:

lb,rqd = (ds / 4) (σsd / fbd)

with: ds = diameter of the rebar


σsd = calculated design stress of the rebar
f bd = design value of bond strength according to corresponding ETA, in consideration of the
coefficient related to the quality of bond conditions and, of the coefficient related to the bar
diameter and of the drilling technique. Refer to the relevant approval or technical data
sheet for details.

4.3 Determination of the design anchorage length

The required design anchorage length lbd shall be determined in accordance with clause 8.4.4, EC2: EN 1992-1-
1:2004:
lbd = α1 α2 α3 α4 α5 lb,rqd ≥ lb,min

Where α1, α2, α3, α4 and α5 are coefficients given in Table 4.1.

α1 is for the effect of the form of the bars assuming adequate cover
(post-installed reinforcement is always straight)

α2 is for the effect of concrete minimum cover

α 2 = 1 − 0,15 (c d − d 0 )/d 0
straight bars; c d = min (a/2 ; c 1 ; c )

With no edge distance, α2 = 0,7 if the spacing given in the table below are fulfilled:
ds (mm) 8 10 12 14 16 18 20 22 24 25 26 28 30 32 34 36 40
Spacing (mm) 56 70 84 98 112 126 140 154 168 175 182 196 210 224 238 252 280
a (mm) 48 60 72 84 96 108 120 132 144 150 156 168 180 192 204 216 240

α3 is for the effect of confinement by transverse reinforcement

α4 is for the influence of one or more welded transverse bars along the design
anchorage length lbd. (no welded transverse reinforcement possible with post-
installed reinforcement)

α5 is for the effect of the pressure transverse to the plane of splitting along the
design anchorage length.
The product (α2α3α5) ≥ 0,7

6 / 2010 689
Basics of post installed
rebar connections

lb,rqd = according to section 5.2


lb,min = minimum anchorage length according to clause 8.4.4, EC2: EN 1992-1-1:2004
= max {0.3 lb,rqd; 10ds; 100 mm} under tension
= max {0.6 lb,rqd; 10ds; 100 mm} under compression
(Please note that the minimum anchorage length may be increased by factor 1,5 according
to EOTA TR023, § 4.2. Refer to the relevant approval or technical data sheet for details.)

Table 4.1: Values of α1, α2, α3, α4 and α5 coefficients


Influencing factor Type of anchorage Reinforcement bar
In tension In compression
Shape of bars Straight α1 = 1.0 α1 = 1.0
Concrete cover Straight α2 = 1 – 0.15(cd – α2 = 1.0
ø)/ø
≥ 0.7
≤ 1.0
Confinement by Straight α3 = 1 – Kλ α3 = 1.0
transverse ≥ 0.7
reinforcement ≤ 1.0
Confinement by Straight α4 = 1.0 α4 = 1.0
welded transverse
reinforcement
Confinement by Straight α5 = 1 – 0.04p -
transverse pressure ≥ 0.7
≤ 1.0
where:
λ = (ΣAst - ΣAst,min)/ As
ΣAst cross-sectional area of the transverse reinforcement along the design anchorage length lbd
ΣAst,min cross-sectional area of the minimum transverse reinforcement = 0.25 As for beams and 0 for slabs
As area of a single anchored bar with maximum bar diameter
K values shown in Figure 4.10
p transverse pressure [MPa] at ultimate limit state along lbd

Figure 4.3 : Values of K for beams and slabs

4.4 Overlap joints


Forces are transmitted from one bar to another by lapping the bars. The detailing of laps between bars shall be
such that:
- the transmission of the forces from one bar to the next is assured
- spalling of the concrete in the neighbourhood of the joints does not occur
- large cracks which affect the performance of the structure do not occur

690 6 / 2010
Basics of post installed
rebar connections

Laps between bars should not be located in areas of high moments / forces (e.g. plastic hinges) and at any section
normally be arranged symmetrically. The arrangement of lapped bars should comply with Figure 4.4. The clear
distance between lapped bars should be ≤ 4ø and ≤ 50 mm, otherwise the lap length should be increased by a
length equal to the clear space where it exceeds 4ø or 50 mm.

≥ 3ø

Figure 4.4: Adjacent laps

The required design lap length l0 shall be determined in accordance with clause 8.7.3, EC2: EN 1992-1-1:2004:
l0 = α1 α2 α3 α5 α6 lb,rqd ≥ l0,min
with: lb,rqd = according to section 4.2
l0,min = minimum lap length = max {0.3α6 lb,rqd; 15ds; 200 mm}
(Please note that the minimum anchorage length may be increased by factor 1,5
according to EOTA TR023, § 4.2. Refer to the relevant approval or technical data sheet for
details.)
Values of α1, α2, α3 and α5 may be taken from Table 4.1; however, for the calculation of α3, ΣAst,min should be taken
as 1,0 As(σsd/fyd), with As = area of one lapped bar.

α6 = (ρ1/25)0.5 but neither not exceeding 1,5 nor less than 1,0, where ρ1 is the percentage of reinforcement lapped
within 0.65l0 from the centre of the lap length considered. Values of α6 are given in Table 4.2. (Note: For post-
installed rebar applications α6 = 1,5 for the majority of the cases)

Table 4.2: Values of the coefficient α6


Percentage of lapped bars < 25% 33% 50% > 50%
relative to the total cross-
section area
α6 1 1,15 1,4 1,5

4.5 Embedment depth for overlap joints


Overlap joint for rebars:
For calculation of the effective embedment depth of overlap joints the concrete cover at end-face of the post-
installed rebar c1 shall be considered:
lv ≥ l0 + c1
with: l0 = required lap length according to paragraph 4.4.
c1 = concrete cover at end-face of bonded-in rebar. See Figure 4.5

6 / 2010 691
Basics of post installed
rebar connections

Figure 4.5: Concrete cover c1

If the clear distance between the overlapping bars is greater than 4ds the lap length shall be enlarged by the
difference between the actual clear distance and 4ds.

4.6 Concrete cover

The minimum concrete cover required for bonded-in rebars is shown in the ETA approvals in relation to the drilling
method and the hole tolerance. Furthermore the minimum concrete cover given in clause 4.4.1.2, EC2: EN 1992-1-
1: 2004 shall be observed.

4.7 Transverse reinforcement

The requirements of transverse reinforcement in the area of the post-installed rebar connection shall comply with
clause 8.7.4, EC2: EN 1992-1-1:2004.

4.8 Connection joint


In case of a carbonated surface of the existing concrete structure the carbonated layer shall be removed in the
area of the post installed rebar connection with a diameter of ds + 60 mm prior to the installation of the new rebar.
The depth of concrete to be removed shall correspond to at least the minimum concrete cover for the respective
environmental conditions in accordance with EC2: EN 1992-1-1:2004.

692 6 / 2010
Basics of post installed
rebar connections

5 Design examples
5.1 Anchorage: End support of slab, simply supported

h = 300

• 2
slab: ln = 6,50 m, Qk = 5 kN/m ,h = 300 mm,d = 260 mm
wall: h = 300 mm
d = 260 h = 300 • Concrete strength class: C20/25, dry concrete
• Properties of reinforcement: fyk = 500 N/mm2
• Short-term/long-term temperature is 20°C
• Fire resistance: F90 (90 minutes)
a1 = 130 al = 260 • Loads: Gd = 1,35 x 7,5 = 10,1 kN/m²;
Qd = 1,5 x 5,0 = 7,5 kN/m²
ln = 6,50 m
⇒ = 17,6 kN/m²

Structural analysis (design forces) based on leff:


MSd = 17,6 x 6,762 / 8 = 100,5 kNm/m
VSd = 17,6 x (6,76 / 2) = 59,5 kN/m

Bottom reinforcement required at mid span:


A s,req = 100,5 x 1,15 / (0,26 x 0,9 x 0,5) = 988 mm²/m
⇒ reinforcement provided: ∅16, s = 200 mm;
A s,prov = 1010 mm²/m

Bottom reinforcement at support:


As,min = 0,4 x 1 x 2,2 x 150 x 1000 / 500 = 264 mm²/m {Clause 7.3.2(2), EC2: EN 1992-1-1:2004}
2
As,min = 0,50 x 988 = 494 mm /m {Clause 9.3.1.2(1), EC2: EN 1992-1-1:2004}

{Clause 9.3.1.1(4), EC 2: EN 1992-1-1:2004} ⇒


As,min = 0,25 x 988 = 247 mm²/m {Clause 9.2.1.4(1), EC2: EN 1992-1-1:2004}
2
As,req = 59,5 x 1 / 0,9 x 1,15 / 0,5 = 152 mm /m (al =d) {Clause 9.2.1.4(2), EC2: EN 1992-1-1:2004}
Decisive is 494 mm²/m ⇒ reinforcement provided: ∅12, s = 200 mm; A s,prov = 565 mm²/m

a) Anchorage according to European Technical Approval (ETA) 08/0105, Post-installed


rebar connections with Hilti injection mortar HIT-RE 500
Determination of the basic anchorage length

The required basic anchorage length lb,rqd shall be determined in accordance with EC2: EN 1992-1-1:2004, section
8.4.3:
lb,rqd = (ds / 4) x (σsd / fbd)
with: ds = diameter of the rebar = 12 mm
σsd = calculated design stress of the rebar = (494 / 565) x (500 / 1,15) = 380 N/mm²
f bd = design value of bond strength according to corresponding ETA = 2,3 N/mm²
lb,rqd = (12 / 4) x (380 / 2,3) = 496 mm

6 / 2010 693
Basics of post installed
rebar connections

Determination of the design anchorage length


The required design anchorage length lbd shall be determined in accordance with EC2: EN 1992-1-1:2004, section
8.4.4:
lbd = α1 α2 α3 α4 α5 lb,rqd ≥ lb,min
with: lb,rqd as above
α1 = 1,0 for straight bars
α2 = 1 – 0,15(cd – ø)/ø
α2 is for the effect of concrete minimum cover ≥ 0,7 ≤ 1,0
a = 200 – 12 = 188 mm
a/2 = 94 mm with c1 and c > 94 mm
ø = 12 mm
α2 = 0,7 Straight bars, cd = min (a/2, c1, c)

α3 = 1,0 because of no transverse reinforcement


α4 = 1,0 because of no welded transverse reinforcement
α5 = 1,0 influence of transverse pressure is neglected in this example

lbd = 0,7 x 496 = 347 mm

2/3lbd = 231 mm ⇒ 230 mm


lb,min = minimum anchorage length
{Clause 8.4.4(1), EC2: EN 1992-1-1:2004}
= max {0,3 x 496; 10 x 12; 100} = 149 mm

b) Anchorage according to Hilti HIT-Rebar design method (splitting):

Reinforcement provided: ∅12, s = 200 mm; A s,prov = 565 mm²/m


Mortar: Hilti HIT-RE 500
FSd = 494 x 0,5 / 1,15 = 214,8 kN/m

Steel:
FRd = 5 x (fyk x π x ∅² x ¼) / γs = 245,9 kN/m > 214,8 kN/m ok

Concrete (splitting) / Mortar (pull-out):


Due to large edge distances in all directions (confined concrete) the failure mode splitting of
concrete is not becoming decisive, but the pull out failure mode: fbd = 6.9 N/mm2

FRd = n(lbd x ∅ x π x fbd) = 5(lbd x 12 x π x 6.9) = 214.8 kN/m


⇒ lbd = 165 mm
lb,min = 120 mm (10 x ∅) ok

Fire resistance:
Fire rating class F 90 (90 min.) (design table see paragraph 4.7):

FsT,req = 0,6 x 66,1 = 39,7 kN/m = 7,9 kN/bar {Clause 2.4.3 (4) and (5), EC2: ENV 1992-1-2:1995}

Hilti HIT-RE 500: ∅12 ⇒ linst = 14,5 cm; Fs,T = 6,02 kN


linst = 18 cm; Fs,T = 15,0 kN

694 6 / 2010
Basics of post installed
rebar connections

Intermediate values may be interpolated linearly: linst = 16,5 cm; Fs,T = 11,2 kN/bar > 7,9 kN/bar

⇒ linst = 165 mm

Top reinforcement

300
Top reinforcement at support:
Minimum reinforcement:
25% of bottom steel required at mid-span
d = 260 h = 300 {Clause 9.3.1.2(2), EC2: EN 1992-1-1:2004}
As,req = 0,25 x 988 = 247 mm2/m
2
As,min = 0,4 x 1 x 2,2 x 150 x 1000 / 500 = 264 mm /m
{Clause 7.3.2(2), EC2: EN 1992-1-1:2004}
a1 = 130 al = 260

ln = 6.50 m Decisive is 264 mm²/m


⇒ reinforcement provided: ∅12, s = 300 mm; A s,prov = 377 mm²/m

a) Anchorage according to European Technical Approval (ETA) 08/0105, Post-installed


rebar connections with Hilti injection mortar HIT-RE 500

Determination of the basic anchorage length

The required basic anchorage length lb,rqd shall be determined in accordance with EC2: EN 1992-1-1:2004, section
8.4.3:
lb,rqd = (ds / 4) x (σsd / fbd)
with: ds = diameter of the rebar = 12 mm
σsd = calculated design stress of the rebar = (264 / 377) x (500 / 1.15) = 304 N/mm²
f bd = design value of bond strength according to corresponding ETA = 2,3 N/mm²
lb,rqd = (12 / 4) x (304 / 2,3) = 397 mm
Determination of the design anchorage length

The required design anchorage length lbd shall be determined in accordance with EC2: EN 1992-1-1:2004, section
8.4.4:
lbd = α1 α2 α3 α4 α5 lb,rqd ≥ lb,min
with: lb,rqd as above
α1 = 1,0 for straight bars
α2 = 1 – 0,15(cd – ø)/ø
α2 is for the effect of concrete minimum cover ≥ 0,7 ≤ 1,0
a = 300 – 12 = 288 mm
a/2 = 144 mm with c1 and c > 144 mm
ø = 12 mm
⇒ 0,7
α3 = 1,0 because of no transverse reinforcement
α4 = 1,0 because of no welded transverse reinforcement
α5 = 1,0 influence of transverse pressure is neglected in this example
lbd = 0,7 x 397 = 278 mm ⇒ 280 mm Can be critical with drilling!
lb,min = minimum anchorage length {Clause 8.4.4(1), EC2: EN 1992-1-1:2004}
= max {0.3 x 397; 10 x 12; 100} = 120 mm ok

6 / 2010 695
Basics of post installed
rebar connections

b) Anchorage according to Hilti HIT Rebar Design Method (CC-Method):

Reinforcement provided: ∅12, s = 300 mm; A s,prov = 377 mm2/m


Mortar: Hilti HIT-RE 500

A s,min = 264 mm2/m

Design Load:
FSd = A s,min ⋅ fyk/γs
= 264 x 500 / 1.15 = 114.8 kN/m

Fbd = Fsd ⋅ s/1000


= 114.8 kN/m ⋅ 300/1000 = 34.4 kN/bar

Steel Verification:
FRd = 1000mm  f yk ⋅ π ⋅ φ 2 ⋅ 1 
s γ 4 
 s
= 1000  500 ⋅ π ⋅ 122 ⋅ 1  = 163.9kN / m > 114.8kN / m  Steel ok!
300  1.15 4

Combined pull-out and concrete cone failure:


Ap,N
N Rk ,p = N Rk
0
,p ⋅ ⋅ψ s ,Np
Ap0,N
τ Rk F ⋅γ
,p = π ⋅ φ ⋅ l bk ⋅ ⇒ l bd = bd Mc
0 0 0
N Rd
γ Mp π ⋅ φ ⋅ τ Rk

34.4 ⋅ 2.1 (τRk from approval ETA-04/0027; table 13)


0
l bd = = 127.9mm
π ⋅ 12 ⋅ 15

Ap0,N = scr ,Np ⋅ scr ,Np = 115200mm2

0 .5
τ 
scr ,Np = 20φ  Rk ,ucr  ≤ 3 ⋅ hef
 7.5 

0.5
 15 
= 20 ⋅ 12  = 339.4 ≤ 3 ⋅ 127.9 = 383.7mm
 7. 5 

ccr ,Np = 0.5scr ,Np = 169 .7mm

c > c cr ,Np ; s < s cr ,Np

A p,N = s (c cr ,Np + 0.5s cr ,Np ) = 300 ⋅ 339 .4 = 101820 mm 2

c
ψ s ,Np = 0.7 + 0.3 ⋅ ≤ 1 → ψ s,Np = 1.0
c cr ,Np

Fbd ⋅ Ap0,N 34.4 ⋅ 115200


lbd ( po & cc ) = = = 144.5mm
τ 15
π ⋅ φ ⋅ Rk ⋅ Ap,N ⋅ ψ s,Np π ⋅ 12 ⋅ ⋅ 101820 ⋅ 1.0
γ Mp 2.1

696 6 / 2010
Basics of post installed
rebar connections

Concrete cone failure:

Ac,N
N Rk ,c = N Rk
0
,c ⋅ ⋅ψ s,N
Ac0,N
2
 Fbd  3

N 0
= k 1 f ck ,cube h 1.5
⇒l 0
=  ⋅ γ Mc
Rk ,c ef bd
k f 
 1 ck ,cube 

k1 = 7.2  cracked concrete


k1 = 10.1  uncracked concrete

2
 34.4  3
l 0
bd =   ⋅ 1.5 = 116.1mm
 10.1 ⋅ 25 

s cr ,N = 3hef = 3 ⋅ 116.1 = 348.3; c cr ,N = 174.15mm

A0c,N= 121312.9mm2

c > c cr ,N ; s < s cr ,N

Ac ,N = s (c cr ,N + 0.5s cr ,N ) = 300 ⋅ 348 .3 = 104490 mm 2

c
ψ s ,Np = 0.7 + 0.3 ⋅ ≤ 1 → ψ s,Np = 1.0
c cr ,Np

2
2
 Fbd  3
A0 c,N 1  34.4  3
121312 .9 1
l bd ( cc ) =  ⋅ ⋅ ⋅ γ Mc =   ⋅ ⋅ ⋅ 1.5 = 134 .8mm
 k1 ⋅ fck ,cube  Ac,N ψ s,N  10 .1⋅ 25  104490 1.0
 

Splitting failure:

only needed if c≥ 1.2ccr,sp and h≥ 2hmin:

h/hef = 300mm / 144.5mm = 2.08; ccr,sp = 1.0hef= 144.5mm

c > 173.4mm  ok

hmin = max(hef+30mm; hef+2d0) = max(174.5; 176.5) = 176.5mm

h=300mm ≥ 353mm  not true, verification needed!!!

Ac,N
N Rk ,sp = N Rk
0
,sp ⋅ ⋅ψ s,N ⋅ψ h,sp
Ac0,N

A0c,N= 83521mm2

scr,sp = 289mm

c > c cr ,N ; s < s cr ,N

Ac,N = s (c cr ,N + 0.5s cr ,N ) = 300 ⋅ 289 = 86700 mm 2

6 / 2010 697
Basics of post installed
rebar connections

c
ψ s ,Np = 0.7 + 0.3 ⋅ ≤ 1 → ψ s,Np = 1.0
c cr ,Np
2 2
 h  3
 300  3
ψ h,sp =   =  = 1.42
 hmin   176.5 

2
 2h  3
1 ≤ ψ h,sp ≤  ef  = 1.39
 hmin 

ψ h,sp = 1.39

2
2
 Fbd  3
A0c,N 1  34 .4  3
83521 1
l bd ( sp ) =  ⋅ ⋅ ⋅ γ Mc =   ⋅ ⋅ ⋅ 1.5 = 80 .5 mm
 k1 ⋅ fck ,cube  Ac,N ψ s,N ⋅ψ h,sp  10 .1 ⋅ 25  86700 1.0 ⋅ 1 .39
 

Embedment depth to use:

lbd = max[lbd(pp&cc); lbd(cc); lbd(sp)]

lbd = 144.5mm ≥ 10ø = 120mm  ok

5.2 Example with overlap joint


lv • Bending moment: MSd = 120 kNm/m
l0 slab: h = 300 mm; d = 250 mm, cs = 50 mm
30
• Concrete strength class: C25/30,
cs = 50 • Properties of reinforcement: fyk = 500 N/mm²
30 • Fire resistance: F60 (60 minutes),
h = 300
d = 250 Light weight plaster for fire protection: 30 mm

• top reinforcement: ∅16, s = 150 mm; As,prov = 1340 mm²/m


cover to face c1 = 30 mm
≥ 10 ∅ • bottom reinforcement: ∅10, s = 200 mm; As,prov = 393 mm²/m
• Note: reduced load in cast-in bar due to lever arm: η = 250 / 270 = 0,93

a) Overlap joints according to European Technical Approval (ETA) 08/0105, Post-installed


rebar connections with Hilti injection mortar HIT-RE 500

Post-installed reinforcement
The required design lap length l0 shall be determined in accordance with EC2: EN 1992-1-1:2004, section 8.7.3:
l0 = α1 α2 α3 α5 α6 lb,rqd ≥ l0,min
with: lb,rqd the basic anchorage length, lb,rqd = (ds / 4) x (σsd / f bd)
ds = diameter of the rebar = 16 mm
σsd = calculated design stress of the rebar
d = 250 mm, z ≈ 0,9 x 250 = 225 mm
As,req = 120 x 1,15 / (0,225 x 0,5) = 1227 mm2/m
σsd = (1227 / 1340) x (500 / 1,15) = 398 N/mm2
2
f bd = design value of bond strength according to corresponding ETA = 2,7 N/mm

698 6 / 2010
Basics of post installed
rebar connections

lb,rqd = (16 / 4) x (398 / 2.7) = 590 mm


α1 = 1,0 for straight bars
α2 = 1 – 0,15(cd – ø)/ø
α2 is for the effect of concrete minimum cover ≥ 0,7 ≤ 1,0
c = 50 - 8 = 42 mm cd = 42 mm
ø = 16 mm
⇒ 0,76
α3 = 1,0 because of no transverse reinforcement
α5 = 1,0 influence of transverse pressure is neglected in this example
α6 = 1,5 influence of percentage of lapped bars relative to the total cross-section area
{Clause 8.7.3(1), EC2: EN 1992-1-1:2004}
l0 = 0,76 x 1,5 x 590 = 673 mm ⇒ 675 mm
l0,min = minimum lap length {Clause 8.7.3(1), EC2: EN 1992-1-1:2004}
= max{0.3 x 1.5 x 590; 15 x 16; 200} = 266 mm ok

Cast-in reinforcement
l0 = α1 α2 α3 α5 α6 lb,rqd ≥ l0,min
with: lb,rqd the basic anchorage length, lb,rqd = (ds / 4) x (σsd / f bd)
ds = diameter of the rebar = 16 mm
σsd = calculated design stress of the rebar
d = 270 mm, z ≈ 0,9 x 270 = 243 mm
As,req = 120 x 1,15 / (0,243 x 0,5) = 1136 mm2/m
σsd = (1136 / 1340) x (500 / 1,15) = 369 N/mm2
f bd = design value of bond strength according to corresponding ETA = 2,7 N/mm2
lb,rqd = (16 / 4) x (369 / 2.7) = 547 mm

α2 = 1 – 0,15(cd – ø)/ø
α2 is for the effect of concrete minimum cover ≥ 0,7 ≤ 1,0
c = 30 - 8 = 22 mm cd = 22 mm
ø = 16 mm
⇒ 0,94
l0 = 0,94 x 1,5 x 547 = 771 mm ⇒ 770 mm Cast-in reinforcement is decisive!
l0,min = minimum lap length {Clause 8.7.3(1), EC2: EN 1992-1-1:2004}
= max{0,3 x 1,5 x 547; 15 x 16; 200} = 246 mm ok

Embedment depth for overlap joints for rebars:


lv ≥ l0 + c1
with: l0 = required lap length = 770 mm (see above)
c1 = concrete cover at end face of cast-in rebar = 30 mm
lv = 800 mm
If the clear distance between the overlapping rebars is greater than 4ds (4 x 16 = 64 mm) the lap length shall be
enlarged by the difference between the clear distance and 4ds.
Most unfavorable case post-installed rebar is located right in the middle between the cast-in rebars. The clear
distance between the overlap is: s22 = a – Ø1/2 – Ø2/2 ; a = (752 + 202)1/2
⇒ s22 = 77,6 mm – 8 mm – 8 mm = 61,6 mm
61,6 < 64 ⇒ lv = 800 mm

6 / 2010 699
Basics of post installed
rebar connections

b) Overlap joints according to Hilti HIT-Rebar design method (splitting):

Post-installed reinforcement
Reinforcement provided: ∅16, s = 150 mm; A s,prov = 1340 mm²/m
Mortar: Hilti HIT-RE 500
FSd = 1340 x 398 = 533,3 kN/m (see above)

Steel:
FRd = 6,66(f yk x π x ∅2 x ¼) / уs = 582,2 kN/m > 533,3 kN/m ok

Mortar (pull-out):
fbd = 7,1 N/mm2
  c + K tr 
f c'  2.5 + 0.75 − 2.5  
 φ
Concrete (splitting):
 
(c + Ktr) / ∅ = 3.1 > 2.5 ⇒ fbd is calculated f bd = according
with: c = min{c, s/2} = 50 mm 4γ
Ktr = 0
∅ = 16 mm
f c' = compressive strength of concrete = 25 N/mm2 for C25/30
γ = reinforcement size factor = 0.8 for ∅18
2
⇒ fbd = 4,6 N/mm

Due to edge distances (c = 50 mm) and spacing (s = 150 mm) the failure mode splitting of
concrete is decisive.

α6 = 1,5 ⇒ fbd = 3,1 N/mm2 {Clause 8.7.3(1), EC2: EN 1992-1-1:2004}


FRd = n(l0 x ∅ x π x fbd) = 6.66(l0 x 16 x π x 3,1) = 533,3 kN/m
⇒ l0 = 514 mm

Cast-in reinforcement
(as above)
l0 = 770 mm Cast-in reinforcement is decisive!

Embedment depth for overlap joints for rebars:


lv = 800 mm

Fire resistance:
Fire rating class F 60 (60 minutes) (design table see paragraph 4.7):
Clear concrete cover including light weight plaster: c = 4 + 3 = 7 cm
FsT,req = 0.6 x 120 / 0,225 = 320 kN/m = 48 kN/bar {Clause 2.4.3 (4) und (5), EC2: ENV 1992-
1-2:1995}
τT,req = 48000 / (16 x π x 770) = 1,2 N/mm2
Hilti HIT-RE 500: τT = 1,0 N/mm2 < 1,2 N/mm ⇒ increase plaster to 4 cm ⇒ c = 8 cm, τT = 1,4 N/mm ok
2 2

700 6 / 2010
Basics of post installed
rebar connections

6 Corrosion behavior
The Swiss Association for Protection against Corrosion (SGK) was given the assignment of evaluating the
corrosion behavior of fastenings post-installed in concrete using the Hilti HIT-HY 150, Hilti HIT-HY 150 MAX and
Hilti HIT-RE 500 injection systems.

Corrosion tests were carried out. The behavior of the two systems had to be evaluated in relation to their use in
field practice and compared with the behavior of cast-in reinforcement. The SGK can look back on extensive
experience in this field, especially on expertise in the field of repair and maintenance work.
The result can be summarized as follows:

Hilti HIT-HY 150 + Hilti HIT-HY 150 MAX


• The Hilti HIT-HY 150 and Hilti HIT-HY 150 MAX systems in combination with reinforcing bars can be
considered resistant to corrosion when they are used in sound, alkaline concrete. The alkalinity of the
adhesive mortar safeguards the initial passivation of the steel. Owing to the porosity of the adhesive mortar,
an exchange takes place with the alkaline pore solution of the concrete.
• If rebars are bonded-in into chloride-free concrete using this system, in the event of later chloride exposure,
the rates of corrosion are about half those of rebars that are cast-in.
• In concrete containing chlorides, the corrosion behavior of the system corresponds to that of cast-in rebars.
Consequently, the use of unprotected steel in concrete exposed to chlorides in the past or possibly in the
future is not recommended because corrosion must be expected after only short exposure times.

Hilti HIT-RE 500


• If the Hilti HIT-RE 500 system is used in corrosive surroundings, a sufficiently thick coat of adhesive
significantly increases the time before corrosion starts to attack the bonded-in steel.
• The HIT-RE 500 system may be described as resistant to corrosion, even in concrete that is carbonated and
contains chlorides, if a coat thickness of at least 1 mm can be ensured. In this case, the unprotected steel in
the concrete joint and in the new concrete is critical.
• If the coat thickness is not ensured, the HIT-RE 500 system may be used only in sound concrete. A rebar may
then also be in contact with the wall of the drilled hole. At these points, the steel behaves as though it has a
thin coating of epoxy resin.
• In none of the cases investigated did previously rusted steel (without chlorides) show signs of an attack by
corrosion, even in concrete containing chlorides.
• Neither during this study an acceleration of corrosion was found at defective points in the adhesive nor was
there any reference to this in literature. Even if a macro-element forms, the high resistance to it spreading
inhibits a locally increased rate of corrosion.
• Information in reference data corresponds with the results of this study.

7 Fire design
If passive fire prevention requirements have to be met, the suitability of rebar connections should be verified
additionally to ULS cold design.

Large-area building components (walls and floors) can be verified according to tables 1 and 2. The design tables
are derived from tests at the University / IBMB Braunschweig following the Standard ISO 834 temperature/time
curve. Design for fire resistance is carried out in line with several specific standards. On the following pages only
the fire data for Standard according EC2 are given.
Details to all available Standards and specific reports are named below the following tables.

Note for the following tables 1 to 6: Fs,T = force in bar when exposed to fire.
Intermediate values may be interpolated linearly. Extrapolating is not permitted.

6 / 2010 701
Basics of post installed
rebar connections

Hilti HIT-HY 150 rebar

Bar perpendicular to slab or wall surface exposed to fire


Temperature time curve (acc. ISO 834)

linst

Table 1: Maximum force in rebar in conjuction with HIT-HY 150 as a function of embedment depth for the
a)
fire resistance classes F30 to F180 (yield strength fyk = 500 N/mm²) according EC2
Drill
Bar ∅ F30 F60 F90 F120 F180
hole ∅
linst FS,T linst FS,T linst FS,T linst FS,T linst FS,T
[mm] [mm]
[mm] [kN] [mm] [kN] [mm] [kN] [mm] [kN] [mm] [kN]
120 10,6 120 5,0 120 2,8 120 1,9 120 0,7
140 14,1 140 8,4 140 4,5 140 3,3 140 1,5
150 15,6 160 11,9 160 7,9 160 5,2 160 2,7
8 10
180 15,4 180 11,4 180 8,6 200 5,3
190 15,6 200 14,9 200 12,1 240 9,6
210 15,6 220 15,6 280 15,6
150 19,8 150 12,7 150 1,7 150 5,1 150 2,6
160 22,0 160 14,9 160 9,9 160 6,5 160 3,3
180 24,3 180 19,3 180 14,3 180 10,7 180 4,9
10 12
200 23,7 200 18,7 200 15,1 220 8,5
210 24,3 220 23,1 220 19,5 260 16,4
230 24,3 250 24,3 300 24,3
180 31,7 180 23,1 180 17,1 180 12,9 180 5,9
200 35,1 200 28,4 200 22,4 200 18,1 200 8,0
12 16 220 33,7 220 27,7 220 23,4 240 14.,4
230 35,1 240 32,9 240 28,7 280 24,9
250 35,1 270 35,1 320 35,1
210 46,2 210 36,2 210 29,2 210 24,2 210 10,6
220 47,7 220 39,3 220 32,2 220 27,3 220 11,9
14 18 240 45,4 240 38,4 240 33,5 240 16,8
250 47,7 260 44,6 260 39,6 280 29,1
270 47,7 280 45,8 320 41,4
290 47,7 350 47,7
240 62,3 240 51,9 240 43,9 240 38,3 240 19,2
260 59,0 260 51,0 260 45,3 280 33,2
16 20 270 62,3 280 58,0 280 52,3 320 47,3
300 62,3 300 59,4 360 61,4
310 62,3 370 62,3
300 97,4 300 91,3 300 81,3 300 74,3 300 50,3
320 97,4 320 90,1 320 83,0 320 59,1
20 25 340 97,4 340 91,8 360 76,7
360 97,4 400 94,3
410 97,4

702 6 / 2010
Basics of post installed
rebar connections

Drill
Bar ∅ F30 F60 F90 F120 F180
hole ∅
linst FS,T linst FS,T linst FS,T linst FS,T linst FS,T
[mm] [mm]
[mm] [kN] [mm] [kN] [mm] [kN] [mm] [kN] [mm] [kN]
375 152,2 375 152,2 375 142,9 375 134,0 375 104,1
380 145,6 380 136,7 380 106,9
25 32 400 152,2 400 147,7 400 117,9
410 152,2 440 139,9
470 152,2
Remark: The minimum setting depth is related to l > 15 x ds
a)
For tables according British- and Singapore Standard (resistance class up to F240) see Warringtonfire report WF
166402 or/and IBMB Braunschweig report No 3162/6989 (including supplements).

Hilti HIT-HY 150 rebar


Bar connection parallel to slab or wall surface exposed to fire

Max. bond stress, τT , depending on actual clear concrete cover for classifying the fire
resistance.
It must be verified that the actual force in the bar during a fire, Fs,T , can be taken up by the bar
connection of the selected length, linst. Note: Cold design for ULS is mandatory.
Fs, T ≤ (linst – cf)⋅ ∅ ⋅ π ⋅ τT where: (linst – cf) ≥ ls;

ls = lap length
∅ = nominal diameter of bar
linst – cf = selected overlap joint length; this must be at least ls,
but may not be assumed to be more than 80 ∅
τT = bond stress when exposed to fire
Temperature time curve (acc. ISO 834)

linst cf

Table 2: Critical temperature-dependent bond stress, τcrit,T, concerning “overlap joint” for Hilti-HIT-HY 150
injection adhesive in relation to fire resistance class and required minimum concrete coverage c.
Clear concrete cover c Max. bond stress, τT [N/mm²]
[mm] F30 F60 F90 F120 F180
20 0,7 0
30 1,4 0,2 0
0
40 1,9 0,7
0
50 2,4 1,2 0,4
60 2,8 1,7 0,7 0,3
70 4,9 2,2 1,2 0,7

6 / 2010 703
Basics of post installed
rebar connections

Clear concrete cover c Max. bond stress, τT [N/mm²]


[mm] F30 F60 F90 F120 F180
80 2,5 1,7 1,0 0,2
90 2,8 2,0 1,5 0,5
100 4,0 2,3 1,9 0,7
110 4,5 2,7 2,3 1,2
120 6,5 2,9 2,6 1,6
130 4,0 2,8 1,9
140 6,5 3,0 2,2
150 4,5 2,3
160 7,0 6,5 2,5
170 2,6
180 2,7
7,0
190 2,8
7,0
200 2,9
7,0
210 3,0
220 4,5
230 6,5
240 7,0

Hilti HIT-HY 150 MAX rebar

Bar perpendicular to slab or wall surface exposed to fire


Temperature time curve (acc. ISO 834)

linst

Table 3: Maximum force in rebar in conjuction with HIT-HY 150 MAX as a function of embedment depth for
the fire resistance classes F30 to F180 (yield strength fyk = 500 N/mm²) according EC2a).
Bar ∅ Drill hole ∅ Max. Fs,T linst F30 F60 F90 F120 F180
[mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN] [kN]
80 2,18 0,73 0,24 0,05 0
120 8,21 2,90 1,44 0,82 0,18
170 16,2 9,95 5,99 3,69 1,35
8 12 16,2 210 16,2 13,01 9,52 3,6
230 16,2 13,04 5,74
250 16,2 9,26
300 16,2
100 5,87 1,95 0,84 0,4 0
150 16,86 8,06 4,45 2,82 0,96
190 25,3 16,83 11,86 7,65 2,91
10 14 25,3 230 25,3 20,66 16,29 7,18
260 25,3 22,89 13,77
280 25,3 18,17
320 25,3

704 6 / 2010
Basics of post installed
rebar connections

Bar ∅ Drill hole ∅ Max. Fs,T linst F30 F60 F90 F120 F180
[mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN] [kN]
120 12,32 4,35 2,16 1,23 0,27
180 28,15 17,56 11,59 7,14 2,69
220 36,4 28,12 22,15 16,91 6,82
12 16 36,4 260 36,4 32,7 27,47 16,53
280 36,4 32,75 21,81
300 36,4 27,08
340 36,4
140 20,53 8,77 4,74 2,95 0,95
210 42,08 29,72 22,76 16,66 6,3
240 49,6 38,96 32,0 25,89 13,12
14 18 49,6 280 49,6 44,31 38,21 25,44
300 49,6 44,36 31,6
330 49,6 40,83
360 49,6
160 30,5 16,38 9,26 5,77 2,04
240 58,65 44,53 36,57 29,59 15,0
260 64,8 51,56 43,61 36,63 22,04
16 20 64,8 300 64,8 57,68 50,70 36,11
330 64,8 61,26 46,67
360 64,8 57,22
400 64,8
200 55,72 38,06 28,12 19,39 7,22
250 77,71 60,06 50,11 41,39 23,15
310 101,2 86,45 76,5 67,78 49,54
20 25 101,2 350 101,2 94,09 85,37 67,13
370 101,2 94,16 75,93
390 101,2 84,72
430 101,2
250 97,13 75,07 62,46 51,73 28,94
280 113,63 91,56 79,13 68,23 45,43
370 158,1 141,04 128,61 117,71 94,91
25 32 158,1 410 158,1 150,60 139,70 116,90
430 158,1 150,69 127,90
450 158,1 138,89
500 158,1
a)
For HIT-HY 150 MAX rebar only the standard acc. EC2 is available (Data also in Warringtonfire report
WF 166402 or/and IBMB Braunschweig report No 3884/8246-CM.

Hilti HIT-HY 150 MAX rebar


Bar connection parallel to slab or wall surface exposed to fire
Max. bond stress, τT , depending on actual clear concrete cover for classifying the fire resistance.
It must be verified that the actual force in the bar during a fire, Fs,T , can be taken up by the bar connection of the
selected length, linst. Note: Cold design for ULS is mandatory.
Fs, T ≤ (linst – cf)⋅ ∅ ⋅ π ⋅ τT where: (linst – cf) ≥ ls;
ls = lap length
∅ = nominal diameter of bar
linst – cf = selected overlap joint length; this must be at least ls,
but may not be assumed to be more than 80 ∅
τT = bond stress when exposed to fire

6 / 2010 705
Basics of post installed
rebar connections

Table 4: Critical temperature-dependent bond stress, τcrit,T, concerning “overlap joint” for Hilti-HIT-HY 150
MAX injection adhesive in relation to fire resistance class and required minimum concrete coverage c.
Clear concrete cover c Max. bond stress, τT [N/mm²]
[mm] F30 F60 F90 F120 F180
30 0,46
35 0,56 0
40 0,69
45 0,84 0,37 0
50 1,04 0,45
0
55 1,22 0,53
60 1,47 0,62
65 1,85 0,73 0,38 0
70 0,87 0,46
75 1,02 0,52
80 1,21 0,59 0,37
85 1,35 0,67 0,43
90 1,52 0,78 0,52
95 1,74 0,91 0,58
100 2,02 1,07 0,66
105 1,21 0,77 0,38
110 1,39 0,91 0,44
115 1,61 1,05 0,48
120 1,89 1,21 0,53
125 2,12 1,37 0,61
130 2,20 1,57 0,69
135 1,82 0,75
140 2,13 0,81
145 0,89
2,20
150 0,88
155 0,97
160 2,20 1,08
165 1,22
2,20
170 1,40
175 1,62
180 1,90
185 2,05
190 2,20

Hilti HIT-RE 500 rebar


Bar perpendicular to slab or wall surface exposed to fire
Temperature time curve (acc. ISO 834)

linst

706 6 / 2010
Basics of post installed
rebar connections

Table 5: Maximum force in rebar in conjuction with HIT-RE 500 as a function of embedment depth for the
fire resistance classes F30 to F240 (yield strength fyk = 500 N/mm²) according EC2a).
Drill hole
Bar ∅ Max. Fs,T linst Fire resistance of bar in [kN]

[mm] [mm] [kN] [mm] F30 F60 F90 F120 F180 F240
65 1,38 0,57 0,19 0,05 0 0
80 2,35 1,02 0,47 0,26 0 0
95 3,87 1,68 0,88 0,55 0,12 0
115 7,3 3,07 1,71 1,14 0,44 0,18
150 16,19 8,15 4,59 3,14 1,41 0,8
8 10 16,19
180 16,19 9,99 6,75 2,94 1,7
205 16,19 12,38 5,08 2,86
220 16,19 6,95 3,82
265 16,19 8,57
305 16,19
80 2,94 1,27 0,59 0,33 0 0
100 5,68 2,45 1,31 0,85 0,24 0
120 10,66 4,44 2,48 1,68 0,68 0,31
140 17,57 7,76 4,38 2,99 1,33 0,73
10 12 25,29 165 25,29 15,06 8,5 5,79 2,58 1,5
195 25,29 17,63 12,18 5,12 2,93
220 25,29 20,66 8,69 4,78
235 25,29 11,8 6,30
280 25,29 13,86
320 25,29
95 5,8 2,52 1,32 0,83 0,18 0
120 12,79 5,33 2,97 2,01 0,82 0,37
145 23,16 10,68 6,02 4,12 1,84 1,03
180 36,42 24,29 14,99 10,12 4,41 2,55
12 16 36,42 210 36,42 27,38 20,65 8,47 4,74
235 36,42 312,01 14,16 7,56
250 36,42 19,13 9,89
295 36,42 21,43
335 36,42
110 10,92 4,65 2,55 1,7 0,61 0,20
140 24,60 10,87 6,13 4,19 1,86 1,03
170 39,12 23,50 13,55 9,2 4,07 2,37
195 49.58 35,6 24,69 17,05 7,17 4,10
14 18 49.58 225 49.58 39,20 31,34 13,48 7,34
250 49.58 43,44 22,32 11,54
265 49.58 29,49 15,00
310 49.58 31,98
350 49.58
130 22,59 9,42 5,30 3,61 1,56 0,8
160 39,17 21,33 11,95 8,15 3,65 2,11
190 55,76 37,92 24,45 17,25 7,35 4,22
210 64,75 48,98 36,51 27,53 11,29 6,32
16 20 64,75 240 64,75 53,10 44,12 20,88 11,04
265 64,75 57,94 33,7 17,14
280 64,75 42,0 22,17
325 64,75 44,84
365 64,75

6 / 2010 707
Basics of post installed
rebar connections

Drill hole
Bar ∅ Max. Fs,T linst Fire resistance of bar in [kN]

[mm] [mm] [kN] [mm] F30 F60 F90 F120 F180 F240
160 48,97 26,67 14,93 10,18 4,56 2,64
200 76,61 54,31 38,73 27,5 11,42 6,48
240 101,18 81,96 66,37 55,15 26,10 13,8
25 101,18 270 101,18 87,11 75,88 45,58 23,36
20 295 101,18 93,16 62,86 35,72
310 101,18 73,23 45,69
355 101,18 76,79
395 101,18
200 95,77 67,89 48,41 34,37 14,27 8,10
250 138,96 111,09 91,60 77,51 39,86 20,61
275 158,09 132,69 113,2 99,17 61,30 31,81
25 30 158,09 305 158,09 139,12 125,09 87,22 52,79
330 158,09 146,69 108,82 74,39
345 158,09 121,77 87,34
390 158,09 126,22
430 158,09
255 183,40 147,72 122,78 104,82 56,35 28,80
275 205,52 169,84 144,90 126,94 78,46 40,71
325 259,02 225,13 200,19 182,23 133,75 89,68
368 259,02 238,89 220,93 172,46 128,39
32 40 259,02
380 259,02 243,05 194,58 150,51
395 259,02 211,16 167,09
440 259,02 216,86
480 259,02
290 249,87 209,73 181,67 161,46 106,93 59,1
325 293,41 253,27 225,21 205,01 150,47 100,89
355 327,82 290,59 262,54 242,33 187,80 138,22
385 327,82 299,86 279,65 225,12 175,54
36 44 327,82
410 327,82 310,75 256,22 206,64
425 327,82 274,88 225,30
470 327,82 281,28
510 327,82
320 319,10 274,50 243,33 220,87 160,28 105,19
355 367,48 322,88 291,71 269,25 208,66 153,57
385 404,71 364,35 333,18 310,72 250,13 195,04
40 47 404,71 415 404,71 374,64 352,19 291,60 236,51
440 404,71 386,75 326,16 271,07
455 404,71 346,89 291,80
500 404,71 354,01
540 404,71
a)
For tables according the standards to DIN 1045-1988, NF-ENV 1991-2-2(EC2), Österreichische Norm B 4700-
2000, British-, Singapore- and Australian Standards see Warringtonfire report WF 166402 or/and IBMB
Braunschweig report No 3357/0550-5.

Hilti HIT-RE 500 rebar


Bar connection parallel to slab or wall surface exposed to fire

Max. bond stress, τT , depending on actual clear concrete cover for classifying the fire resistance.
It must be verified that the actual force in the bar during a fire, Fs,T , can be taken up by the bar connection of the
selected length, linst. Note: Cold design for ULS is mandatory.
Fs, T ≤ (linst – cf)⋅ ∅ ⋅ π ⋅ τT where: (linst – cf) ≥ ls;

708 6 / 2010
Basics of post installed
rebar connections

ls = lap length
∅ = nominal diameter of bar
linst – cf = selected overlap joint length; this must be at least ls,
but may not be assumed to be more than 80 ∅
τT = bond stress when exposed to fire

Table 6: Critical temperature-dependent bond stress, τcrit,T, concerning “overlap joint” for Hilti-HIT RE 500
injection adhesive in relation to fire resistance class and required minimum concrete coverage c.
Clear concrete cover c Max. bond stress, τT [N/mm²]
[mm] F30 F60 F90 F120 F180 F240
10 0
20 0,494 0
30 0,665 0
0
40 0,897 0,481
0
50 1,209 0,623
0
60 1,630 0,806 0,513
70 2,197 1,043 0,655 0,487
80 2,962 1,351 0,835 0,614
90 3,992 1,748 1,065 0,775 0,457
100 5,382 2,263 1,358 0,977 0,553
110 7,255 2,930 1,733 1,233 0,669 0,469
120 9,780 3,792 2,210 1,556 0,810 0,551
130 4,909 2,818 1,963 0,980 0,647
140 6,355 3,594 2,477 1,185 0,759
150 8,226 4,584 3,125 1,434 0,829
160 10.649 5,846 3,943 1,735 1,047
170 7,456 4,974 2,099 1,230
180 9,510 6,276 2,540 1,445
190 7,918 3,037 1,697
200 9,990 3,718 1,993
210 4,498 2,341
220 11,00 5,442 2,749
230 6,584 3,228
240 11,00 7,966 3,792
250 11,00 9,639 4,453
260 11,00 5,230
270 6,143
280 7,214
11,00
290 8,473
300 9,951
310 11,00

6 / 2010 709
Basics of post installed
rebar connections

8 Fatigue of bonded-in reinforcement for joints with


predominantly cyclical imposed loading
8.1 General notes
For loadbearing elements which are subjected to considerable cyclic stress the bonded-in connections should be
designed for fatigue. In that case evidence for fatigue of reinforcing steel bars, concrete and bond should be
provided separately.
For simple cases it is reasonable to use simplified methods on the safe side.
The partial safety factors for loads are specified in the code for reinforced concrete.
The partial safety factors for material are specified in Table 4.3.

Table 4.3: Partial safety factors for materials subjected to cyclic loading
Evidence for concrete bond reinforcing bars (steel)
Partial safety factor 1.5 1.8 1.15

8.2 Fatigue of reinforcing bars (steel)


The resistance for fatigue of reinforcing bars (steel) is specified in the actual code for reinforced concrete. The
behaviour of the steel of reinforcing bars bonded-in by means of Hilti HIT is at least as good as cast-in place
reinforcement.

8.3 Fatigue of bond and concrete (simplified approach)


As a simple and conservative approach on the safe side evidence for fatigue is proven if the following equation is
valid:

FSd,fat ≤ NRd ⋅ f fat

where:
FSd,fat Design value of the anchorage force for the ruling loading model for fatigue.
NRd Design resistance for static load of the anchorage (bond and concrete).
f fat Reduction factor for fatigue for bond and concrete: f fat = 0.5
If max/min of cycles is known, reduction factors are shown in Figure 4.13.

1
0.9 Diagram for a simplified approach
with 2⋅106 cycles (Weyrauch diagram)
0.8
Sd,fat max
0.7
2 / N Rd FSd,fat
0.6 FSd,fat max

0.5
0.4
0.3
0.2
0.1
FSd,fat min
0
0 0.2 0.4 0.6 0.8 1
0 time
Sd,fat min / N Rd
1

Figure 4.13: Reduction factors for fatigue for bond and concrete
Hilti design software for rebar connections does also the fatigue design.

If the simplified method is not satisfying, additional information using the “Woehler” - lines is available.
Ask Hilti Technical Service for the Hilti Guideline: TWU-TPF 06a/02 Hilti HIT-Rebar: Fatigue.

710 6 / 2010
Hilti HIT-RE 500
post installed rebars

Hilti HIT-RE 500 post installed rebars


Injection mortar system Benefits
- suitable for non-cracked concrete
Hilti C 20/25 to C 50/60
HIT-RE 500 - high loading capacity
330 ml foil pack - suitable for dry and water
(also available saturated concrete
as 500 ml - under water application
and 1400 ml - large diameter applications
foil pack) - high corrosion resistant
- long working time at elevated
temperatures
Static mixer - odourless epoxy

Rebar

European Drinking Hilti anchor Hilti rebar


Fire Corossion
Concrete Technical DIBt approval water
tested
Marque NF design design
resistance appoved
Approval software software

Service temperature range


Temperature range: -40°C to +80°C (max. long term temperature +50°C, max. short term temperature +80°C).

Approvals / certificates
Description Authority / Laboratory No. / date of issue
a)
European technical approval DIBt, Berlin ETA-08/0105 / 2008-06-30
DIBt approval DIBt, Berlin Z-21.8-1790 / 2009-03-16
Fire test report IBMB Braunschweig 3357/0550-5 / 2002-07-30
Assessment report (fire) Warringtonfire WF 166402 / 2007-10-26
a)
All data given in this section according ETA-08/0105, issue 2008-06-30.

712 6 / 2010
Hilti HIT-RE 500
post installed rebars

Materials
Reinforcmenent bars according to EC2 Annex C Table C.1 and C.2N.

Properties of reinforcement
Product form Bars and de-coiled rods
Class B C
Characteristic yield strength f yk or f 0,2k (MPa) 400 to 600
≥ 1,15
Minimum value of k = (ft/fy)k ≥ 1,08
< 1,35
Characteristic strain at maximum force, εuk (%) ≥ 5,0 ≥ 7,5
Bendability Bend / Rebend test
Maximum deviation from Nominal bar size (mm)
nominal mass ≤8 ± 6,0
(individual bar) (%) >8 ± 4,5
Bond: Nominal bar size (mm)
Minimum relative rib area, 8 to 12 0,040
fR,min > 12 0,056

Setting details
For detailed information on installation see instruction for use given with the package of the product.

Curing time for general conditions


Data according ETA-08/0105, issue 2008-06-30
Temperature Working time in which Initial curing time Curing time before
of the anchor can be inserted tcure,ini anchor can be fully
base material and adjusted tgel loaded tcure
5 °C ≤ TBM < 10 °C 2h 18 h 72 h
10 °C ≤ TBM < 15 °C 90 min 12 h 48 h
15 °C ≤ TBM < 20 °C 30 min 9h 24 h
20 °C ≤ TBM < 25 °C 20 min 6h 12 h
25 °C ≤ TBM < 30 °C 20 min 5h 12 h
30 °C ≤ TBM < 40 °C 12 min 4h 8h
TBM = 40 °C 12 min 4h 4h

For dry concrete curing times may be reduced according to the following table. For installation temperatures below
+5 °C all load values have to be reduced according to the load reduction factors given below.

Curing time for dry concrete


Additional Hilti technical data
Temperature Working time in which anchor Initial curing Reduced curing time Load
of the can be inserted and adjusted time before anchor can be reduction
base material tgel tcure,ini fully loaded tcure factor
TBM = -5 °C 4h 36 h 72 h 0,6
TBM = 0 °C 3h 25 h 50 h 0,7
TBM = 5 °C 2½h 18 h 36 h 1
TBM = 10 °C 2h 12 h 24 h 1
TBM = 15 °C 1½h 9h 18 h 1
TBM = 20 °C 30 min 6h 12 h 1
TBM = 30 °C 20 min 4h 8h 1
TBM = 40 °C 12 min 2h 4h 1

6 / 2010 713
Hilti HIT-RE 500
post installed rebars

Dry and water-saturated concrete, hammer drilling

a)

a
) Note: Manual cleaning for element sizes d ≤ 16mm and embedment depth hef ≤ 20 d only!

714 6 / 2010
Hilti HIT-RE 500
post installed rebars

Dry and water-saturated concrete, diamond coring drilling; Hilti technical information only

a)
Note: Manual cleaning for element sizes d ≤ 16mm and embedment depth hef ≤ 20 d only!

Fitness for use


Some creep tests have been conducted in accordance with ETAG guideline 001 part 5 and TR 023 in the following
conditions : in dry environnement at 50 °C during 90 days.
These tests show an excellent behaviour of the post installed connection made with HIT-RE 500: low
displacements with long term stability, failure load after exposure above reference load.

6 / 2010 715
Hilti HIT-RE 500
post installed rebars

Resistance to chemical substances


Non
Categories Chemical substances resistant
resistant
Drilling dust slurry pH = 12,6 
Alkaline products
Potassium hydroxide solution (10%) pH = 14 
Acetic acid (10%) 
Nitric acid (10%) 
Acids
Hydrochloric acid (10%) 
Sulfuric acid (10%) 
Benzyl alcohol 
Ethanol 
Ethyl acetate 
Solvents
Methyl ethyl keton (MEK) 
Trichlor ethylene 
Xylol (mixture) 
Concrete plasticizer 
Diesel 
Products from job site Engine oil 
Petrol 
Oil for form work 
Sslt water 
Environnement De-mineralised water 
Sulphurous atmosphere (80 cycles) 

Electrical Conductivity
12
HIT-RE 500 in the hardened state is not conductive electrically. Its electric resistivity is 66⋅10 Ω.m
(DIN IEC 93 – 12.93). It is adapted well to realize electrically insulating anchorings (ex: railway applications,
subway).

716 6 / 2010
Hilti HIT-RE 500
post installed rebars

Drilling diameters

Drill bit diameters d0 [mm]


Rebar (mm) Compressed air Diamond coring
Hammer drill (HD)
drill (CA) Wet (DD) Dry (PCC)
a) a)
8 12 (10) - 12 (10) -
a) a)
10 14 (12) - 14 (12) -
a) a)
12 16 (14) 17 16 (14) -
14 18 17 18 -
16 20 20 20 -
18 22 22 22 -
20 25 26 25 -
22 28 28 28 -
24 32 32 32 35
25 32 32 32 35
26 35 35 35 35
28 35 35 35 35
30 37 35 37 35
32 40 40 40 47
34 45 42 42 47
36 45 45 47 47
40 55 57 52 52

a) Max. installation length I = 250 mm.

6 / 2010 717
Hilti HIT-RE 500
post installed rebars

Basic design data for rebar design according to ETA


Bond strength

Bond strength in N/mm² according to ETA for good bond conditions


for hammer drilling, compressed air drilling, dry diamond core drilling

Concrete class
Rebar (mm)
C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60
8 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
10 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
12 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
14 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
16 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
18 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
20 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
22 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
24 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
25 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
26 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
28 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
30 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
32 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
34 1,6 2,0 2,3 2,6 2,9 3,3 3,6 3,9 4,2
36 1,5 1,9 2,2 2,6 2,9 3,3 3,6 3,8 4,1
40 1,5 1,8 2,1 2,5 2,8 3,1 3,4 3,7 4,0

718 6 / 2010
Hilti HIT-RE 500
post installed rebars

Bond strength in N/mm² according to ETA for good bond conditions


for wet diamond core drilling

Concrete class
Rebar (mm)
C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60

8 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3


10 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
12 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
14 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
16 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
18 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
20 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
22 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
24 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
25 1,6 2,0 2,3 2,7 3,0 3,4 3,7 4,0 4,3
26 1,6 2,0 2,3 2,7 2,7 2,7 2,7 2,7 2,7
28 1,6 2,0 2,3 2,7 2,7 2,7 2,7 2,7 2,7
30 1,6 2,0 2,3 2,7 2,7 2,7 2,7 2,7 2,7
32 1,6 2,0 2,3 2,7 2,7 2,7 2,7 2,7 2,7
34 1,6 2,0 2,3 2,6 2,6 2,6 2,6 2,6 2,6
36 1,5 1,9 2,2 2,6 2,6 2,6 2,6 2,6 2,6
40 1,5 1,8 2,1 2,5 2,5 2,5 2,5 2,5 2,5

Minimum anchorage length


According to ETA-08/0105, issue 2008-06-30, the minimum anchorage length shall be increased by factor 1,5 for
wet diamond core drilling. For all the other given drilling methods the factor is 1,0.

6 / 2010 719
Hilti HIT-RE 500
post installed rebars

Minimum and maximum embedment depths and lap lengths for C20/25 according
to ETA
Hammer drilling, Wet diamond coring
Rebar Compressed air drilling, drilling
Dry diamond coring drilling
Diameter lb,min* l0,min * lb,min* l0,min * lmax
fy,k
ds [mm] [mm] [mm] [mm] [mm]
[N/mm²]
[mm]
8 500 113 200 170 300 1000
10 500 142 200 213 300 1000
12 500 170 200 255 300 1200
14 500 198 210 298 315 1400
16 500 227 240 340 360 1600
18 500 255 270 383 405 1800
20 500 284 300 425 450 2000
22 500 312 330 468 495 2200
24 500 340 360 510 540 2400
25 500 354 375 532 563 2500
26 500 369 390 553 585 2600
28 500 397 420 595 630 2800
30 500 425 450 638 675 3000
32 500 454 480 681 720 3200
34 500 492 510 738 765 3200
36 500 532 540 797 810 3200
40 500 616 621 925 932 3200
lb,min (8.6) and l0,min (8.11) are calculated for good bond conditions with maximum utilisation of rebar yield strength
fyk = 500 N/mm² and α6 = 1,0

720 6 / 2010
Hilti HIT-RE 500
post installed rebars

Precalculated values
Example of pre-calculated values for “anchoring”
Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions
For all drilling procedures, excluding wet diamond core drilling (DD)
Anchorage Design Mortar Anchorage Design Mortar
Rebar
length lbd value NRd volume length lbd value NRd volume
[mm] [mm] [kN] [ml] [mm] [kN] [ml]
α2 or α5= 0.7
α1=α
α2=α
α3=αα4=αα5=1.0
α1 = α3 = α4 = 1.0
100 6,79 8 100 9,70 8
160 10,86 12 160 15,52 12
8
200 13,58 15 - - -
322 21,87 24 225 21,87 17
121 10,24 11 121 14,63 11
200 16,96 18 200 24,22 18
10 250 21,20 23 250 30,28 23
300 25,43 27 - - -
403 34,13 36 282 34,13 25
145 14,74 15 145 21,06 15
240 24,41 25 240 34,87 25
12 300 30,51 32 300 43,59 32
360 36,61 38 - - -
483 49,13 51 338 49,13 36
169 20,09 20 169 28,70 20
280 33,26 34 280 47,52 34
14 350 41,58 42 350 59,40 42
480 57,02 58 - - -
564 66,96 68 395 66,96 48
193 26,22 26 193 37,45 26
320 43,42 43 320 62,02 43
16 400 54,27 54 400 77,53 54
480 65,12 65 - - -
644 87,39 87 451 87,39 61
217 36,86 46 217 52,66 46
360 61,04 76 360 87,20 76
18 450 76,30 95 450 109,00 95
540 91,56 115 - - -
725 122,87 154 507 122,87 108
242 40,96 51 242 58,51 51
400 67,82 85 400 96,89 85
20 500 84,78 106 500 121,11 106
600 101,74 127 - - -
805 136,52 171 564 136,52 120
266 49,57 56 266 70,81 56
440 82,08 93 440 117,26 93
22 550 102,60 117 550 146,58 117
660 123,12 140 - - -
886 165,22 188 620 165,22 131
* Values corresponding to the minimum anchorage length. The maximum permissible load is valid for “good bond
conditions” as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of
mortar correspond to the formula “1,2∗(d0²-d²)∗π∗lb/4”

6 / 2010 721
Hilti HIT-RE 500
post installed rebars

Example of pre-calculated values for “anchoring”


Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions
For all drilling procedures, excluding wet diamond core drilling (DD)
Anchorage Design Mortar Anchorage Design Mortar
Rebar
length lbd value NRd volume length lbd value NRd volume
[mm] [mm] [kN] [ml] [mm] [kN] [ml]
α2 or α5= 0.7
α1=α
α2=α
α3=αα4=α
α5=1.0
α1 = α3 = α4 = 1.0
290 58,97 61 290 84,24 61
480 97,65 102 480 139,51 102
24 600 122,07 127 600 174,38 127
720 146,48 153 - - -
966 196,57 205 676 196,57 143
302 64,04 114 302 91,49 114
500 106,06 188 500 151,51 188
25 625 132,57 235 625 189,39 235
750 159,08 282 - - -
1 006 213,48 378 705 213,48 265
314 69,26 67 314 98,94 67
520 114,70 110 520 163,85 110
26 650 143,37 138 650 204,81 138
780 172,04 165 - - -
1 047 230,87 222 733 230,87 155
338 80,35 72 338 114,78 72
600 142,56 127 600 203,66 127
28 700 166,32 148 700 237,60 148
840 199,59 178 - - -
1 127 267,83 239 789 267,83 167
362 92,22 160 362 131,74 160
600 152,71 265 600 218,16 265
30 750 190,89 332 750 272,70 332
900 229,07 398 - - -
1 418 360,91 627 845 307,39 374
386 104,87 210 386 149,81 210
640 173,66 347 640 248,09 347
32 800 217,08 434 800 310,11 434
960 260,50 521 - - -
1 288 349,57 699 902 349,57 490
426 118,43 90 426 169,19 90
680 188,86 144 680 269,81 144
34 850 236,08 180 850 337,26 180
1 020 283,30 216 - - -
1 421 394,78 301 995 394,78 211
452 132,78 96 452 189,69 96
720 211,74 153 720 302,49 153
36 900 264,68 191 900 378,11 191
1 080 317,61 229 - - -
1 505 442,60 319 1 054 442,60 223
522 163,96 701 522 234,22 701
800 251,40 1 074 800 359,14 1 074
40 1 000 314,25 1 343 1 000 448,93 1 343
1 200 377,10 1 612 - - -
1 739 546,52 2 336 1 217 546,52 1 635
* Values corresponding to the minimum anchorage length. The maximum permissible load is valid for “good bond
conditions” as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of
mortar correspond to the formula “1,2∗(d0²-ds²)∗π∗lb/4” for hammer drilling

722 6 / 2010
Hilti HIT-RE 500
post installed rebars

Example of pre-calculated values for “overlap joints”


Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions
For all drilling procedures, excluding diamond wet (DD)
Anchorage Design Mortar Anchorage Design Mortar
Rebar
length lbd value NRd volume length lbd value NRd volume
[mm] [mm] [kN] [ml] [mm] [kN] [ml]
α2 or α5= 0,7
α1=αα2=α
α3=α
α5=αα6=1,0
α1 = α3 = α6 = 1,0
200 13,58 15 200 19,40 15
250 16,98 19 - - -
8
300 20,37 23 - - -
322 21,87 24 225 21,87 17
200 16,96 18 200 24,22 18
250 21,20 23 250 30,28 23
10 300 25,43 27 - - -
350 29,67 32 - - -
403 34,13 36 282 34,13 25
200 20,34 21 200 29,06 21
240 24,41 25 240 34,87 25
12 300 30,51 32 300 43,59 32
360 36,61 38 - - -
483 49,13 51 338 49,13 36
210 24,95 25 210 35,64 25
280 33,26 34 280 47,52 34
14 350 41,58 42 350 59,40 42
480 57,02 58 - - -
564 66,96 68 395 66,96 48
240 32,56 33 240 46,52 33
320 43,42 43 320 62,02 43
16 400 54,27 54 400 77,53 54
480 65,12 65 - - -
644 87,39 87 451 87,39 61
270 45,78 57 270 65,40 57
360 61,04 76 360 87,20 76
18 450 76,30 95 450 109,00 95
540 91,56 115 - - -
725 122,87 154 507 122,87 108
300 50,87 64 300 72,67 64
400 67,82 85 400 96,89 85
20 500 84,78 106 500 121,11 106
600 101,74 127 - - -
805 136,52 171 564 136,52 120
330 61,56 70 330 87,95 70
440 82,08 93 440 117,26 93
22 550 102,60 117 550 146,58 117
660 123,12 140 - - -
886 165,22 188 620 165,22 131
• Values corresponding to the minimum anchorage length. The maximum permissible load is valid for “good
bond conditions” as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume
of mortar correspond to the formula “1,2∗(d0²-ds²)∗π∗lb/4” for hammer drilling

6 / 2010 723
Hilti HIT-RE 500
post installed rebars

Example of pre-calculated values for “overlap joints”


Rebar yield strength f yk = 500 N/mm², concrete C25/30, good bond conditions
For all drilling procedures, excluding diamond wet (DD)
Anchorage Design Mortar Anchorage Design Mortar
Rebar
length lbd value NRd volume length lbd value NRd volume
[mm] [mm] [kN] [ml] [mm] [kN] [ml]
α2 or α5= 0.7
α1=α
α2=α
α3=αα4=α
α5=1.0
α1 = α3 = α4 = 1.0
360 73,24 76 360 104,63 76
480 97,65 102 480 139,51 102
24 600 122,07 127 600 174,38 127
720 146,48 153 - - -
966 196,57 205 676 196,57 143
375 79,54 141 375 113,63 141
500 106,06 188 500 151,51 188
25 625 132,57 235 625 189,39 235
750 159,08 282 - - -
1 006 213,48 378 705 213,48 265
390 86,02 83 390 122,89 83
520 114,70 110 520 163,85 110
26 650 143,37 138 650 204,81 138
780 172,04 165 - - -
1 047 230,87 222 733 230,87 155
420 99,79 89 420 142,56 89
600 142,56 127 600 203,66 127
28 700 166,32 148 700 237,60 148
840 199,59 178 - - -
1 127 267,83 239 789 267,83 167
450 114,53 199 450 163,62 199
600 152,71 265 600 218,16 265
30 750 190,89 332 750 272,70 332
900 229,07 398 - - -
1 418 360,91 627 845 307,39 374
480 130,25 261 480 186,07 261
640 173,66 347 640 248,09 347
32 800 217,08 434 800 310,11 434
960 260,50 521 - - -
1 288 349,57 699 902 349,57 490
510 141,65 108 510 202,35 108
680 188,86 144 680 269,81 144
34 850 236,08 180 850 337,26 180
1 020 283,30 216 - - -
1 421 394,78 301 995 394,78 211
540 158,81 115 540 226,87 115
720 211,74 153 720 302,49 153
36 900 264,68 191 900 378,11 191
1 080 317,61 229 - - -
1 505 442,60 319 1 054 442,60 223
600 188,55 806 600 269,36 806
800 251,40 1 074 800 359,14 1 074
40 1 000 314,25 1 343 1 000 448,93 1 343
1 200 377,10 1 612 - - -
1 739 546,52 2 336 1 217 546,52 1 635
* Values corresponding to the minimum anchorage length. The maximum permissible load is valid for “good bond
conditions” as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of
mortar correspond to the formula “1,2∗(d0²-ds²)∗π∗lb/4” for hammer drilling

724 6 / 2010
Hilti HIT-HY 150 MAX
post installed rebars

Hilti HIT-HY 150 MAX post installed rebars


Injection mortar system Benefits

Hilti - suitable for concrete C 12/15 to


HIT-HY 150 C 50/60
MAX - high loading capacity and fast
330 ml foil pack cure
(also available - suitable for dry and water
as 500 ml saturated concrete
and 1400 ml - for rebar diameters up to 25 mm
foil pack) - non corrosive to rebar elements
- good load capacity at elevated
temperatures
Static mixer
- hybrid chemistry
- multiplication factor for minimum
anchoring and splice length 1.0
- suitable for embedment length till
Rebar 2000 mm
- suitable for applications down to -
10 °C

European Drinking Hilti anchor Hilti rebar


Fire CE Corossion
Concrete Technical water
tested
design design
resistance conformity appoved
Approval software software

Service temperature range


Temperature range: -40°C to +80°C (max. long term temperature +50°C, max. short term temperature +80°C).

Approvals / certificates
Description Authority / Laboratory No. / date of issue
a)
European technical approval CSTB, France ETA-08/0202 / 2008-07-24
Fire test report IBMB Braunschweig 3884/8246 / 2007-05-24
Assessment report (fire) Warringtonfire WF 166402 / 2007-10-26
a)
All data given in this section according ETA-08/0202, issue 2008-07-24.

Materials
Reinforcmenent bars according to EC2 Annex C Table C.1 and C.2N.

734 6 / 2010
Hilti HIT-HY 150 MAX
post installed rebars

Properties of reinforcement
Product form Bars and de-coiled rods
Class B C
Characteristic yield strength f yk or f 0,2k (MPa) 400 to 600
≥ 1,15
Minimum value of k = (ft/fy)k ≥ 1,08
< 1,35
Characteristic strain at maximum force, εuk (%) ≥ 5,0 ≥ 7,5
Bendability Bend / Rebend test
Maximum deviation from Nominal bar size (mm)
nominal mass ≤8 ± 6,0
(individual bar) (%) >8 ± 4,5
Bond: Nominal bar size (mm)
Minimum relative rib area, 8 to 12 0,040
fR,min > 12 0,056

Setting details
For detailed information on installation see instruction for use given with the package of the product.

Working time, Curing time


Temperature Working time Curing time
of the base material TBM tgel tcure
-10 °C ≤ TBM < -5 °C 180 min 12 h
-5 °C ≤ TBM < -0 °C 90 min 9h
0 °C ≤ TBM < 5 °C 45 min 4,5 h
5 °C ≤ TBM < 10 °C 20 min 2h
10 °C ≤ TBM < 15 °C 7 min 50 min
15 °C ≤ TBM < 20 °C 6 min 40 min
20 °C ≤ TBM < 25 °C 5 min 30 min
25 °C ≤ TBM < 30 °C 3 min 30 min
30 °C ≤ TBM ≤ 40 °C 2 min 30 min

6 / 2010 735
Hilti HIT-HY 150 MAX
post installed rebars

Dry and water-saturated concrete, hammer drilling

a)

a) Note: Manual cleaning for element sizes d ≤ 16mm and embedment depth hef ≤ 10 d only!

736 6 / 2010
Hilti HIT-HY 150 MAX
post installed rebars

Fitness for use


Creep behaviour
Creep tests have been conducted in accordance with ETAG guideline 001 part 5 and TR 023 in the following
conditions: in dry environnement at 50 °C during 90 days.
These tests show an excellent behaviour of the post installed connection made with HIT-HY 150 MAX: low
displacements with long term stability, failure load after exposure above reference load.

Water behaviour
 Water: HIT-HY 150 MAX is water tight and water resistant, without any toxicity risk for the environnement.
 Drinking water: HIT-HY 150 MAX is «NSF» certified, in accordance with NSF/ANSI St 61 «Drinking Water
System Components - Health Effects». Tests are done at 60 °C, which corresponds to domestic hot water. The
use of HIT-HY 150 MAX is possible for water tanks.

Resistance to chemical substances

Chemical substance Comment Resistance


Sulphuric acid 23°C +
Under sea water 23°C +
Under water 23°C +
Alkaline medium pH = 13,2, 23°C +

Drilling diameters

Drill bit diameters d0 [mm]


Rebar (mm) Compressed air
Hammer drill (HD)
drill (CA)
8 12 (10) a) -
a)
10 14 (12) -
a)
12 16 (14) 17
14 18 17
16 20 20
18 22 22
20 25 26
22 28 28
24 32 32
25 32 32

a) Max. installation length I = 250 mm.

6 / 2010 737
Hilti HIT-HY 150 MAX
post installed rebars

Basic design data for rebar design according to ETA


Bond strength

Bond strength in N/mm² according to ETA for good bond conditions


for all drilling methods

Concrete class
Rebar (mm)
C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60
8 1,6 2,0 2,3 2,7 3,0 3,4 3,4 3,4 3,7
10 1,6 2,0 2,3 2,7 3,0 3,4 3,4 3,4 3,7
12 1,6 2,0 2,3 2,7 3,0 3,4 3,4 3,4 3,7
14 1,6 2,0 2,3 2,7 3,0 3,4 3,4 3,4 3,7
16 1,6 2,0 2,3 2,7 3,0 3,4 3,4 3,4 3,7
18 1,6 2,0 2,3 2,7 3,0 3,4 3,4 3,4 3,7
20 1,6 2,0 2,3 2,7 3,0 3,4 3,4 3,4 3,7
22 1,6 2,0 2,3 2,7 3,0 3,4 3,4 3,4 3,7
24 1,6 2,0 2,3 2,7 3,0 3,4 3,4 3,4 3,7
25 1,6 2,0 2,3 2,7 3,0 3,4 3,7 3,7 3,7

Minimum anchorage length

According to ETA-08/0202, the multiplication factor for minimum anchorage length is 1,0 for all approved drilling
methods.
Minimum and maximum embedment depth and lap lengths for C20/25
Hammer drilling,
Rebar
Compressed air drilling
lb,min* l0,min *
Diameter ds fy,k lmax
[mm] [N/mm²] [mm] [mm]
[mm]
8 500 113 200 1000
10 500 142 200 1000
12 500 170 200 1000
14 500 198 210 1000
16 500 227 240 1500
18 500 255 270 2000
20 500 284 300 2000
22 500 312 330 2000
24 500 340 360 2000
25 500 354 375 2000
lb,min (8.6) and l0,min (8.11) are calculated for good bond conditions with maximum utilisation of rebar yield strength
fyk = 500 N/mm² and α6 = 1,0

738 6 / 2010
Hilti HIT-HY 150 MAX
post installed rebars

Precalculated values
Example of pre-calculated values for “anchoring”
Rebar yield strength fyk = 500 N/mm², concrete C25/30, good bond conditions
Anchorage Design Mortar Anchorage Design Mortar
Rebar
length lbd value NRd volume length lbd value NRd volume
[mm] [mm] [kN] [ml] [mm] [kN] [ml]
α2 or α5= 0.7
α1=α
α2=α
α3=αα4=αα5=1.0
α1 = α3 = α4 = 1.0
100 6,79 8 (4)** 100 9,70 8 (4)**
160 10,86 12 (6)** 160 15,52 12 (6)**
8
200 13,58 15 - - -
322 21,87 24 225 21,87 17
121 10,24 11 (5)** 121 14,63 11 (5)**
200 16,96 18 (8)** 200 24,22 18 (8)**
10 250 21,20 23 250 30,28 23
300 25,43 27 - - -
403 34,13 36 282 34,13 25
145 14,74 15 (7)** 145 21,06 15 (7)**
240 24,41 25 (12)** 240 34,87 25 (12)**
12 300 30,51 32 300 43,59 32
360 36,61 38 - - -
483 49,13 51 338 49,13 36
169 20,09 20 169 28,70 20
280 33,26 34 280 47,52 34
14 350 41,58 42 350 59,40 42
480 57,02 58 - - -
564 66,96 68 395 66,96 48
193 26,22 26 193 37,45 26
320 43,42 43 320 62,02 43
16 400 54,27 54 400 77,53 54
480 65,12 65 - - -
644 87,39 87 451 87,39 61
217 36,86 46 217 52,66 46
360 61,04 76 360 87,20 76
18 450 76,30 95 450 109,00 95
540 91,56 115 - - -
725 122,87 154 507 122,87 108
242 40,96 51 242 58,51 51
400 67,82 85 400 96,89 85
20 500 84,78 106 500 121,11 106
600 101,74 127 - - -
805 136,52 171 564 136,52 120
266 49,57 56 266 70,81 56
440 82,08 93 440 117,26 93
22 550 102,60 117 550 146,58 117
660 123,12 140 - - -
886 165,22 188 620 165,22 131
* Values corresponding to the minimum anchorage length. The maximum permissible load is valid for “good bond
conditions” as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of
mortar correspond to the formula “1,2∗(d0²-d²)∗π∗lb/4” (** values correspond to min. hole diameter)

6 / 2010 739
Hilti HIT-HY 150 MAX
post installed rebars

Example of pre-calculated values for “anchoring”


Rebar yield strength fyk = 500 N/mm², concrete C25/30, good bond conditions
Anchorage Design Mortar Anchorage Design Mortar
Rebar
length lbd value NRd volume length lbd value NRd volume
[mm] [mm] [kN] [ml] [mm] [kN] [ml]
α2 or α5= 0.7
α1=α
α2=α
α3=αα4=α
α5=1.0
α1 = α3 = α4 = 1.0
290 58,97 61 290 84,24 61
480 97,65 102 480 139,51 102
24 600 122,07 127 600 174,38 127
720 146,48 153 - - -
966 196,57 205 676 196,57 143
302 64,04 114 302 91,49 114
500 106,06 188 500 151,51 188
25 625 132,57 235 625 189,39 235
750 159,08 282 - - -
1 006 213,48 378 705 213,48 265
* Values corresponding to the minimum anchorage length. The maximum permissible load is valid for “good bond
conditions” as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of
mortar correspond to the formula “1,2∗(d0²-ds²)∗π∗lb/4” (** values correspond to min. hole diameter)

740 6 / 2010
Hilti HIT-HY 150 MAX
post installed rebars

Example of pre-calculated values for “overlap joints”


Rebar yield strength fyk = 500 N/mm², concrete C25/30, good bond conditions
Anchorage Design Mortar Anchorage Design Mortar
Rebar
length lbd value NRd volume length lbd value NRd volume
[mm] [mm] [kN] [ml] [mm] [kN] [ml]
α2 or α5= 0,7
α1=α
α2=α
α3=α α5=α
α6=1,0
α1 = α3 = α6 = 1,0
200 13,58 15 (7)** 200 19,40 15 (7)**
8 250 16,98 19 (9)** - - -
322 21,87 24 225 21,87 17
200 16,96 18 (8)** 200 24,22 18 (8)**
300 25,43 27 - - -
10
350 29,67 32 - - -
403 34,13 43 282 34,13 25
200 20,34 21 (10)** 200 29,06 21 (10)**
240 24,41 25 (12)** 240 34,87 25 (12)**
12 300 30,51 32 300 43,59 32
360 36,61 38 - - -
483 49,13 51 338 49,13 36
210 24,95 25 210 35,64 25
280 33,26 34 280 47,52 34
14 350 41,58 42 350 59,40 42
480 57,02 58 - - -
564 66,96 68 395 66,96 48
240 32,56 33 240 46,52 33
320 43,42 43 320 62,02 43
16 400 54,27 54 400 77,53 54
480 65,12 65 - - -
644 87,39 87 451 87,39 61
270 45,78 57 270 65,40 57
360 61,04 76 360 87,20 76
18 450 76,30 95 450 109,00 95
540 91,56 115 - - -
725 122,87 154 507 122,87 108
300 50,87 64 300 72,67 64
400 67,82 85 400 96,89 85
20 500 84,78 106 500 121,11 106
600 101,74 127 - - -
805 136,52 171 564 136,52 120
330 61,56 70 330 87,95 70
440 82,08 93 440 117,26 93
22 550 102,60 117 550 146,58 117
660 123,12 140 - - -
886 165,22 188 620 165,22 131
360 73,24 76 360 104,63 76
480 97,65 102 480 139,51 102
24 600 122,07 127 600 174,38 127
720 146,48 153 - - -
966 196,57 205 676 196,57 143
375 79,54 141 375 113,63 141
500 106,06 188 500 151,51 188
25 625 132,57 235 625 189,39 235
750 159,08 282 - - -
1 006 213,48 378 705 213,48 265
* Values corresponding to the minimum anchorage length. The maximum permissible load is valid for “good bond
conditions” as described in EN 1992-1-1. For all other conditions multiply by the value by 0,7. The volume of
mortar correspond to the formula “1,2(d0²-ds²)lb/4” (** values correspond to min. hole diameter)
6 / 2010 741

You might also like