You are on page 1of 53

LOGO

Building Energy Analysis - Assignment 6

Jing--ge Ceramics Museum


Jing

Equest-Model

Instructor: Prof Vincent Yun Shang Chiou


Student: Nguyen Duc Anh – M9913801
Perspective
Contents

1 Model implement

2 Simulation result

3 Post –retrofit simulation

4 Energy Saving Analysis

5 Conclusion
General Information
Building type : Museum
Weather file : TWN Taipei 46698
Electric Utility : - custom
Gas Utility : - none
Number of season : typical use through the
Year
Electric Utility charges : Don’t know
Model structure
Building shell components :
- Envelope 1: The permanent
exhibition area
- Envelope 2: The contemporary
exhibition area ( Natural Lighting)

Air-side system Types:


- HVAC System 1 : Envelope 1
- HVAC System 2 : Envelope 2
General Shell Information
Building type : Museum
Building area : 80000 ft2
Number of floor
- Above Grade : 3
- Below Grade : 1

Building footprint
Wide Length 1 Length2
Cm 6550 1705 2944
Feet 214.90 55.94 96.59

12020.87 20056.26
Building Footprint
Plan North : East
Floor Height :
Floor to Floor:18 Ft
Floor to Ceil : 15 Ft

cm 540 450

feet 17.82 14.86


Zoning pattern
Plan North : East
Floor Conditional Height : 15 Ft
Zone conditioned: 76 Ft ( Permanent Exh )
12 Ft ( Cond Hall)
Zone unconditioned : 12 Ft ( Un-cond Stair)

cm 370 450

feet 12.13 14.86


Building Envelope Constructions
Roof : 6 in. Concrete
Finish : Gravel
Wall : Brick wall
Ground floor : Over Parking Garage

cm 370 450

feet 12.13 14.86


Building Interior Constructions
Ceiling Int finish : Dry wall
Wall type : Air - none
floor : Ceramic stone tile
Rigid Insulation : polystirence
Section and Elevation
Façade Dimension Total
Cm 540 460 420 340 240 2280 Façade Dimension Total
Feet 16459.2 14020.8 12801.6 10363.2 7315.2 44500.8 Cm 115 1205 1320
Feet 3505.2 36728.4 40233.6

Façade Dimension Total


Cm 270 900 360 180 120 1740
Feet 8229.6 27432 10972.8 5486.4 3657.6 52120.8
Exterior Window
Type of Window : Single Low – E
It occupied 33% of the total
Façade in each floor , so we
can simply by add one window
in each floor with the height
of 1800 mm, and run along
the façade of building
Window blind: Roller shade –
Translucent
100 % Closed in West and East

cm 9 18 9 18

Ft 3.54 7.09 3.54 7.09


Roof skylights

cm 9 18 9 18

Ft 3.54 7.09 3.54 7.09


Time schedule

 Opening hours:
Tuesday to Friday 9:30 to 17:00
Saturday and Sunday 9:30 AM to 18:00
Museum closed every Monday
(except on national holidays)
Chinese New Year's Day and Eve

Activity Area Allocation
Basement 1, Ground,MAbove,Top Floor
Exhibit display area/Museum
Function Area (m2) Electric consumption
Ceramic Hallway 317 2154
Information terminal 187 1326
Gallery Hall 370 3808
Galery 1 + Galery 5 536 4000
Galery 2 + Galery 6 536 3740
Galery 3 + Galery 7 536 3062
Galery 4 + Galery 8 536 2042
Total 3018 20132
Total ( feet2) 32473.7 0.630

Basement 1, Ground,MAbove,Top
Floor Basement 1,
Lobby (Main Entry and Assembly) Ground,MAbove,Top Floor
Function Area (m2) Electric consumption
Rest room
Stairs 154 508
Electric
Hall around 198 973 Function Area (m2) consumption
Stairs 272 1202
Rest room 96 276
Lift 96 200
Hall 242 3584 Rest room 96 276
Total 962 6467 Total 192 552
Total ( feet2) 10351.1 0.605 Total ( feet2) 2065.9 0.263
Activity Area Allocation
Envelope 1 Percentage of
Area

Galery
space
Mechanical 41%
42%

Lobby (Main
Entry and
Rest room Assembly)
2% 15%

Basement 1, Ground,MAbove,Top Floor


Galery space 3018
Lobby (Main Entry and
Assembly) 1102
Rest room 192
Mechanical 3088
Interior Lighting
Envelope 1 Percentage of
Area

Galery
space
Mechanical 41%
42%

Lobby (Main
Entry and
Rest room Assembly)
2% 15%

Basement 1, Ground,MAbove,Top Floor


Galery space 0.63
Lobby (Main Entry and
Assembly) 0.60
Rest room 0.26
Mechanical 0
General Shell Information
Position : West of Reference
Building area : 24000 ft2
Number of floor
- Above Grade : 2
- Below Grade : 0
- Due to Equest only allow 1
specific floor height , so we can
define the below grade floor, but
instead we have 2 above grade
floor.

cm 540 450

feet 17.82 14.86


Building Footprint
Plan North : North
Floor Height :
Floor to Floor:23 Ft
Floor to Ceil : 21 Ft
Zoning : 100 % Condition ,
Multi Function

cm 1420 1705

feet 46.6 55.94


Building Envelope Constructions
Roof : Metal Frame
Finish : Steel Galvanized
Wall :Aluminum
Ground floor : Over Parking Garage
Building Interior Constructions
Ceiling Int finish : Dry wall
Wall type : Air - none
floor : Ceramic stone tile
Rigid Insulation : polystirence
Exterior Window
Type of Window : Single Low – E
It occupied 90% of the total
Façade in each floor , so we
can simply by add one window
in each floor with the height
of 4800 mm, and run along
the façade of building
Window blind: None

cm 48

Ft 18.90
Roof skylights
Time schedule

 Opening hours:
Tuesday to Friday 9:30 to 17:00
Saturday and Sunday 9:30 AM to 18:00
Museum closed every Monday
(except on national holidays)
Chinese New Year's Day and Eve

Activity Area Allocation

Basement 1, Ground Floor


Exhibit display area/Museum
Function Area (m2) Electric consumption
Sun light Galery 490 3860
(Feet 2) 5228.3 0.738
% 22.27273
Restaurant 246 3882
(Feet 2) 2624.82 1.479
% 11.18182
Stair + Lobby 135 508
Stair + Lobby 135 508
Total 270 1016
(Feet 2) 2880.9 0.353
% 12.27273
Activity Area Allocation

Envelope 2
Percantage of Area

Sun light
Galery
Technical 30%
45%

Restauran
Stair + t
Lobby 12%
13%

Basement 1, Ground Floor


Sun light Galery 656
Restaurant 268
Stair + Lobby 278
Technical 998
Interior Lighting

Basement 1, Ground Floor


Sun light Galery 0.738
Restaurant 1.479
Stair + Lobby 0.353
Technical 0
HVAC System Definition
Cooling Source: Chilled Water
Heating Source: No heating
System Type : Standard VAV
HVAC System Definition
C temp F temperature
20 68
23 73.4

Average
Ceiling Temperature 22.5
Wall Temperature 22.68
Floor temperature 21.23
Window Temperature 24
Air outlet Temperature 20.25
Lighting Temperature 29.93
Perspective
Interior Perspective
Simulation 1 : Electric consumption by month

- The electric consumption is highest in June ,July


August and Sep. The total energy consumption
In July is 103 000 kWh. ( Compared with 84000 in
measurement statistics)
- From March to November : Space Cooling occupy
more than 50% energy consumption in the building
- The energy for lighting is account for 10% energy
consumption a month, equal to energy for pump.
- Ventilation fan account for 13% energy consumption

2010 604140
2009 620940
Model 680011
Simulation1 – Percentage of Energy Consumption by
Function
Monthly electric day load by file
Energy Consumption by Hour
Simulation 1 : Energy Consumption by Month

2010 604140
2009 620940
Model 680011

1 2 3 4 5 6 7 8 9 10 11 12
Monthy Energy comsumption in 2010 44580 30900 31860 41100 35880 45540 57540 75900 77220 67560 56880 46560
Monthy Energy comsumption in 2009 39180 23640 39840 35940 40320 43620 59340 83880 75960 76860 55800 46560
Energy Consumption by Month
(Measurement)
Energy Consumption by Month
(kWh)
90000

80000 75900 77220

70000 67560

60000 57540 56880

50000 44580 45540


41100
40000 35880 83880
75960 76860
30900 31860
30000 59340 55800
46560
20000 39180 39840 35940 40320 43620

10000 23640
0
0
1 2 3 4 5 6 7 8 9 10 11 12

2010 2009

1 2 3 4 5 6 7 8 9 10 11 12
Monthy Energy comsumption in 2010 44580 30900 31860 41100 35880 45540 57540 75900 77220 67560 56880 46560
Monthy Energy comsumption in 2009 39180 23640 39840 35940 40320 43620 59340 83880 75960 76860 55800 46560
Simulation 2 : Some renovation in Building Envelope
Constructions

Roof :Add some exterior insulation


Finish : Steel Galvanized
Wall : Add Insulation and
polystyrene
Ground floor : Make more Insulation
In both exterior and interior
Simulation 2 : Reduce roof skyline

Roof Skyline: Decrease the density of skyline window


Add some Insulation and material has low u-value to deacrese solar conduction and solar radiation
Simulation2 - Energy Consumption by Month

- The electric consumption is highest in Jule ,August but it decreased


significantly from 103000 to 95000 due to the heating exchange is Simulation 1 680011
smaller than present situation Simulation 2 630310

The total energy consumption in all the year is 630310 kWh in , so it is


deacreased near 50000 kW than present situation case
Simulation2 - Energy Consumption by Month

- The electric consumption for ventilation fan is higher


due to too much space was the open space in
museum. And exchange air between indoor space
and outdoor space
- The energy used for space cooling is decreased
significantly
- Pumps and Aux is still keep their function but
decreased slightly due to decreased the water
consumption for air-conditional system

Space cooling
Simu 1 Simu 2
37495 34506

Ventilation Fan
Simu 1 Simu 2
9660 8766
Simulation 3 solution

Window: Decrease the density of window


Add some Insulation and material has low u-value window to decrese solar conduction and solar
radiation
Simulation 3 solution

Decrease the area of Sunlight gallery as small as possible


Use some fan in the border to prevent the air temperature loss in space between Gallery and Stair
Simulation3 - Energy Consumption by Month

- The electric consumption is highest in July ,August but it decreased


significantly from 103000 to 88000 due to the heating exchange is Simulation 1 680011
smaller than present situation Simulation 2 610260

The total energy consumption in all the year is 610260 kWh in , so it


decreases near 70000 kW than situation case
Simulation3 - Electric consumption by month

- The electric consumption for ventilation fan is higher


due to too much space was the open space in
museum. And exchange air between indoor space
and outdoor space
- The energy used for space cooling is decreased
significantly
- Pumps and Aux is still keep their function but
decreased slightly due to decreased the water
consumption for air-conditional system

Space cooling
Simu 1 Simu 2
37495 26641

Ventilation Fan
Simu 1 Simu 2
9660 16531
Lighting fixture
 There are too much lighting
here. We can reduce lighting in
this area.
 This window can open more to
receive natural lighting
 Task lighting in this area is not
necessary. We can turn it off to
save energy
Lighting fixture
 There are too much lighting
here even in window where we
can open to receive natural
lighting
 The density of lighting is too
high . We can reduce it.
Simulation 4 solution

We can decrease the Design Ventilation in Lobby and Restroom


Add some curtain wall to make the space more independent . So that we can control the area that need
air conditioning and the area can use natural ventilation
Simulation 4 solution

There is over lighting in the area of Restaurant , and in the sunlight exhibition
We can take advantages from natural lighting in the out side and decrease the lighting in
this area. It is big like in restaurant now, it is 2 times than normal different space
Simulation4 - Energy Consumption by Month

- The electric consumption is highest in July ,August but it decreased


significantly from 103000 to 88000 due to the heating exchange is Simulation 1 680011
smaller than present situation Simulation 2 600690

The total energy consumption in all the year is 600690 kWh in , so it


decreases near 80000 kW than situation case
Simulation4 - Electric consumption by month

- The electric consumption for ventilation fan is higher


due to too much space was the open space in
museum. And exchange air between indoor space
and outdoor space
- The energy used for space cooling is decreased
significantly
- Pumps and Aux is still keep their function but
decreased slightly due to decreased the water
consumption for air-conditional system

Space cooling
Simu 4 Simu 3
26525 26641

Ventilation Fan
Simu 4 Simu 3
17105 16531

Area Lighting
Simu 4 Simu 3
6080 6531
Conclusion

- The electric consumption is highest in July ,August due to so large


amount of energy is used for space cooling
- There are some method to reduce the energy consumption in the
building by separate the space, use the low u-value
material, decrease the skylight window and close the window to
decrease the solar radiation and solar conduction
- The electric fixtures is quite consume less money than other
consumption source, so it will not contribute much to energy
consumption in the building
- With all above method, the building still work well , but the energy
consumption will less in enormous amount than before