Remote control
Number of poles 1P - -
2P b b
3P - -
4P - -
dB
CT+
Audible
perception
threshold t
1
CT+
0
Electromagnetic
E91529
U
disturbances
1
CT+
0
Temperature rise
E91531
CT+
Ambient
temperature t
1
CT+
0
Auxiliaries
Auxiliary contacts ACTo+f No No
Interference filter ACTp No No
Mixed control: impulse/latched ACTc No No
Time delay ATEt No No
Choice of 60 Hz contactors
Contactors that can be equipped with auxiliaries
Standard contactor Manually-operated
contactors
Rating A 16 25 40 63 40
Control voltage V AC 127 220/240 127 220/240 127 220/240 127 220/240 127 230/240
Number of poles 1P - - b b - - - - - -
2P g g br br b b - - b b
3P - - b b b b b b - -
4P - - - - - - - - - -
Auxiliaries
Auxiliary contacts ACTo+f Yes Yes
Interference filter ACTp Yes Yes
Mixed control: impulse/ ACTc Yes Yes
latched
Time delay ATEt Yes Yes
;
b b b - b - b - b - - - - - - - - - - - - - -
bg bg bg bg b br - br b b b b bg bg br b - b b b b b
- - - r - - - b - b - b - - - - - b - - - - -
- - - rg - br - brg - br br brg b - - br - b - br b b b
100 100
200,000 200,000
All types as per derating table All types as per derating table
Vertical ± 30° max. Vertical ± 30° max.
E91526
dB
CT
t
1
CT
0
E91528
1
CT
0
E91530
˚
CT
t
1
CT
0
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Remote control
062006N
062007N
DB106316
ATEt
CT
16...100 A
ACTo+f
ACTp
ACTc
mechanical
Manually-operated CT
electrical
16...63 A
Accessories
PB101205-23
055642N
055641N
055643N
Yellow clips
Ensure the mechanical and/or electrical link between contactors and their auxiliaries.
Sealable screw shields
Used to avoid all contact with device terminals (upstream and downstream).
Remote control
CT+ high performance contactors allow CT+ high performance contactors combine the advantages of static switching and
remote control of single-phase circuits. electromechanical technology: compact dimensions, minimum temperature rise.
CT+ contactors provide a solution when high performance is required, particularly in
They are intended for demanding terms of number of switching operations, lifetime, versatility with loads, minimum
applications. noise, absence of electromagnetic disturbances, installation in all positions and
limited temperature rise.
062006N
N L
E57636 A1 1 3
15030
062007N
A2 2 4
1P+N with manual 1NO 20 230 2+1(1) 15031
operation
N L
E57646
A1 1 3
I
auto
15031
O
A2 2 4
PB100151
(1) comes with a 9 mm spacer (cat. no. 27062): to be used in case of mounting of the CT+ next
to a circuit-breaker, contactor, impulse relay, etc. to guarantee optimum use.
Operation
CT+ high performance contactors have a NO contact and are controlled by latched
type electrical orders. An orange indicator light comes ON on the front face when the
output contact is closed.
The manually-operated CT+ contactors are equipped on their front face with an
operating mode selection pushbutton. A green indicator light indicates the current
spacer mode:
b automatic operating mode (green light ON)
b temporary "ON" override (green light flashing)
b permanent shutdown mode (light OFF).
In ON override or permanent shutdown mode, the CT+ systematically returns to
automatic operating mode further to a supply outage.
d It is compulsory to use the same phase for power and control connection.
Technical data
Technical data
Power circuit
CT ratings 16 to 100 A (category AC7a)
Manually-operated CT ratings 16 to 63 A (category AC7a)
Characterisation on load types Consult Practical Advice p. 92306
Permanent ON override Voltage rating 250 V AC (1P and 2P), 400 V AC (3P and 4P)
Frequency 50 Hz or 60 Hz
Control circuit
Voltage 12 V AC (±10 %), 24 V AC (±10 %), 127 V AC (±10 %),
220 V AC (-10 % +5 %), 230...240 V AC (-10 % +6 %)
Coil frequency 50 Hz or 60 Hz
Accessories
DB106584
Screw shields
b Designed to cover terminals to avoid contact with device screws.
b Allow sealing.
Spacer
b Required to reduce temperature rise of modular devices installed side by side.
b Recommended to separate electronic devices (thermostat, programmable clock,
2 CT + spacer + 2 CT etc.) from electromechanical devices (relays, contactors).
Derating of contactors mounted in modular enclosure if inside temperature is
> 40°C
DB106585
9 mm
50 Hz contactors
1P 1NO 16 12 2 16110
1 1NO 16 24 2 16111
1NO 16 220 2 18006
DB103373
1NO 16 230...240 2 16113
2 1NO 25 220 2 18011
1NO 1NO 25 230...240 2 15958
16113
2P 2NO 16 12 2 16114
055833
R1 R3 1 3 2NO 16 24 2 16115
DB103376 2NO 16 220 2 18007
DB103375
2NO 16 230...240 2 15957
R2 R4 2 4 1NO+1NC 16 12 2 16125
2NC 2NO 1NO+1NC 16 24 2 16126
1NO+1NC 16 220 2 18008
1NO+1NC 16 230...240 2 15956
1 R1 2NO 25 24 2 16020
DB103377
DB103378
2 4 6
3NC 3NO
DB103381
DB16580
4NO 63 24 6 16025
2 4 R2 R4 2 4 6 R2 4NO 63 220...240 6 15973
2NO + 2NC 3NO + 1NC 4NC 63 24 6 16026
4NC 63 220...240 6 15974
2NO+2NC 63 220...240 6 15975
3NO+1NC 63 220...240 6 15976
4NO 100 220...240 12 15978
Remote control
9 mm
50 Hz manually-operated contactors
2P 2NO 16 220 2 18015
A1 1 3 2NO 16 230...240 2 16116
1NO+1NC 16 220 2 18016
DB106317
I P
auto 1NO+1NC 16 230...240 2 16127
O 2NO 25 24 2 16490
A2 2 4
2NO 25 220 2 18018
15981
2NO 2NO 25 230...240 2 15981
A1 1 R1 2NC 25 24 2 16491
055837
I P
auto
O
15988
A2 R2 R4
2NC
I P
auto
O
A2 2 4 6
3NO
4P 4NO 25 24 4 16492
A1 1 3 5 7 4NO 25 220...240 4 15983
4NC 25 24 4 16493
DB103382
I P
auto 4NO 40 24 6 16495
O 4NO 40 220...240 6 15986
A2 2 4 6 8
4NC 40 24 6 16496
4NO 4NO 63 24 6 16498
A1 R1 R3 R5 R7 4NO 63 220...240 6 15988
DB106587
I P
auto
O
A2 R2 R4 R6 R8
4NC
Remote control
DB103373
2
1NO
DB103375
2NO 25 220...240 2 16145
R2 R4 2 4 2NC 25 127 2 16137
2NC 2NO 2NC 25 230...240 2 16147
2NO 40 127 4 16138
1 R1 2NO 40 230...240 4 16148
DB103377
2 R2
1NO + 1NC
60 Hz manually-operated contactors
2P 2NO 40 127 4 16141
A1 1 3 2NO 40 230...240 4 16151
DB106317
I P
auto
O
A2 2 4
2NO
055641N
055643N
cos ϕ = 0.6 9 mm
CT accessories
Screw shields 3P, 4P 25 4 15921
(bag of 10 upstream/downstream) 2P 40/63 4 15922
15921 15922 15923 3P 40/63 6 15923
Spacer 1 27062
PB100151
27062
E91479
1 23
A1
CT ACTo+f
PB100152
A2
2 24
indication
load
N
Technical data
Combination with CT Right side
Connection Tunnel terminals
Flexible cable: 2 x 2.5 mm2
Rigid cable: 2 x 1.5 mm2
ACTp
This auxiliary is an interference suppressor which limits overvoltages on the control
circuit.
ACTp
L 2 24 15919
110...240 15920
DB105712
BP BP
1 1 A1 1
A1
CT ACTp CT
A2
15920
2 2 A2 2
N load load
The ACTp has 2 separate and identical circuits, allowing it to be combined with
2 different CT contactors:
b one by clips, on the CT mounted to its right
b the other by wires.
Technical data
Power supply Voltage: 24 V, 230 V
Frequency: 50/60 Hz
Combination with CT Left side
By clips(1)
Consumption Off-load: 3 VA
Connection Tunnel terminals
Flexible cable: 2 x 2.5 mm2
Rigid cable: 2 x 1.5 mm2
(1) electrical and mechanical link.
ACTc
This auxiliary, combined with contactors, enables them to be controlled by 2 order
types:
b impulse order for local control (input T)
b latched order for centralised control (input X).
The last order received takes priority.
ACTc
L 2 230...240 18308
24...48 18309
E32448
S BP
L 1
T
ACTc CT
18308 N 2
load
N
Technical data
Power supply Voltage: 24...48 V, 230 V
Frequency: 50/60 Hz
Combination with CT Left side
By clips(1)
Consumption Off-load: 3 VA
Inrush(2): 2 A
Holding(2): 0.5 A
Connection Tunnel terminals
Flexible cable: 2 x 2.5 mm2
Rigid cable: 2 x 1.5 mm2
1) Electrical and mechanical link.
(2) Maximum consumption of all contactors controlled.
ATEt
This auxiliary is used to time delay contactor control. According to cabling, there are
4 possible time delay types.
Type Width in mod. Control voltage Cat. no.
of 9 mm (V AC)
PB101193-35
ATEt
2 24...240 15419
Caractéristiques
Power supply Voltage: 24...240 V
Frequency: 50/60 Hz
Combination with CT Left side
By clips(1)
Consumption Off-load: 5 VA
15419 Inrush(2): 3 A
Holding(2): 0.2 A
Connection Tunnel terminals
Flexible cable: 2 x 2.5 mm2
Rigid cable: 2 x 1.5 mm2
1) Electrical and mechanical link.
(2) Maximum consumption of all contactors controlled.
Operation
b There are 4 types of time delay:
v the A type time delay is used to delay energisation of a load
v the B type time delay is used, on closing of the control contact (pushbutton), to
energise a load for a given time
v the C type time delay is used to extend energisation of a load
v the H type time delay is used, as long as the control contact remains closed, to
energise a load for a given time.
b Time delay range: 1 s to 10 h.
b Repetition accuracy: ± 0,5 %.
A type:
Delays energisation of the contactor or relay.
DB106348
N (-) L (+) U
DB105962
1
0
A1
A1 1
CT/RLI
A2 0
t
ATEt CT/RLI T
Y1 A2
B Type:
Energises the contactor or relay on closing of a pushbutton.
The time delay starts on closing of the control order.
N (-) L (+) U
DB106349
DB105963
A1 A1 1
CT/RLI
A2 0
t
ATEt CT/RLI T
Y1 B1 A2
C Type:
Energises the contactor or relay on closing of a pushbutton.
The time delay starts on release of the control order.
N (-) L (+) U
1
DB106350
DB105964
A1 A1 1
CT/RLI
A2 0
t
T
ATEt CT/RLI
B2
Y1B1 A2
H Type:
Controls the contactor or relay for a given time on energisation.
N (-) L (+) U
1
DB106351
DB105965
0
A1 A1 1
CT/RLI
A2 0
t
ATEt CT/RLI T
B2
B1 A2