A81356044 - "Quick Start" for the 1769-IF8 module.

1769-IF8 configuration information in RSLogix 5000.


This document will cover what is needed to get the 1769-IF8 module configured and channels enabled in RSLogix 5000 software. RSLogix 5000 version 12 and 13: See Knowledgbase document G80353611 for generic profile information for the 1769-IF8 module. Based on the profile information, there is a configuration file created that is 50 words long. There are two words for each channel that need to be modified to configure the Output Data Format, Output Data Type, and Channel Enable which will get the channel working. For example, words 2 and 3 are used for Channel 0 configuration, words 8 and 9 are for Channel 1 configuration and so on.

Configuration File Map


Word/Bit Word 0 Word 1 Word 2 Word 3 Word 4 Word 5 Word 6 Word 7 Word 8 Word 9 Word 10 Word 11 Word 12 Word 13 Word 14 Word 15 Word 16 Word 17 Word 18 Word 19 Word 20 Word 21 Word 22 Word 23 Word 24 Word 25 Word 26 Word 27 Word 28 Word 29 Word 30 Word 31 S S S S S S EC Reserved Reserved S S S EC Reserved Reserved S S S EC Reserved Reserved S S S EC Reserved Reserved 15
ERTS

14

13

12

11

EC

Reserved Reserved

09 08 07 06 05 04 Real Time Sample Value Reserved EA AL EI Reserved Inpt Dta Fm Reserved Chl0 Process Alarm High Data Value Channel 0 Process Alarm Low Data Value Channel 0 Alarm Dead Band Value Channel 0 Pad EA AL EI Reserved Inpt Dta Fm Reserved Chl1 Process Alarm High Data Value Channel 1 Process Alarm Low Data Value Channel 1 Alarm Dead Band Value Channel 1 Pad EA AL EI Reserved Inpt Dta Fm Reserved Chl2 Process Alarm High Data Value Channel 2 Process Alarm Low Data Value Channel 2 Alarm Dead Band Value Channel 2 Pad EA AL EI Reserved Inpt Dta Fm Reserved Chl3 Process Alarm High Data Value Channel 3 Process Alarm Low Data Value Channel 3 Alarm Dead Band Value Channel 3 Pad EA AL EI Reserved Inpt Dta Fm Reserved Chl4 Process Alarm High Data Value Channel 4 Process Alarm Low Data Value Channel 4 Alarm Dead Band Value Channel 4 Pad

10

03

02

01

00

Inpt Filter Sel Chl0 Inpt Tp/RngeSel Chl0

Inpt Filter Sel Chl1 Inpt Tp/RngeSel Chl1

Inpt Filter Sel Chl2 Inpt Tp/RngeSel Chl2

Inpt Filter Sel Chl3 Inpt Tp/RngeSel Chl3

Inpt Filter Sel Chl4 Inpt Tp/RngeSel Chl4

A81356044 - "Quick Start" for the 1769-IF8 module.

Configuration File Map continued


Word 32 Word 33 Word 34 Word 35 Word 36 Word 37 Word 38 Word 39 Word 40 Word 41 Word 42 Word 43 Word 44 Word 45 Word 46 Word 47 Word 48 Word 49 S S S S S S EC Reserved Reserved S S S EC Reserved Reserved EC Reserved Reserved
AL EI Reserved Inpt Filter Sel Chl5 Inpt Dta Fm Reserved Inpt Tp/RngeSel Chl5 Chl5 Process Alarm High Data Value Channel 5 Process Alarm Low Data Value Channel 5 Alarm Dead Band Value Channel 5 Pad EA AL EI Reserved Inpt Filter Sel Chl6 Inpt Dta Fm Inpt Tp/RngeSel Chl6 Reserved Chl6 Process Alarm High Data Value Channel 6 Process Alarm Low Data Value Channel 6 Alarm Dead Band Value Channel 6 Pad EA AL EI Reserved Inpt Filter Sel Chl7 Inpt Dta Fm Inpt Tp/RngeSel Chl7 Reserved Chl7 Process Alarm High Data Value Channel 7 Process Alarm Low Data Value Channel 7 Alarm Dead Band Value Channel 7 Pad EA

WHERE: EC = Enable Channel Inpt Dta Fm Chlx = Input Data Format Select: select the form the analog data is presented to the controller and used in the control program. Inpt Tp/Rnge Sel Chlx = Input Type/Range Select: configure the Input Type/Range. Reserved = Bits not used, allows for future expansion. Should be programmed to 0.

Channel Configuration Word Format


Word/Bit 15 14 13 12 11 10 EA 9 AL 8 EI 7 6 5 4 3 2 1 0

Configuration Word 2 Configuration Word 3

EC

Reserved Reserved

Reserved Reserved

Inpt Filter Sel Chl0 Inpt Tp/RngeSel Chl0

Inpt Dta Fm Chl0

The areas in red are the only bits that need to be changed to get the channels operational. 1. Set the enable bit to turn on the channel. Configuration Word 2, 8, 14, 20, 26, 32, 38, or 44: Bit 15: E Channel Enable. (0) Disabled. (1) Enabled. 2. Set the bits necessary for the output type and data type according to the lists below. Configuration Word 3, 9, 15, 21, 27, 33, 39, or 45: Bit 0-3: Input Type/ Range Bit 8-10: Input Data Format

A81356044 - "Quick Start" for the 1769-IF8 module.

INPUT TYPE/RANGE SELECT Bit 00-03 Settings Bit 02 Bit 01 Bit 00

INPUT DATA FORMAT SELECT Bit 08-10 Settings Bit 10 Bit 09 Bit 08 0 0 0 0 0 0 0 1 1 1 0 1

Input Type/ Normal Operating Range -10 to +10 Vdc 0-5 vdc 0-10 Vdc 4-20 mA 1-5 Vdc 0-20 mA

Bit 03

0 0 0 0 0 0

0 0 0 0 1 1

0 0 1 1 0 0

0 1 0 1 0 1

Data Format Raw/Proportional Data Engineering Units Scaled For PID Percent Range

3. Download the program to the processor to make the configuration take affect. Note: The actual addressing for the configuration word will appear as Local:e:C.Data[0] where e is the slot number of the analog card.

Range Types and Data Formats Defined


Input Type Normal Op. Range Full Range (Includes amount Over and Under Normal Operating) +10.5V to 10.5V 0.0V to 5.25V Raw/Pro p. Data Units for Full Range -32,767 to +32,767 -27068 to +32,767 -29788 to +32,767 -32767 to +32767 -32767 to +32767 -32,767 to +32,767 Input Data Word Ranges Eng. Units Scaled-for- Scaled-forValues for PID Values PID Values Full Range for Full for Normal Range Operating Range -10500 to + 10500 0 to +5250 0 to 16,383 -410 to 16793 0 to 17202 Percent of Normal Op. Range Values Percent of Full Range Values

+/-10 Vdc

-100% to +100%* 0-100%

-105.00 to 105.00%* 0 to 105.00% 0 to 105.00% -5.00 to 106.25% -12.50 to 106.25% 0.00 to 105.00%

0-5 Vdc

0 to 16,383

0-10 Vdc

0.0V to 10.5V

0 to +10500 3200 to 21000 +500 to +5250 0 to 21000

0 to 16,383

-0 to 17202

0-100%

4-20 mA

3.2 mA to 21 mA +0.5V to 5.25V 0 mA to 21 mA

0 to 16,383

-819 to 17407 -2048 to 17407 0 to 17202

0-100%

1-5 Vdc

0 to 16,383

0-100%

0 20 mA

0 to 16,383

0-100%