Functional Description. 3 Usage. 3 Technical data.. 4 Front View. 4 Example wiring diagram..5 Cresnet connections 6 Cresnet ID. 7 Method A viewport.. 7 Method B Toolbox...9 Configuration Manager......................................................................10 Programming Manager..................................................................... 10 Example Program............................................................................. 11

Setup

Programming

10

Further enquiries

12

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

CH-UNI8IO Description

Product Manual

Figure 1: CH-UNI8IO

Functional Description
The UNI8IO is a custom button panel interface. It provides connections for max. 8 potential free contacts and max. 8 outputs for LEDs or Lamps , Relays etc. untill max. 48VDC/100mA. The CH-UNI8IO was specifically developed to be used in combination with the normal light switches / wall button panels. Fits in standard 55mm UP/AP-switchboxes Connections: Cresnet via a standard mini phoenix and in/outputs via a mini screw terminals.

Usage
Interface with any 3rd party button panel for : Light control, Blinds control, Screen control ... Synoptic panels Local relay control Low Voltage light bulb switching

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

CH-UNI8IO
Technical data
Dimensions Weight Installation Connector (Cresnet) Connector ( Input ) Connector ( Output )

Product Manual

: 50 x 42 x 24 : 40 g : Fits in standard 55mm UP/AP-switchboxes : 4-pin mini phoenix 1.5mm2 : 9 P. Screw terminal 8 IN / 1 x GND : 10 P. Screw terminal 8 OUT 1 x +5VDC ( only for LED mode ) 1 x +24VDC ( max. 300mA ) : Crestron Viewport or Toolbox : 24 VDC : all LEDs on 45mA / all LEDs off 22mA : 1W : CNWM-LT9 : bidirektional symmetrical databus : Interface incl. 1 x. 4-pin phoenix connector : 8 x for LED ~5mA / 5VDC

ID setup Power required Power usage LED-MODUS Cresnet power factor Crestron Device Library Cresnet Includes Outputs LED - MODUS with internal 5VDC power provision

Output pen Collector - MODUS : max. current for one output is 100mA With external power provision Maximum Current all output together : 5VDC, total 500mA : 12VDC, total 400mA : 24VDC, total 300mA : 48VDC, total 150mA Inputs Impuls time : 8 x. for buttons or switches to GND : minimum. 10ms

Typical applications

Interface with any 3rd party button panel for : Light control, Blinds control, Screen control ... Synoptic panels Local relay control Low Voltage light bulb switching

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

CH-UNI8IO Layout Front

Product Manual

Setup
Example wiring diagram INTERNAL LED MODUS

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

CH-UNI8IO
Example wiring diagram EXTERNAL MODUS

Product Manual

!!!! IMPORTANT !!!! In External mode it is critical to take the total output current for the module into account. Not doing so can damage the module.
MAX output for 1 output is 100mA. MAX output current for all outputs together depends on the supply voltage : 5VDC, max 500mA 12VDC, max 400mA 24VDC, max 300mA 48VDC, max 150mA Some R-LED calculatation examples : Power supply = 12VDC LED current is 100mA 12 / 0.1 = 120 Ohm Power supply = 48VDC LED Current is 50mA 48 / 0.05 = 960 Ohm

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

CH-UNI8IO
Cresnet Connections

Product Manual

Note: Before making any connections, CRESTRON recommends that all power is off and the installer reviews the latest revision of the network interconnection drawing (DOC5411i). Connect the CH-UNI8IO to the Cresnet network via a Cresnet network cable (CRESNET cable). This cable is not supplied with the CH-UNI8IO but can be obtained from Crestron International.

Cresnet Hook-up

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

CH-UNI8IO
Cresnet ID

Product Manual

Every equipment and user interface within the network requires a unique identity code (NET ID). These codes are recognized by a two-digit hexadecimal number from 03 to FE. The NET ID of each unit must match an ID code specified in the Simpl Windows program. Use the following methods to change NET ID of the CH-UNI8IO. Method A: (Viewport) 1. Ensure that the CH-UNI8IO.is connected to the control system. 2. Open the Crestron viewport and connect to the control system (RS-232 or IP) 3. From the viewport menu, select Functions -> Set network ID. The software checks the network and then opens the Set Network ID window. 4. In the Set Network ID window, select the CNMW-LT9 from the current network devices text window. 5. Select the new NET ID for the CH-UNI8IO. From the choose the new network ID for the selected device (HEX): text box. 6. Click the Set ID to initiate the change. This will display the ID command has been set window. 7. In the Command complete window, click OK. 8. In the current network devices text window, verify the net NET ID code. 9. In the Set network ID window, click close.

Set Network ID (viewport)

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

CH-UNI8IO
Method B: (Toolbox)

Product Manual

1. Ensure that the CH-UNI8IO is connected to the control system. 2. Open Crestron Toolbox and connect to the control system via Tools -> Manage Address Book 3 After setting the correct parameters, click OK to return to the Crestron Toolbox main window. 4 Click Tools | Network Device Tree, or click the network device tree icon to display the Network Device Tree window. Use the Address Book icon or the drop-down list at the lower left of the window to select the appropriate address for the devices in the system. Communications are confirmed when the network devices are displayed.

Network Device Tree (Toolbox)

5 To view a specific device, expand the network device tree by clicking +. Expand the network device tree until the device to be managed is selected. Right-click the desired NET ID to open the sub-menu.

Change Network ID (Toolbox)

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

CH-UNI8IO Programming

Product Manual

The next subsections describe a sample SIMPL Windows program that utilizes a CH-UNI8IO. It provides a description of how to actually create the SIMPL Windows program. NOTE: The following descriptions assume that the reader has knowledge of SIMPL Windows. If not, please refer to the extensive help information provided with the software. Minimal software requirements SIMPL Windows 2.01.06 Ops. for CNX: 5.12.63X/W Ops. for 2 series: C2-1014.cuz *check website www.crestron.com for latest OPS and software versions*

Configuration manager
A CH-UNI8IO needs to be defined as a CNWM-LT9 in Simpl Windows.

Hardware configuration

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

10

CH-UNI8IO
Programming manager
The CNWM-LT9 symbol has 9 digital press and fb (feedback) signals.

Product Manual

CNMW-LT9 symbol

*The first 8 fb signals (fb1-fb8) represent the 8 LEDS of the CH-UNI8IO. The first 8 press signals (press1-press8) represent the 8 button inputs.

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be

11

CH-UNI8IO
Troubleshooting

Product Manual

If further assistance is required, please contact a Crestron Technical Support representative or submit your question on the Crestron True Blue On Line Service (www.crestron.com)

Further Inquiries
If after reviewing this Operations Guide on the CH-UNI8IO you cannot locate specific information or have questions, please take advantage of Crestron's award winning customer service team by calling:

In Europe, call Crestron International at +32-15-50-99-50. In the UK, call Crestron UK at +44-20.845.74.007. In Germany, call Crestron Germany at +49-731.96.28.10. In France, call Crestron France at +33-1-47-91-00-00. In Spain, call Crestron Iberica at +34.952.76.82.33 In the Benelux, call Crestron Benelux at +32-15-50-40-70.

Crestron International 2 Oude Keerbergsebaan 2820 Rijmenam Belgium Tel: +32 15 50 99 50 info@crestron-int.be www.crestron-int.be