You are on page 1of 64

Allen-Bradley

Bulletin 2100

CENTERLINE
Motor Control Centers
(Cat. No. 2100-5.0)

Instruction Manual

Please Read!

This manual is intended to guide qualified personnel in the installation of CENTERLINE Motor Control Centers. When additional information is required relating to the installation and/or operation of CENTERLINE Motor Control Centers, refer to your local Allen-Bradley Sales Office. For further instructions regarding the handling, installation, operation, and maintenance of motor control centers, refer to NEMA Publication ICS 2.3. Before installing and operating your CENTERLINE Motor Control Center, carefully read this manual, read all related procedures and instructions, and observe all precautions. Because of the variety of uses and applications for this equipment, the user must be satisfied with the acceptability of each application and use of the equipment. In no event will Allen-Bradley Company, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The illustrations shown in this manual and any referenced publication are intended solely to illustrate the text of the manual or referenced publication. Because of the many variables and requirements associated with any particular installation, the Allen-Bradley Company, Inc. can not assume responsibility or liability for actual use based upon the illustrative uses and applications.

Important User Information

Reproduction of the content of this manual and/or related procedures/instructions, in whole or in part, without the written permission of the Allen-Bradley Company, Inc. is prohibited. ATTENTION and IMPORTANT notes are used throughout this manual to make you aware of safety considerations: ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attention notes help you to identify a hazard, avoid a hazard, and recognize the consequences.

Important: Identifies information that is especially important for successful application and understanding of the product.
CENTERLINE is a registered trademark of Allen-Bradley Company, Inc.

-2

Publication 2100-5.0 - October 1995

Table of Contents

General Information

+D=FJAH  General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Nameplate Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 UL / CSA Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Short Circuit Rating Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 Series Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4 Series Lettering Units & Sections . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5 Receiving, Handling, and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6 +D=FJAH Location Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Mounting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Securing a Motor Control Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Seismic Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Joining & Splicing: New Motor Control Centers . . . . . . . . . . . . . . . . . 2-5 Joining & Splicing Existing Motor Control Centers . . . . . . . . . . . . . . . 2-5 Joining & Splicing NEMA Type 3R Motor Control Centers . . . . . . . . . . 2-5 Bus Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7 Installing & Joining NEMA Type 1 and Type 12 Pull Boxes . . . . . . . . . 2-7 +D=FJAH ! Conduit Installing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Bottom Entry Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Top Entry Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Installing Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Incoming Line Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Main Fusible Disconnect and Main Circuit Breaker . . . . . . . . . . . . . 3-2 Cable Bracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 Incoming Line Brace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 +D=FJAH " Installing Plug-In Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 Removing Plug-In Unit From a Section (1.0 Space Factor or Larger) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 Removing Support Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3 Removing Plug-In Unit From a Section (0.5 Space Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4 Removing Support Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 +D=FJAH # Locking Provisions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3 +D=FJAH $ Final Check Before Energizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1

Installation Procedures

Conduit and Cable Installation

Installing and Removing Plug-In Units

Operator Handle and Unit Interlock Final Check List Before Energizing

Publication 2100-5.0 - October 1995

tocii

Table of Contents Bulletin 2100 Centerline Motor Control Centers

Energizing Equipment

+D=FJAH % Energizing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 +D=FJAH & Maintenance Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1 Disconnect Switch Contact Lubrication . . . . . . . . . . . . . . . . . . . . . . . 8-3 Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4 +D=FJAH ' +D=FJAH  Order Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1 Recommended Spare Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1 +D=FJAH  +D=FJAH 

Maintenance

Maintenance After Fault Condition Renewal Parts

Parts Illustrations Purchased Components and Additional Instruction Sheets

Publication 2100-5.0 - October 1995

+D=FJAH

General Information
General Description

CENTERLINE Motor Control Centers consist of one or more vertical sections containing electromagnetic and/or solid state control devices that are prewired and tested within modular plug-in or frame mounted (hard-wired) units. Line power is distributed throughout the motor control center through an isolated bus work structure. The main horizontal bus is located in the center of the section. The center-fed 300 ampere rated vertical bus supplies power to the individual units above and below the horizontal bus for an effective 600 ampere capacity, allowing virtually unrestricted unit arrangement. The individual units house a wide variety of power and logic devices. Plug-in units are mounted on unit support pans within the section, and stab assemblies on the back of the unit plug onto the vertical bus. Mechanical interlocks prevent unit doors from being opened while units are energized.

Nameplate Data

Each vertical section has a nameplate located on the vertical wireway door. On special width sections, the nameplate is located on the section door. See Figure 1.1. Information on nameplates include: catalog number / serial number series letter of the section maximum bus bar voltage and current rating section location number

Figure 1.1 Section Nameplate

Publication 2100-5.0 - October 1995

1-2

General Information

Each individual plug-in and frame mounted unit also has an identification nameplate. The unit nameplate is located on the interior of the bottom plate of plug-in units or on the interior right hand side plate of the frame mounted units. See Figure 1.2. The unit nameplate for each plug-in or frame mounted unit includes: catalog number / serial number series letter of the unit device size all maximum ratings

Figure 1.2 Unit Nameplate

When communicating with Allen-Bradley about a particular motor control center or motor control center unit, the catalog number or serial number and series letter are required to properly identify the equipment.
UL / CSA Marking

CENTERLINE Motor Control Centers (MCCs) are listed by Underwriters Laboratories, Inc. (UL), Standard for Safety UL 845 and certified by the Canadian Standards Association (CSA), Standard C222, No. 14. Due to standards harmonization, a motor control center may also carry the ULc designation. UL c is comparable to CSA certification. All vertical sections and units listed with UL will carry the UL label. All vertical sections and units certified to CSA standards will carry the CSA or ULc mark. Vertical sections and units are labeled independently. Therefore, it is possible to have combinations of labeled and non-labeled sections and units in the same motor control center. Vertical sections and structure options that are UL listed and CSA/ULc certified are marked accordingly. For a section to carry the UL and/or CSA/UL c designation, all of its components must be UL listed and/or CSA/ULc certified. The UL and/or CSA/ULc designation is an integral part of the section nameplate. See Figure 1.1.

Publication 2100-5.0 - October 1995

General Information

1-3

Units and unit options that are UL listed and CSA/ULc certified are marked accordingly. For a unit to carry the UL label and/or CSA/ULc designation, all of its options must be UL listed and/or CSA/ULc certified. The UL designation is located on the interior of the bottom plate of plug-in units or on the interior right-hand side plate of frame mounted units. See Figure 1.3.
Figure 1.3 UL Label and CSA Designation for Units

Short Circuit Rating Label

Motor control center vertical sections that are UL listed and/or CSA/ULc certified will carry a short circuit rating label. The short circuit rating label for a vertical section is located on the inside of the vertical wireway door of standard sections or on the interior right-hand side plate of special width sections. See Figure 1.4.
Figure 1.4 Short Circuit Label for Sections

Motor control center units that are UL listed and/or CSA/ULc certified will carry a short circuit rating label located on the bottom plate of plug-in units or on interior right-hand side plate of frame mounted units. See Figure 1.5.
Figure 1.5 Short Circuit Label for Units

Publication 2100-5.0 - October 1995

1-4

General Information

!
Series Identification

ATTENTION: Read the following information BEFORE adding new sections or units to an existing CENTERLINE Motor Control Center.

Table 1A gives the history of series letter changes for structures and units since the original design of the CENTERLINE MCC manufactured in the United States.
Table 1.A Series Identification SECTIONS

Series Letter

Scope

Description of Change

Date Implemented in U.S.

A B C D E F G G H J K L A B C D E F G H J

All All All All All 42K 65K All All All All All Sizes All Sizes Size 5 All Sizes All Sizes All Sizes All Sizes Size 5 Size 3 Size 6 Size 15 CB Units & Size 12 Disc Units 21A thru 54A All Sizes All Sizes

Original design Changed terminal blocks Elimination of external mounting channels Reverse fed 2192s and 2193s Redesign gasketing Modified top horizontal wireway pan to accept units with handle interlock in topmost space factor 42K bracing-incorporates new bus support & cover 65K bracing-incorporates new bus support & cover New hinge design Changed handle, operating mechanism and circuit breaker to Westinghouse series C, 150A, 250A and 400A frame Changed to new unit grounding system Changed to new 600A1200A circuit breaker operating mechanism.
2100 UNITS

271 1176 679 481 1082 1083 185 785 186 1086 590 296 271 1176 679 481 481 1082 1082 484 1084 1288 1088 1086 1189 590 193 494 296 690 392 792 296

K L M N P Q A B C D

0.5 SF CB Units 2103L, 2113, 2193 All Sizes New disconnect external auxiliary contacts and new 600A1200A circuit breaker operating mechanism.
2400 Units

Original design Changed terminal blocks Changed handle mechanism to Westinghouse MCPs Changed from ITE to AB 400A disconnect Changed from Bul. 709 series K starters to Bul. 500 line starters Redesign of gasketing, wraparound and unit support pan for Bul. 700 line. Redesign of gasketing, wraparound and unit support pan for Bul. 500 line. Changed to new door, CB mechanism & control station Changed to Bul. 500 series L Changed to new PCP 100A disconnect Changed to Bul. 500 series B starters Changed handle, operating mechanism and circuit breaker to Westinghouse series C, 150A, 250A, and 400A frame Changed to Bul. 100 line contactors in 21A, 30A, 45A SMC units and original design 24A, 35A,54A SMC units. Changed to new unit grounding system and 600A, 800A, and 1200A bolted pressure switch. Changed to PCP 200A and 400A disconnect, rerated vacuum Bul. 2112 and 2113 and new pilot device offerings. External auxiliary on circuit breakers

All sizes 18A, 24A, 30A 18A, 24A, 30A All Sizes

Original design Changed to Series B, Bulletin 194R, 30A disconnect. Changed to (3) Bulletin 800E pilot devices on 0.5 space factor units. New disconnect external auxiliary contacts and new 600A1200A circuit breaker operating mechanism.

Publication 2100-5.0 - October 1995

General Information

1-5

!
Series Lettering Units & Sections

ATTENTION: Read the following information BEFORE adding new sections or units to an existing CENTERLINE Motor Control Center.

When using sections in conjunction with units of different series letters, consult the MCC Modifications for Unit and Structure Compatibility table below.
Table 1.B MCC Modifications for Unit and Structure Compatibility

Plug-In Units

No Additional Parts

Requires Style 1 Unit Support Pan

Requires Style 3 (or 2) Unit Support

Requires Style 3 Unit Support Pan w/ Bushing

Requires Alternate Top Horizontal Wireway Pan

Requires Door Gasketing Kit

Requires Retrofit Kit

Requires Ground Bus Kit

If mounted in this type of section Space Factor

Required

Series

Pan

2100HUAJ1

2100HUA1 2100HUJ1

2400HUSPA1 2400HUSPJ1

2100HNA4A1 2100HNA4J1 2100HNA4A2 2100HNA4J2

2100GJ10

2400HR1

2400HGS1

AE NEMA Type 1 Series AD 1.0 or larger 0.5 NEMA Type 1 Series EJ FL M or later

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
unit handle-to-floor height limitation,

4 4 4

N or later AE FL M or later N or later AL M or later AE FL M or later N or later AE FL M or later N or later AL M or later

1.0 or larger 0.5

4 4

NEMA Type 1 Series K or later

1.0 or larger 1.0 or larger 0.5

NEMA Type 1 w/ gasket or Type 12 Series AD

4 4

4 4 4 4

NEMA Type 1 w/ gasket or Type 12 Series EJ 1.0 or larger 0.5

NEMA Type 1 w/ gasket or Type 12 Series K or later

1.0 or larger

When installing unit in topmost location in vertical section, care must be taken to comply with the National Electrical Code 6 6

as identified in NEC Article 3808(a) and UL Standard for Safety 845. A unit operating handle extender (2100HNE1) is available which allows you to comply with this restriction. See Publication 21003.0 for catalog number and pricing.

When Bulletin 2100 0.5 space factor units are ordered unassembled or ordered for existing sections, a centralized wiring diagram holder kit (2400HWDH) should be ordered. See Publication 21003.0 for catalog number and pricing.

Required only if series F or later 1.0 space factor or larger Bulletin 2100 unit is installed in topmost location of series A through E vertical sections. Permits installation of 0.5 space factor plug-in units in existing series E through J Bulletin 2100 vertical sections. pricing. A wire can be used to ground units rather than installing a ground bus. See Publication 21005.12. See Publication 21003.0 for catalog number and

Publication 2100-5.0 - October 1995

1-6

General Information

Receiving, Handling, and Storage

CENTERLINE Motor Control Centers are shipped upright in shipping blocks of one to three front-mounted sections or two to six back-to-back sections as standard. All motor control centers (MCCs) are mechanically and electrically tested before shipment. Each MCC is provided with a lifting device for handling convenience (lifting device is optional on NEMA Type 3R). The motor control center is bolted to the shipping skid and further packaged to protect it during upright shipments. (Refer to Publication 21005.5 for receiving, handling, and storage instructions. This publication is shipped with each MCC, attached to the outside of the MCC within a layer of clear plastic wrap. For additional information, consult NEMA ICS 2.3.) ATTENTION: Motor control centers are top heavy and front heavy. To avoid personal injury or structural damage to the motor control center, never attempt to lift or to move the motor control center by any means other than the methods outlined in Publication 21005.5, Receiving, Handling, and Storing Motor Control Centers.

Publication 2100-5.0 - October 1995

+D=FJAH

Installation Procedures
Location Planning

When planning the location for your CENTERLINE Motor Control Center, take the following items into consideration: conduits busways overall height alignment with other equipment future needs

In addition, the area must be level and the environment must be compatible with the NEMA enclosure rating of the equipment.
Mounting Considerations

If the motor control center is equipped with optional external mounting channels or is mounted on a pad, the height to the center of the top handles must be checked for compliance with NEC 3808(a) and UL Standard 845. If handles are higher than 67 (2000mm), then Unit Operating Handle Extender should be added to these handles (catalog number 2100NE1). Anchor bolts (1/2(13mm)) may be pre-located and embedded in the MCC foundation prior to installation. Two bolts per vertical section fasten the motor control center through its internal mounting angle to the foundation (corner sections require three (3) bolts and 40-inch wide sections require four (4) bolts). See Figures 2.1 through 2.6.
Figure 2.1 Mounting Dimensions for 15^ and 20 ^ Deep Front-Mounted Section

Securing a Motor Control Center

Publication 2100-5.0 - October 1995

2-2

Installation Procedures

Securing a Motor Control Center continued

Figure 2.2 Mounting Dimensions for 30^ and 40 ^ Deep Back-To-Back Section

Figure 2.3 Mounting Dimensions for 25^ Deep Back-To-Back Section

Publication 2100-5.0 - October 1995

Installation Procedures

2-3

Securing a Motor Control Center continued

Figure 2.4 Mounting Dimensions for 15^ and 20^ Deep N 40^ Wide Front-Mounted Section

Figure 2.5 Mounting Dimensions for NEMA Type 3R Section

Figure 2.6 Mounting Dimensions for 15^ and 20 ^ Deep Corner Section

Documentation packages shipped with assembled MCCs include a CAD drawing (Form 385E) showing an MCC floor plan layout.

Publication 2100-5.0 - October 1995

2-4

Installation Procedures

Seismic Requirements

When secured as indicated, (see Figure 2.7 for Bolt Down Securing or Figure 2.8 for Weld Down Securing), the CENTERLINE Motor Control Centers (20 (508mm) only) will withstand seismic activity Zones 0 to 4. Zone 4 is the maximum zone magnitude as defined by the Uniform Building Code (UBC).
Figure 2.7 Seismic Bolt Down Requirements

Figure 2.8 Seismic Weld Down Requirements

Publication 2100-5.0 - October 1995

Installation Procedures

2-5

Joining & Splicing: New Motor Control Centers

A main horizontal bus splice kit must be installed between shipping blocks of new motor control centers in order to connect the main horizontal bus. In addition, the neutral bus splice kit (if required) and the ground bus splice kit must be installed between shipping blocks. Refer to 21005.1 Joining & Splicing Vertical Sections for joining and splicing 15 (381mm) or 20 (508mm) front-mounted sections and 30 (762mm) and 40 (1016mm) deep back-to-back construction. A main horizontal bus, a neutral bus (if required), and a ground bus splice kit must be installed when adding to existing motor control centers. When adding to existing motor control centers, you must identify the series of the motor control center that you will be adding to. If the existing motor control center is Series A or B, you must consult the factory for joining and splicing procedures. When the existing motor control center is Series C or later, refer to Publication 21005.1, Joining and Splicing Vertical Sections for joining and splicing 15 (381mm) or 20 (508mm) front-mounted sections and 30 (762mm) and 40 (1016mm) deep back-to-back construction. A main horizontal bus, a neutral bus (if required), and a ground bus splice kit must be installed between the internal sections for new and existing NEMA Type 3R motor control centers. Refer to Publication 21005.1, Joining and Splicing Vertical Sections for splicing Type 3R internal sections. Refer to Instruction Sheets:Drawing No. 40110077(shipped with NEMA Type 3R sections) for instructions on joining the NEMA Type 3R external cabinets. Figure 2.9 on the next page is a copy of this drawing for reference purposes only.

Joining & Splicing Existing Motor Control Centers

Joining & Splicing NEMA Type 3R Motor Control Centers

Publication 2100-5.0 - October 1995

2-6

Installation Procedures

Figure 2.9 Joining Instructions for NEMA Type 3R Sections

Publication 2100-5.0 - October 1995

Installation Procedures

2-7

Bus Torque Specifications

Tighten all bus connections with a torque wrench and socket at intervals established by your maintenance policy. If a torque wrench is not available, tighten until the conical spring washer is flat. Refer to the table below for bus connection torque values.
Description
Horizontal to Vertical Bus Connection

Required Torque
38 ft-lb (50 Nm

Horizontal Splice

38 ft-lb (50 N

m) )

Lug Attachment Bolts

45 ft-lb (61 Nm

The torque values can also be found on the information label located on the interior of the vertical wireway door or on the interior right-hand side plate of frame mounted units or in Publication 2100 5.0.1, CENTERLINE Motor Control Centers Start-Up Procedures.

Installing & Joining NEMA Type 1 and Type 12 Pull Boxes

When pull boxes are supplied with your motor control center, refer to Publication 21005.28, Installing a Pull Box on a Bulletin 2100 Vertical Section for installing and joining the pull box onto the vertical section.

Publication 2100-5.0 - October 1995

2-8

Installation Procedures

Publication 2100-5.0 - October 1995

+D=FJAH

Conduit and Cable Installation


Conduit Installing
When installing conduit, make sure it is installed so that water and moisture can not enter or accumulate in the MCC enclosure. Conduits must be installed so that they are compatible with the NEMA rating of the MCC. The conduit should be placed away from the horizontal ground bus to avoid physical damage. It is recommended that the conduit be positioned so as to minimize cable bending and maintain relative vertical alignment to incoming bus pads and terminals of main fusible disconnects or main circuit breakers.

Bottom Entry Conduit


Prepare the installation site so that the foundation is level. Before the MCC is installed, place and stub up conduit approximately 2 (51mm) above floor level. Make sure that all incoming conduit is clear of the horizontal ground bus. 1. For approximate section base dimensions and ground bus locations, refer to Chapter 2, Installation Procedures, Figures 2.1 through 2.6. 2. For approximate bottom entry locations and wiring schemes for main fusible disconnects, main circuit breakers, and incoming line compartments, refer to Publication 21004.2, Mains and Incoming Lines Dimension Reference.

Top Entry Conduit


After the MCC is in place, is leveled, and the sections are joined and spliced, bring conduit into the top of the incoming section. 1. Remove the lifting angle and top plate. Modify the top plate for the necessary conduit entries. (This method helps guard against metal chips falling into the MCC, which can cause serious damage.) 2. Replace the top plate and lifting angle bolts. (This guards against dust or dirt entering the top horizontal wireway. 3. Make sure that all incoming conduit is clear of the horizontal ground bus. 4. For approximate location of the horizontal ground bus mounted in the top horizontal wireway, refer to Publication 21004.2, Mains and Incoming Lines Dimension Reference.

Publication 2100-5.0 - October 1995

3-2

Conduit and Cable Installation

5. For space availability for incoming cables, refer to the documentation package shipped with assembled MCCs. This package includes Form 385E, a CAD drawing showing available space. 6. For approximate top entry locations and wiring schemes for main fusible disconnects, main circuit breakers, and incoming line compartments, refer to Publication 21004.2, Mains and Incoming Lines Dimension Reference.
Installing Cable

Install cable when the temperature is above freezing (32F or 0C) (unless cable is suitable for installation at temperatures below freezing). This will help prevent cable insulation from cracking or splitting. Motor control centers are rated for use with 75C cable for current ratings above 100 amperes. Cable must be sized using 75C column in NEC Table 31016. The actual temperature rating of the lugs used is not relevant.

Incoming Line Compartment


Top or bottom entry to the incoming line section bus is straight through to the connection terminals. The vertical bus provides pads for the incoming lugs. The lug selection should be based on the size, number, and type of conductor. 1. Use mechanical screw type lugs when the incoming lines available short circuit current is under 42,000 amperes RMS symmetrical. 2. Use crimp type or compression type lugs when the incoming lines available short circuit current is above 42,000 amperes RMS symmetrical.

Main Fusible Disconnect and Main Circuit Breaker


Top entry is straight through to the line side of the main fusible disconnect and main circuit breaker. However, for bottom entry, the connection scheme varies depending on the rating of the main device. In some cases, the bottom entry goes to the top or line side of the main fusible disconnect or main circuit breaker. In other cases, the bottom entry would go straight through to the bottom of the main fusible disconnect or main circuit breaker. This is referred to as reverse fed.

Publication 2100-5.0 - October 1995

Conduit and Cable Installation

3-3

Mechanical screw type lugs are supplied as standard with all main fusible disconnects or main circuit breakers. Crimp type or compression type lugs are also available.

Cable Bracing
The CENTERLINE MCC bus work system has been tested and is qualified to withstand maximum short circuit forces exceeding the short circuit withstand ratings for the MCC. Incoming line cables and outgoing feeder cables also need to be supported to withstand the same short circuit forces. There are many sizes and types of cables, as well as different means by which the cables can be supported. Acceptable methods are shown below in Figures 3.1, 3.2, and 3.3. In Figure 3.1, glass fiber reinforced tape or glass filament tape is used. The taping should be continuous from the point the cables enter the MCC to the point the cables are terminated. It is important that cables are wrapped several times for additional strength. Cable slack should be drawn up during wrapping so that individual cables are supported together by the tape as a single mass.
Figure 3.1 Securing Cables with Glass Tape

Publication 2100-5.0 - October 1995

3-4

Conduit and Cable Installation

Cable Bracing continued


In Figure3.2, cables are lashed in a figure 8-type configuration using nylon rope. The rope lashing should be continuous from the point the cables enter the MCC to the point the cables are terminated. Other types of rope lashing may be acceptable. However, cable slack should be drawn up during wrapping so that individual cables are supported together by the rope as a single mass.
Figure 3.2 Securing Cables with Nylon Rope

In Figure 3.3, a hardwood brace (maple hardwood) made for the specific application is used. Holes are bored approximately the size of the cable diameter. Several bolt holes are also bored the breadth of the hardwood brace. The brace is cut in two pieces and is used as a clamp to secure the cables.
Figure 3.3 Securing Cables with Hardwood

Publication 2100-5.0 - October 1995

Conduit and Cable Installation

3-5

Cable Bracing continued


The through bolts are inserted into the brace and tightened so that the cables are held tightly in place. A second form of hardwood brace (not shown) is a yolk type in which the cables are passed through. Holes should be small enough to provide a snug fit for the cables. The connectors or lugs are attached to the cables and cables are bolted to the terminals. When using the hardwood bracing method, the cables should be braced every 12 (305mm) when the incoming lines available short circuit current is below 42,000 amperes RMS and every 6 (153mm) when the incoming lines available short circuit current is 42,000 amperes RMS or greater.

Incoming Line Brace


Allen-Bradley manufactures an incoming line brace similar to the hardwood clamping type brace. To order an incoming line brace, contact your local Allen-Bradley sales office and ask for assembly number 4011384801. Important: Connectors should be installed so that they are in line with each other and so that there is proper spacing between phases. Make sure that hardware is torqued according to the required specifications.

Publication 2100-5.0 - October 1995

3-6

Conduit and Cable Installation

Publication 2100-5.0 - October 1995

+D=FJAH
Installing and Removing Plug-In Units

!
Installing Plug-In Units

ATTENTION: Turn off power to unit before installing or removing unit.

For unit installation, refer to Publication 21005.12, Installing Units with Vertical Operating Handles, and Publication 24005.2, Installing Units with Horizontal Operating Handles.

Removing Plug-In Unit From a Section (1.0 Space Factor or Larger)

1. Make sure disconnect handle is in the OFF/O position. 2. Turn door latches 1/4 turn. 3. Open door completely.

It is not necessary to remove the unit door in order to remove a unit from a section. However, steps 2 and 3 below may still be necessary even when door is not removed. 1. Remove hinge pins slide up with a screwdriver. 2. Remove control station, if present. Also remove wiring from meters, if present. 3. Hang control station on front of unit using square holes adjacent to top unit latch.
Publication 2100-5.0 - October 1995

4-2

Installing and Removing Plug-In Units

Removing Plug-In Unit From a Section (1.0 Space Factor or Larger)

continued

1. Swing door to near closed position. 2. Lift door off outward.

1. Disengage captive latches located at front of unit, one at top and one at bottom. 2.0 space factor units and larger have two latches at top. 2. Detach wiring/terminal block(s) from unit. Place wires/terminal blocks in line with wiring clearance tunnel. It is not necessary to stuff wires/terminal blocks into vertical wireway.

1. Pull unit forward (outward) using handle provided at lower left of unit and the tab at the upper right of unit as finger holds.
Publication 2100-5.0 - October 1995

Installing and Removing Plug-In Units

4-3

Removing Support Pan

1. Pry the plastic retaining clip from the right hand unit support using a screwdriver. This is visible in the vertical wireway. 2. Lift the right side of the support pan approximately 4 (102mm).

1. Pull right side of support pan forward to release from left rear slot on structure. 2. Push back on left side of support pan until support pan is free from structure. NOTE: Vertical sections may be supplied with plug-in stab opening protective caps, manual shutters, or automatic shutters. Refer to Step 3 if any of these options are supplied. 3. Carefully install protective caps or close manual shutters after unit is removed. Automatic shutters will close as units are removed.

Publication 2100-5.0 - October 1995

4-4

Installing and Removing Plug-In Units

Removing Plug-In Unit From a Section (0.5 Space Factor

1. Make sure disconnect handle is in the OFF/O position. 2. Turn door latches 1/4 turn. 3. Open door completely.

Door removal is not necessary when removing a unit. 1. Remove hinge pins slide up with a screwdriver. 2. Swing door to near closed position. 3. Lift door off outward.

1. Detach wiring/terminal block from unit. 2. Place wiring/terminal block in vertical wireway to right of unit.

Publication 2100-5.0 - October 1995

Installing and Removing Plug-In Units

4-5

Removing Plug-In Unit From a Section (0.5 Space Factor

continued

1. Push latch mechanism to the left with right hand. 2. Pull unit forward (outward) with left hand using the left top portion of the disconnect handle flange as finger hold.
Removing Support Pan

1. Pry the plastic retaining clip from the right hand unit support using a screwdriver. This is visible in the vertical wireway. 2. Lift the right side of the support pan approximately 4 (102mm).

1. Pull right side of support pan forward to release from left rear slot on structure. 2. Push back on left side of support pan until support pan is free from structure. NOTE: Vertical sections may be supplied with plug-in stab opening protective caps, manual shutters, or automatic shutters. Refer to Step 3 if any of these options are supplied. 3. Carefully install protective caps or close manual shutters after unit is removed. Automatic shutters will close as units are removed.
Publication 2100-5.0 - October 1995

4-6

Installing and Removing Plug-In Units

Publication 2100-5.0 - October 1995

+D=FJAH

Operator Handle and Unit Interlock


The flange operator handle, for either a disconnect or circuit breaker, is an integral part of the unit insert. No adjustment is required. The operator handle is interlocked with unit door as outlined by UL 845. When the unit door is closed and the operator handle is in the ON/I position, the defeater located just below (1.0 space factor or larger units) or just to the right (0.5 space factor units) of the pivot point of the handle, must be deliberately operated to be able to open the unit door. See Figure 5.1 and 5.2.
Figure 5.1 Operating Handle Defeater for 1.0 Space Factor and Larger

Figure 5.2 Operating Handle Defeater for 0.5 Space Factor

Publication 2100-5.0 - October 1995

5-2

Operator Handle and Unit Interlock

When the unit door is open and the operator handle is in the OFF/O position, the defeater lever must be held up (1.0 space factor and larger units) or held to the left (0.5 space factor units) in order to move the operator handle to the ON/I position. See Figure 5.3 & 5.4.
Figure 5.3 Defeater Lever for 1.0 Space Factor and Larger

Figure 5.4 Defeater Lever for 0.5 Space Factor

Publication 2100-5.0 - October 1995

Operator Handle and Unit Interlock

5-3

Locking Provisions

To lock the small and medium operator handle in the OFF/O position, put the shackle of the lock through the opening of the operator handle. The opening can accommodate up to three (3) padlocks. See Figure 5.5.
Figure 5.5 Locking Small and Medium Handle in OFF/O Position, 1.0 Space Factor or Larger (Smaller Handle Shown)

The 0.5 space factor units utilize the small handle. The small handle can be locked in the OFF/O position the same way the small handle for 1.0 space factor and larger units can be locked. See Figure 5.6.
Figure 5.6 Locking Small Handle in OFF/O Position, 0.5 Space Factor

Publication 2100-5.0 - October 1995

5-4

Operator Handle and Unit Interlock

ATTENTION: Locking an operating handle in the ON/I position may be in conflict with local codes and emergency shut down requirements.

To lock the small operator handle in the ON/I position, drill out the top pre-located hole to 3/8 (9.5mm) diameter maximum, and padlock. See Figure 5.7 and 5.8.
Figure 5.7 Locking Small Handle in ON/I POSITION, 1.0 Space Factor and Larger

Drill Out

Figure 5.8 Locking Small Handle in ON/I Position, 0.5 Space Factor

Drill Out

Publication 2100-5.0 - October 1995

Operator Handle and Unit Interlock

5-5

ATTENTION: Locking an operating handle in the ON/I position may be in conflict with local codes and emergency shut down requirements.

To lock the medium operator handle in the ON/I position, drill out the bottom pre-located hole to 3/8 (9.5mm) diameter maximum, and padlock. See Figure 5.9.
Figure 5.9 Locking Medium Handle in ON/I Position

Drill Out

To lock the large operator handle in the OFF/O position, put the shackle of the padlock through the opening of the operator handle. The opening can accommodate up to three (3) padlocks. See Figure 5.10.
Figure 5.10 Locking Large Handle in OFF/O Position

Publication 2100-5.0 - October 1995

5-6

Operator Handle and Unit Interlock

ATTENTION: Locking an operating handle in the ON/I position may be in conflict with local codes and emergency shut down requirements.

To lock the large operator hand in the ON/I position, drill out the pre-located hole to 3/8 (9.5mm) diameter maximum, and padlock. See Figure 5.11.
Figure 5.11 Locking Large Handle in ON/I Position

Drill Out

Publication 2100-5.0 - October 1995

Operator Handle and Unit Interlock

5-7

The unit interlock, provided with each 1.0 space factor or larger plug-in unit, prevents the unit from being plugged into or unplugged out of a vertical section with the operator handle in the ON/I position. The unit interlock also provides a means by which the unit can be locked out with a padlock preventing installation of the unit into a vertical section. The lockout feature of the unit interlock can be used with the operator handle in either the ON/I or OFF/O position. See Figure 5.12.
Figure 5.12 Unit Interlock, 1.0 Space Factor or Larger

Publication 2100-5.0 - October 1995

5-8

Operator Handle and Unit Interlock

The unit interlock provided with the 0.5 space factor units also prevents the unit from being plugged into or plugged out of a vertical section when the operator handle is in the ON/I position. Just as with the unit interlock for 1.0 space factor and larger units, the interlock mechanism for the 0.5 space factor unit has a lockout feature. This lockout can be used in either the ON/I or OFF/O position. See Figure 5.13.
Figure 5.13 Unit Interlock, 0.5 Space Factor

Publication 2100-5.0 - October 1995

+D=FJAH

Final Check List Before Energizing


The following procedure is provided as general guidance for a final check before energizing a newly installed CENTERLINE Motor Control Center. Use this final check list in conjunction with procedures listed in Publication 21005.0.1, CENTERLINE Motor Control Centers Start-Up Procedure. ATTENTION: To ensure the safety of personnel performing the Final Check, make sure that the motor control center remote power source(s) is disconnected and locked in the OFF/O position.

Final Check Before Energizing

1. Remove all blocks or temporary holding means used for shipment from all component devices in the motor control center. 2. Check enclosure and units to see that they have not been damaged so as to reduce electrical spacings. 3. Check the motor control center and verify that it is installed properly, making sure that it is level, supported, and anchored (if necessary or required). 4. Check the integrity of splice and other accessible bus connections. Torque values can be found on the information label located on the interior of the vertical wireway door or on the interior right-hand side plate of frame mounted units. 5. Check that all ground connections are made properly. 6. Check field wire for proper size. Proper field wire sizing criteria can be found on the information label located on the interior of the vertical wireway door or on the interior right-hand side plate of frame mounted units. 7. Check field wired circuits for agreement with wiring diagrams, and make sure the wiring is clear of live bus areas. 8. Make certain that all incoming and outgoing power wiring is secure and braced to withstand the effects of a fault current. Also make sure that the conduit and/or cabling is well supported.

Publication 2100-5.0 - October 1995

6-2

Final Check List Before Energizing

9. Check to make sure that the voltage and horsepower ratings of the motor agree with the ratings stamped on the unit nameplate of the unit to which it is connected. The unit nameplate is located on the interior of the bottom plate of plug-in units or on the interior right-hand side plate of frame mounted units. 10. Set any adjustable current and voltage trip mechanisms to their proper values. (Circuit breaker trip settings are listed in Publications 21002.3.1 and 21002.3.2.) 11. Where applicable, install power circuit fuses in the fusible switches compliant with local electrical code application requirements. Make sure that fuses are completely inserted into the fuse clips. 12. Where applicable, timers should be set for their proper interval settings. 13. Make sure that the overload relays or heater elements are selected, installed and/or adjusted to the relative full load current shown on the motor nameplate. 14. Manually exercise all switches, circuit breakers, their respective operators, interlocks and any other operating mechanisms to make certain they operate freely. ATTENTION: Do not operate a current transformer with its secondary open.

15. Check all current transformers to make sure that they are wired to their respective devices. Where applicable, remove shorting bars from the secondary of current transformers and make connections to their respective devices. 16. To avoid injury or possible damage to equipment, check and make sure that all barriers and parts that may have been removed during installation have been reinstalled. 17. Before closing the enclosure and/or the individual units, remove all tools, metal chips, scrap wire, and other debris from the motor control center interior. If there is an accumulation of dust or dirt, clean out by using a brush, vacuum cleaner or clean, lint-free rags. Do not use compressed air, because it will redistribute contaminants onto other surfaces.

Publication 2100-5.0 - October 1995

Final Check List Before Energizing

6-3

ATTENTION: Equipment that is sensitive to high test voltages such as meters, solid state devices, and capacitor units, should be isolated.

18. Conduct an electrical insulation resistance test to make sure that the motor control center and field wiring are free from short circuits and grounds. Conduct this test using an insulation resistance tester (megger) with a potential of 5001000 volts. This test should be conducted phase-to-phase and phase-to-neutral in the motor control center. This test should be conducted with all of the switches or circuit breakers opened or in the OFF/O position. Electrical Insulation Resistance Test Typical insulation resistance values are 50 megaohms or greater. Next, check the field wiring. For example, motor cables and/or incoming line cables. Note that the insulation resistance values are affected by humidity or dampness that may cause a considerably lower insulation resistance reading. If this is the case and the insulation resistance values are below 1 megaohm, or the motor control center has been stored in a damp or humid area, it is recommended that the equipment be dried out. Dry out the motor cables by injecting a low voltage current. Use space heaters to dry out the motor control center. When the equipment is dry, repeat the insulation resistance test. The minimum value for insulation resistance on a new installation at start-up or energizing is 1 megaohm. 19. Make sure that all latches are secure. Close and latch all doors, making certain that no wires are pinched. Turn all unit disconnects or circuit breakers to the open or OFF/O position before energizing the motor control center.

Publication 2100-5.0 - October 1995

6-4

Final Check List Before Energizing

Publication 2100-5.0 - October 1995

+D=FJAH

Energizing Equipment
The following procedure is provided as general guidance for energizing a newly installed CENTERLINE Motor Control Center after the Final Check procedure has been completed, (see Chapter 6, Final Check List Before Energizing). Use this procedure in conjunction with procedures listed in Publication 21005.0.1, CENTERLINE Motor Control Centers Start-Up Procedure. ATTENTION: Energizing a motor control center for the first time is potentially dangerous. Serious damage and personal injury can result when the power is turned on. Therefore, only qualified personnel should energize the equipment.

Energizing Procedure
1. Review any additional instructions supplied for the proper operation of special units such as drives, Smart Motor Controllers (SMC), etc., with appropriate personnel. 2. Make sure that there is no load on the motor control center when it is energized. Turn off all of the main and unit disconnect handles. Also, make sure any associated remote devices are turned off. 3. Energize the motor control center remote power source. 4. Energize the main devices followed by the feeder devices and then the branch circuit devices. Always energize from the source of the system, working toward the loads. 5. After all of the disconnect devices have been closed, loads such as lighting circuits, motor starters, contactors, etc. may be energized. A. When power factor correction capacitors are energized along with the motor windings and the start-up procedure requires that the respective motors be jogged or inched, temporarily disconnect the power factor correction capacitors. B. Verify that any acceleration times are within specific application specifications.

Publication 2100-5.0 - October 1995

7-2

Energizing Equipment

Publication 2100-5.0 - October 1995

+D=FJAH

Maintenance
A periodic maintenance program should be established for your motor control center to avoid unnecessary downtime due to neglect. How frequently you service your MCC will depend upon the equipment usage and the environment in which it operates. The following is a suggested checklist. ATTENTION:

De-energize motor control center before servicing.

Maintenance Checklist
1. Inspect the motor control center at least once per year. 2. Carefully inspect doors and enclosure sides for evidence of excessive heat. Generally, any temperature during operation that the palm of your hand can not stand for approximately 3 seconds may indicate a problem. 3. Check for moisture or any signs of dampness or drippings inside the motor control center. Condensation in conduit or dripping from an outside source is a common cause of motor control center failure. Eliminate any source of moisture. Seal off conduit, cracks, and openings that have allowed and/or could allow moisture to enter the MCC enclosure. Dry or replace and clean insulating material that is damp or wet or shows signs of moisture. Check devices such as contactors, circuit breakers, disconnect switches, relays, pushbuttons, etc., for wetness or signs of moisture, corrosion, or contamination. Replace damaged or malfunctioning parts. Make sure that the source or cause of wetness or contamination is identified and eliminated. 4. Check the integrity of bus splice connections. Bus splices can be easily identified by the label located on the interior of the vertical wireway door or on the interior right hand side plate of frame mounted units. Recommended torque values can be found on the information label located on the interior of the vertical wireway door or on the interior right-hand side plate of frame mounted units, and in Chapter 2, Installation Procedures Bus Torque Specifications or in Publication 21005.0.1, CENTERLINE Motor Control Centers Start-Up Procedure.

Publication 2100-5.0 - October 1995

8-2

Maintenance

Maintenance Checklist continued


NOTE: The factory-made power connections are tightened by a computer-controlled torquing system. The following connections should never require re-torquing: Vertical to horizontal bus connections, power conductor to horizontal bus connections. These factory-made power bus connections do not require servicing for the life of the motor control center. 5. Air filters for fans should be periodically cleaned or changed, depending on the environmental conditions. 6. Check for proper function and freedom of movement (no sticking or binding) of the disconnect handle operating mechanisms and their defeater mechanisms. Replace broken, deformed, malfunctioning, or badly worn parts or assemblies. 7. Inspect bus stab connections for wear or corrosion. Wear and/or corrosion can cause increased resistance causing an increased temperature of the contact point which can lead to failure. Replace bus stabs if wear or corrosion is excessive. Lubricate bus stabs with NOOXID grease (catalog number 2100HN18 or 2100HN18T) before replacing the unit into the section. 8. Inspect current carrying parts such as fuse clips, knife blades of disconnects, and line and load terminals of devices for discoloration, corrosion or other signs of abnormalities. 9. Check locking or interlocking devices for proper working condition and capability of performing their intended functions. Adjust, repair, or replace any device if necessary. 10. Check contacts for excessive wear and dirt accumulation. Vacuum or wipe contacts with a soft cloth to remove dirt. Contacts are not harmed by discoloration and/or slight pitting. Contacts should never be filed, as this would reduce the life of the contacts. Contact spray cleaners should not be used, as they cause sticking on magnetic pole faces or in operating mechanisms, interfering with the electrical continuity of the contacts. Contacts should be replaced only after the silver has become badly worn. Always replace contacts in complete sets to avoid misalignment and uneven contact pressure. 11. Check for loose connections on power and control circuit terminals. Loose connections can cause overheating or hot spots that could lead to equipment malfunction or failure. Replace any damaged parts or wiring.

Publication 2100-5.0 - October 1995

Maintenance

8-3

Maintenance Checklist continued


12. Check coils for evidence of overheating cracking, melting, or burning of insulation. If there is evidence of overheating, the coil must be replaced. When a coil needs to be replaced, check for and correct the overvoltage or undervoltage conditions that are causing the coil failure. Be sure to clean any residue of melted coil insulation from other parts of the device, or replace such parts. 13. Check all pilot lights. Replace burned out lamps and/or damaged lenses. 14. Check all fuses. When replacement is necessary, always install the same type and rated fuse that was originally furnished with the motor control center. 15. Remove accumulated dust and dirt by vacuuming. Do not use compressed air, as it may contain moisture and blow debris elsewhere within the enclosure. 16. Refer to individual user policies for periodic servicing of MCCs, and refer to NFPA 70B, Electrical Equipment Maintenance.

Disconnect Switch Contact Lubrication

The disconnect switches used within the MCC units are supplied with proper contact lubrication, and under normal operating conditions should not require further lubrication. However, if a switch that is used frequently becomes difficult to operate or is located in a highly corrosive or caustic environment, it may require lubrication. The lubricant to be used is NOOXID Compound (catalog number 2100HN18 for a 1 pint can or 2100HN18T for a 1 ounce tube.) To obtain the lubricant, contact your local Allen-Bradley sales office, distributor, or Packaged Control Products at Allen-Bradley, Company, Inc. ATTENTION: To prevent injury or death to personnel lubricating disconnect switch contacts, make sure that the motor control center remove power source(s) is disconnected and the respective disconnect(s) is locked in the OFF/O position. In the case of a plug-in unit, remove the unit from the motor control center. ATTENTION: To prevent personal injury or damage to equipment, make sure that the unit handle operator is in the OFF/O position before removing the unit.

Publication 2100-5.0 - October 1995

8-4

Maintenance

Disconnect Switch Contact Lubrication


continued

Instructions
1. For Plug-In Construction If disconnect switch needing lubrication is housed in a plug-in unit, remove the plug-in unit from the motor control center. (For removal of unit, refer to Chapter 4, Unit Removal and Installation.) For Frame Mounted Construction: If disconnect switch needing lubrication is housed in a frame mounted unit, turn off the power source(s) to the motor control center. ATTENTION: To prevent injury or death to personnel lubricating disconnect switch contacts, make sure that the motor control center remote power sources (s) is disconnected and the respective disconnects(s) is locked in the OFF/O position.

2. Remove the line guard cover and retain. 3. Remove and retain the arc hood. This allows access to the disconnects stationary contacts. 4. Generously apply the compound (sufficient enough to cover with a noticeable film) to both sides of the movable contact blades and to the adjacent insides of the stationary contacts. 5. Re-install the arc hood that was removed in Step 3. 6. Re-install the line guard cover that was removed in Step 2. 7. If the lubricated disconnect switch is housed in a plug-in unit, reinstall the unit. (For installation of unit, refer to Publication 21005.12, Installing Units with Vertical Operating Handles). NOTE: If the reasons for lubrication are due to corrosion (for example, a sulfur environment), replacing the unit disconnect may be required to avoid overheating conditions. Lubrication may reduce the problem short term; however, replacing the disconnect switch would be the correct and long term solution.

Publication 2100-5.0 - October 1995

+D=FJAH

Maintenance After Fault Condition

ATTENTION: Disconnect all power sources to the motor control center before diagnosing the cause of the fault condition.

The opening of the short circuit protective device (such as fuses or circuit breakers) in a properly coordinated motor branch circuit is an indication of a fault condition in excess of operating overload. This fault condition must be corrected. Such a condition can cause damage to control equipment. When a fault occurs, de-energize the motor control center, repair the cause of the fault, and inspect all equipment thoroughly per NEMA Standards Publication No. ICS 2.21983 Part ICS 2302 Maintenance of Motor Controllers After A Fault Condition. Make necessary repairs or replacements prior to re-energizing the equipment. Be sure that replacements are of proper rating and are suitable for the application. In certain cases, it may be necessary to conduct an electrical insulation resistance test (megger). For procedure, refer to Chapter 6, Final Checklist Before Energizing.

Publication 2100-5.0 - October 1995

9-2

Maintenance After Fault Condition

Publication 2100-5.0 - October 1995

+D=FJAH

10

Renewal Parts
A Renewal Parts Stocking Program for your motor control center is recommended in conjunction with a maintenance program. This is important for minimizing expensive downtime and when repair is critical. Factors to consider when developing an effective Renewal Parts Stocking Program: 1. The frequency of ONOFF cycling and the amount of ON or operating time. 2. The need for continuous operation, inherent design limitations, environmental considerations, etc. 3. The total number of like devices supplied as original equipment within the motor control center. 4. The individual user policies governing spare parts. Consideration should also be given to stocking complete units when the job site is in an area remote from a distributor or district sales office or when it is critical to maintain continuous operation of a system.
Order Information

The following information is required when ordering renewal parts: description of part or unit series letter part or catalog number quantity shipping address motor control center serial number and complete nameplate data

Refer to Chapter 11, Parts Illustration, for pictures and descriptions of common section and unit parts.
Recommended Spare Parts List

The following is an example of a typical Recommended Spare Parts List that can be supplied with your motor control center, upon request. Lists contain spare part information specific to the particular motor control center that was ordered. NOTE: The information in the following example is accurate at time of release.

Publication 2100-5.0 - October 1995

10-2

Renewal Parts

Figure 10.1 Sample of Renewal Parts List Page 1 through 4

Publication 2100-5.0 - October 1995

Renewal Parts

10-3

Figure 10.2

continued

Sample of Renewal Parts List Page 5 through 7

Publication 2100-5.0 - October 1995

10-4

Renewal Parts

Publication 2100-5.0 - October 1995

+D=FJAH

11

Parts Illustrations
Figure 11.1 Typical Section Construction

Publication 2100-5.0 - October 1995

11-2

Parts Illustrations

Figure 11.2 Typical Unit Construction (shown Bulletin 2113 Size 1 with Control Transformer)

Publication 2100-5.0 - October 1995

Parts Illustrations

11-3

Figure 11.3 Typical 0.5 Space Factor Unit Construction

Publication 2100-5.0 - October 1995

11-4

Parts Illustrations

Publication 2100-5.0 - October 1995

+D=FJAH

12

Purchased Components and Additional Instruction Sheets


When equipment such as transformers, metering, PLCs, drives, is supplied with the motor control center, specific manuals and data sheets are also supplied. These manuals and data sheets should be read and understood before installing and operating the motor control center. Refer to the unit locations of these devices for their manuals and/or data sheets.

Publication 2100-5.0 - October 1995

12-2

Purchased Components and Additional Instruction Sheets

Publication 2100-5.0 - October 1995

Index

Bus Torque Specifications, 2-7,

B,

C, Cable - Installing, 3-2, Cable Bracing, 3-3, Incoming Line Compartment, 3-2, Main Fusible Disconnect and Main Circuit Breaker, 3-2, Conduit - Installing, 3-1, Bottom Entry Conduit, 3-1, Contact Lubrication-Disconnect Switch, 8-3, Lubrication Instructions, 8-4,
Disconnect Switch Contact Lubrication, 8-3, Energizing Procedure, 7-1, Fault Condition - Maintenance After, 9-1, Installation, Location Planning, 2-1, Mounting Considerations, 2-1, Securing a Motor Control Center, 2-1, Mounting Dimensions, 15 & 20 Deep Corner Section, 2-3, 15 & 20 Deep Front Mounted, 2-2, 2-3, 15 & 20 Deep x 40 Wide Front-Mounted, 2-3, 25 Deep Back-To-Back, 2-2, 30 & 40 Deep Back-To-Back, 2-2, NEMA Type 3R Section, 2-3,

Instruction Sheets, Additional, 12-1, Install Units with Horizontal Handles, 4-1, Pub. 2100-5.0.1 - MCC Start-Up Procedures, 2-7, Publ. 2100-5.1 - Joining & Splicing Vertical Sections, 2-5, Joining & Splicing, Existing MCCs, 2-5, NEMA Type 3R MCCs, 2-5, New MCCs, 2-5, Locking Provisions, 5-3, Maintenance, 8-1, Checklist, 8-1, Nameplate Data, 1-1, Section Nameplate, 1-1, Unit Nameplate, 1-2, Operator Handle & Unit Interlock, 5-1, Defeater Lever for 0.5 Space Factor, 5-2, Defeater Lever for 1.0 Space Factor & Up, 5-2, Locking Handle (Small) - 0.5 Space Factor, 5-3, Operating Handle Defeater for 0.5 Space Factor, 5-1, Operating Handle Defeater for 1.0 Space Factor & Up, 5-1,

J,

D, E, F, I,

L,

M, N,

O,

Publication 2100-5.0 - October 1995

1`

Index

Parts Illustrations, 1.0 Space Factor Unit, 11-2, Section, 11-1, Plug-In Units, Installing into Structure, 4-1, Plug-In Units - Removing from a Section, 0.5 Space Factor, 4-4, 4-5, 1.0 Space Factor or Larger, 4-1, Receiving, Handling, and Storing MCCs, 1-6, Seismic Requirements, Bolt Down Requirements, 2-4, Weld Down Requirements, 2-4, Series Identification, 1-4, Series Lettering - Units & Sections, 1-5, Short Circuit Label for Sections, 1-3, Short Circuit Label for Units, 1-3, Support Pan Removal, 4-3, Type 1 Pull Boxes - Installing & Joining, 2-7, Type 12 Pull Boxes - Installing & Joining, 2-7, UL / CSA Marking, 1-2,

2,

4, 5,

6,

7,

Publication 2100-5.0 - October 1995

Publication 2100-5.0 - October 1995 Supersedes Publication 2100-5.0 - August 1987

1997 Rockwell International. All Rights Reserved. Printed in USA

You might also like