NS2 Configuration Guide

Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Backup Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Secondary Backup Battery. . . . . . . . . . . . . . . . . . . . . . . . 1 Reader & Aux Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Reader Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Supervised Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 2 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Enclosure Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 4 Communications & Wiring . . . . . . . . . . . . . . . . . . . . . . . 4 DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Connection Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Configuration Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 RS-232 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 RS-485 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 NSLAN1 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 LANSRL100 Connection. . . . . . . . . . . . . . . . . . . . . . . . 10 LANSRLU1 Connection . . . . . . . . . . . . . . . . . . . . . . . . 11 Lease Line Modem Connection . . . . . . . . . . . . . . . . . . . 12 RS-485 Short Haul Modem Connection . . . . . . . . . . . . 13 RS-232 Short Haul Modem Connection . . . . . . . . . . . . 14 M-9600 Dial-up Modem, RS-485 Connection . . . . . . . 15 M-56K Dial-up Modem, RS-485 Connection . . . . . . . . 16 Fiber Converter to RS-485 Connection . . . . . . . . . . . . . 17 485-PCI/NS2 Panel Connection Detail . . . . . . . . . . . . . 18 Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Specifications
Power
AC Non-Polarized: 16.5 VAC utilizing a UL-listed 50 VA Class 2 transformer (TB9-4 AC+/TB9-5 AC) or DC Polarized: 24 VDC, 1.25 Amp (TB9-4 DC+/TB9-5 DC) Power Wire Two-wire, 18 AWG, shielded cable.

Backup Battery
Casil 12 VDC (NCI Part #: BAT-3) 4Ah, sealed acid/lead backup battery (J6 DC+/J7 DC) Backup battery will provide 2.5 hours of standby backup power. Charging voltage: 13.7 +/ 0.1 VDC
NOTE: The NS2 panel has deep discharge protection built in for the protection of the battery and will only utilize a backup battery down to 10.2 VDC before the NS2 shuts down. Backup battery should be replaced 2 to 2.5 years: more often if panel has a high rate of backup use.

Description
The NS2 is a two reader panel providing access control for up to two doors through the use of Wiegand readers. The NS2 may be used as a standalone panel with independent card and transaction storage or, with a software upgrade, as a fully monitored online access control device. Communication to the front-end computer is achieved through an RS-232 serial cable (included with installation kit) or an optional RS-485 interface. Each RS-485 interface is capable of communicating with up to 31 panels. The NS2 is designed for tile mount using the ENC10 enclosure. The I/O terminals are organized by operational utility with connectors for power and RS-485 communications located on the lower right followed from right to left by the relays, auxiliary power, door control inputs, and readers. The Tamper and External Power Fail terminal are located at the left edge above the main line of connectors.

Secondary Backup Battery


The NS2 panel memory is backed up using a super capacitor for one week in the absence of power or a backup battery. The super capacitor will backup panel memory and real-time clock and does not require maintenance or replacement.

Reader & Aux Power


Reader and AUX power is supplied at 10.8-12.7 VDC with a maximum current of 600 mA. Five volt (5 VDC) readers require five-volt regulators (Northern part no. 5VRDREG) Maximum draw is less then 600 mA: (Reader 1+ Reader 2 + Aux Power) < 600 mA.
NOTE: Aux power must not be used to power locks.

7-101004-01

NS2 Configuration Guide

Honeywell Access Systems

Reader Wiring
Each reader port supports a single 12-volt reader with Wiegand output format.
Reader 1 Terminal TB3-1 TB3-2 TB3-3 TB3-4 TB3-5 TB3-6 Reader 2 Terminal TB4-1 TB4-2 TB4-3 TB4-4 TB4-5 TB4-6 Wire Color Brown Green White Black Red Variable Wire Color Brown Green White Black Red Variable Wiegrand Reader LED Control Data 0 Signal Data 1 Signal Common 12VDC Power Tamper Wiegrand Reader LED Control Data 0 Signal Data 1 Signal Common 12VDC Power Tamper

Supervised Input Wiring

The NS2 supervises inputs 1 through 8 and may be configured for supervised or non-supervised normally open or normally closed contacts. Use standard 1K ohm 5% resistors for supervision. All eight inputs are assigned default features but can be changed for other configurations as needed.

Inputs
The NS2 has 8 input points located on the following terminals:
Input Terminal TB5-1 TB5-3 TB5-2 TB5-4 TB5-6 TB5-5 TB3-6 TB3-5 TB4-6 TB4-4 TB1-3 TB1-1 TB1-2 Door 1 Rex Door 1 Status Door 1 & 2 Common Door 2 Rex Door 2 Status Input 3 & 4 Common Reader Tamper or Aux Input 5 Common (Input 5 Common) Reader Tamper or Aux Input 6 Common (Input 6 Common) Power Fail or Aux Input 7 Enclosure Tamper or Aux Input 8 Common (Input 7 & 8 Common) Description Input/Aux Number 1 2 1&2 3 4 3&4 5 5 6 6 7 8 7&8

NS2 version 1.01.01 - 1.03.09 supports only the defaulted Wiegand formats: F=PN 1 26 S 1 D 1 B1 B2 B3 B4 F=PN 2 32 S 0 D 0 B1 B2 B3 B4 F=PN 3 34 S 1 D 1 B1 B2 B3 B4
NOTE: NS2 version 1.01.01 - 1.02.04 at this time does not support the ABA card format, the OL, OJ, and OH Options, Anti- Passback and Lock Down Time. NOTE: NS2 version 1.03.09 does not support the ABA card format or the Lock Down Time option, but does support the NS2MEM module, the OL, OJ, and OH Options, as well as Anti-Passback (In card only mode).

NOTE: Tamper and External Power Fail are supervised and capable of being used as additional inputs if the default functionality is not needed. NOTE: The wire used for the inputs should be shielded and cannot exceed 30 ohms over the entire length of the cable. Remember that the distance from the panel to the door must be doubled to determine the total resistance.

7-101004-01

Honeywell Access Systems

NS2 Configuration Guide

Outputs
Four form-C relays SPDT (Single Poll Double Throw) goldcontact relays are provided for controlling door locks or other output devices (I.E. sounder, burg panel, phone dialer....etc.).
Output Terminal TB7-1 TB7-2 TB7-3 TB7-4 TB7-5 TB7-6 TB8-1 TB8-2 TB8-3 TB8-4 TB8-5 TB8-6 Description Normally Open (NO) Common (COM) Normally Closed (NC) Normally Open (NO) Common (COM) Normally Closed (NC) Normally Open (NO) Common (COM) Normally Closed (NC) Normally Open (NO) Common (COM) Normally Closed (NC) Relay/Output Number Relay 1 (Door 1) Relay 1 (Door 1) Relay 1 (Door 1) Relay 2 (Door 2) Relay 2 (Door 2) Relay 2 (Door 2) Relay 3 Relay 3 Relay 3 Relay 4 Relay 4 Relay 4

Relay 1 is defaulted to control the Door 1 lock & Relay 2 is defaulted for the Door 2 lock. Relay 3 & 4 are used as auxiliary relays for signaling other devices. All 4 relays are rated at 12 Amps / 28VDC for resistive loads and 6 Amps / 28VDC for inductive loads (data switching).
NOTE: Once the relay pole has been used for an inductive load (including door strikes and magnetic locks) it should not be used for low current dry circuit applications. NOTE: Switching of inductive loads can cause EMI (Electromagnetic Interference) which may interfere with the normal operation of other equipment.

The energized or ON time for each relay can be configured by using either time zone control, or programmable pulse time via the host software.

To minimize premature contact failure and increase system reliability, contact circuit protection such as the S-4 suppressor is required. Locate this device as close as possible to the Door Strike / Maglock.

7-101004-01

NS2 Configuration Guide

Honeywell Access Systems

Enclosure Specifications
Mounting One NS2 panel in a standard 19-inch, high density enclosure. Up to eight NS2 panels in a single 19-inch rack mountable enclosure Dimensions Board Enclosure Environmental Temperature Humidity 35110 F operational 085% RHNC 9-inch Length x 5.5-inch Wide x 1-inch High 12.5-inch Wide x 14.5-inch High x 3.5-inch Deep

Communications & Wiring


Communication Type Direct to COM Port CBL50, RS-232 Cable N-485-PCI-2 Network NSLAN1 LANSRL100/N-485-PCI-2L LANSRLU1/N-485-PCI-2L Modems M-9600-LA (LO)/N-485-PCI SHM-B-ASYNC/N-485-PCI SHM-B-ASYNC/CBL50 M-9600-2/N-485-HUB-2 M-56/N-485-HUB-2 Fiber FC485 Cable Specifications Readers NC1861-BL Alarm Input NC1821-GR Relay Outputs NC1821-GR Twisted Pair, Shielded 18 2K 609.8 Twisted Pair, Shielded 18 2K 609.8 6 Conductor, Shielded 18 500 152.5 Fiber converter to RS-485 Description 31 AWG 10K/4K 3049/ 1219.6 Lease-line Modem to RS-485 Short-haul Modem to RS-485 Short-haul Modem to RS-232 Dial-up Modem to RS-485 Dial-up Modem to RS-485 31 31 1 31 31 NA/4K 5279.9/4K 5279.9/50 NA/4K NA/4K NA/1219.6 1609.84/ 1219.6 1609.84/ 15.25 NA/1219.6 NA/1219.6 Cobox Unit (RS-232) Ethernet to RS-485 Ethernet to RS-485 1 NS2 panel per NSLAN1 64 max IP connections per system 31 NS2 panels per 485 interface 64 max IP connections per system 31 NS2 panels per 485 interface 64 max IP connections per system 328 328/4K 328/4K 100 100/1219.6 100/1219.6 9-pin to RJ-45 RS-485 9-pin to CPU 1 31 50 4K 15.25 1219.5 Description Maximum Panels Maximum Distance Feet / Meters

Maximum Distance Feet / Meters

NOTE:

The C-100-A1/A2 (RS-232 communication loop), M-200 (1,200 Baud rate dial up modem), M-300-LO/LA (1,200 Baud Leased line modem), F210D (Fiber to RS-232) [Discontinued] and F290D (Fiber to RS-485) [Discontinued] are not supported with the NS2 panel(s).

7-101004-01

Honeywell Access Systems

NS2 Configuration Guide

DIP Switch Settings


S1 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON S2 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON S3 OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON OFF ON ON S4 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON S5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF ON OFF ON OFF ON OFF ON S6 S7 S8 S9 S10 SELECTION Address 0 Address 1(default) Address 2 Address 3 Address 4 Address 5 Address 6 Address 7 Address 8 Address 9 Address 10 Address 11 Address 12 Address 13 Address 14 Address 15 Address 16 Address 17 Address 18 Address 19 Address 20 Address 21 Address 22 Address 23 Address 24 Address 25 Address 26 Address 27 Address 28 Address 29 Address 30 Address 31 RS-232 (default) RS-485 PCI Interface 19200 Baud (RS-232 only) 57600 Baud (RS-232 only, default) RS-485 Bias Off (default) RS-485 Bias On OFF RS-485 EOL Off ON RS-485 EOL On

7-101004-01

NS2 Configuration Guide

Honeywell Access Systems

Connection Schematic
TB1
PWR FAIL/AUX 7 COMMON ENCTMPR/AUX8

TB2

RESERVED RESERVED RESERVED RESERVED LED DATA 0 DATA 1

READER1

BROWN GREEN WHITE

C1 C2

PF RUN

TB3

BLACK COMMON RED +12VDC VARIES RDR TMPR/AUX 5

SYSTEM STATUS LEDS

LED BROWN DATA 0 GREEN DATA 1 WHITE COMMON TB4 BLACK RED +12VDC VARIES RDR TMPR/AUX 6 DR1 REX INPUT 1

READER2

ON

DIPSWITCHES
10

OPTIONAL ETHERNET INTERFACE

COMMON DR1 STATUS INPUT 2 INPUT 3 TB5 DR2 REX COMMON DR2 STATUS INPUT 4

RELAY LEDS
3 4 1 2

TB6

AUX +12VDC AUX COM RELAY1 NO RELAY1 COM RELAY1 NC RELAY1 X PORT RELAY2

TB7

RELAY2 NO RELAY2 COM RELAY2 NC RELAY3 NO RELAY3 COM

RELAY3

TB8

RELAY3 NC RELAY4 NO RELAY4 COM RELAY4 NC RS485 + RS485 RS485 COM

RELAY4

TB9

PWR ON LED AC/DC + PWR ON LED AC/DC -

RS-232 PORT J6 (DC+) J7 (DC-) BATTERY

POWER LED

7-101004-01

Honeywell Access Systems

NS2 Configuration Guide

Configuration Diagrams
RS-232 Connection
One NS2 panel for each COM port.

COM 1 COM 2

CBL50 (RS-232) 50 ft. Max.

NStar Server CBL50 (RS-232) 50 ft. Max.


DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600 Baud Rate) S8-S10: OFF

NS2 Panel

NS2 Panel

EG

It is recommended to earth ground (EG) each NS2 enclosure individually.

EG

RS-232 (DB9) 8 5 2 3 7

CBL50 (RS-232) RJ-45


Request To Send (RTS) Signal Ground (GND) Receive Data (RXD) Transmit Data (TXD) Clear To Send (CTS)

2 3 4 5 7

9-Pin COM 1 or COM 2 to RJ-45 on NS2 Panel

7-101004-01

NS2 Configuration Guide

Honeywell Access Systems

RS-485 Connection
Thirty-one NS2 panels for each drop line.

COM Port

RS-232 (50 Ft. Max.)

RS-485 (4,000 Ft.)

N-485-PCI-2 NStar Server


Refer to 485-PCI / NS2 Panel Connection Detail diagram.

RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)

DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL)

NS2 Panel

NS2 Panel See RS-485 Cable note.

EG EG

EG Only Earth Ground one side of cable.

EG

It is recommended to earth ground (EG) each NS2 enclosure individually.

7-101004-01

Honeywell Access Systems

NS2 Configuration Guide

NSLAN1 Connection
One NSLAN1 for each NS2 panel, Maximum sixty-four IP connections.

HUB NIC 100BaseT (CAT 5) 328 Ft. Max.

NStar Server

NS2 Panel
NSLAN1 installed

100BaseT (CAT 5) 328 Ft. Max. EG

DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600 Baud Rate) S8-S10: OFF

NSLAN1 must be programmed with a static IP address See NSLAN1 product documentation for programing instructions.

NS2 Panel
NSLAN1 installed

100BaseT (CAT 5) 328 Ft. Max.

EG

It is recommended to earth ground (EG) each NS2 enclosure individually.

7-101004-01

NS2 Configuration Guide

Honeywell Access Systems

LANSRL100 Connection
Thirty-one NS2 panels for each drop line, Maximum sixty-four IP connections.

NIC

100BaseT (CAT 5) 328 Ft. Max.

NStar Server

HUB 100BaseT (CAT 5) 328 Ft. Max.

RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)

LANSRL100 Refer to LANSRL100 documentation for programmig.

DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate)

RJ-45 RS-232 (50 Ft.)

N-485-PCI-2L

Refer to 485-PCI / NS2 Panel Connection Detail diagram.

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL)

NS2 Panel EG EG EG

NS2 Panel

See RS-485 Cable note.

Only Earth Ground (EG) one side of cable.

EG

It is recommended to earth ground (EG) each NS2 enclosure individually.

10

7-101004-01

Honeywell Access Systems

NS2 Configuration Guide

LANSRLU1 Connection
Thirty-one panels for each drop line, Maximum sixty-four IP connections.

NIC

100BaseT (CAT 5) 328 Ft. Max.

NStar Server

HUB 100BaseT (CAT 5) 328 Ft. Max.


RS-485 Cable

RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)

LANSRLU1 Refer to LANSRLU1 documentation for programmig.

DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate)

RJ-45 RS-232 (50 Ft.)

N-485-PCI-2L

Refer to 485-PCI / NS2 Panel Connection Detail diagram.

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL)

NS2 Panel EG EG

NS2 Panel

See RS-485 Cable note.

EG

Only Earth Ground (EG) one side of cable.

EG

It is recommended to earth ground (EG) each NS2 enclosure individually.

7-101004-01

11

NS2 Configuration Guide

Honeywell Access Systems

Lease Line Modem Connection


Thirty-one NS2 panels for each drop line.
Straight Thru Cable (9-25 Pin)
Female 9 Pin (RX) 2 (TX) 3 (Comm) 5 Male 25 Pin 3 (RX) 2 (TX) 7 (Comm)

M-9600-LO COM Port RS-232 (50 Ft.)

NStar Server Null Modem Cable Cable (9-25 Pin)


Male 9 Pin (RX) 2 (TX) 3 (Comm) 5 N-485-PCI-2 Female 25 Pin 2 (TX) 3 (RX) 7 (Comm)

Lease Line Phone Line M-9600-LA

Refer to 485-PCI / NS2 Panel Connection Detail diagram.

RS-232 (50 Ft.) RS-485 (4,000 Ft.)

DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL)

NS2 Panel

NS2 Panel

See RS-485 Cable note.

EG EG

EG
Only Earth Ground (EG) one side of cable.

EG

It is recommended to earth ground (EG) each NS2 enclosure individually. DB 9 / DB 25 Connectors Female Male

RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)

12

7-101004-01

Honeywell Access Systems

NS2 Configuration Guide

RS-485 Short Haul Modem Connection


Thirty-one NS2 panels for each drop line.
RS232 Cable PC (DB-9) DTE MODEM DCE
(Null) 2 (RX) 3 (TX) 7 (GND) (Straight) 2 (TX) or 3 (RX) 7 (GND)

RS-232, 50 Ft. Max.

2 TX 3 RX 5 Comm

NStar Server

SHM-B-ASYNC Short Haul Modem

RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL)

5279.9 Feet

NS2 Panel EG EG

NS2 Panel

See RS-485 Cable note.

EG

Only Earth Ground (EG) one side of cable. EG

It is recommended to earth ground (EG) each NS2 Enclosure individually.


SHM-B-ASYNC Short Haul Modem

DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate)

RS-232, 50 Ft. Max.


Male 9 Pin Male 25 Pin

RS232 Cable
N-485-PCI-2

MODEM
(Straight) 2 (TX) or 3 (RX) 7 (GND)

PC (DB-9) Refer to 485-PCI/NS2 Panel Connection Detail diagram.


2 TX 3 RX 5 Comm

DTE

DCE
(Null) 2 (RX) 3 (TX) 7 (GND)

7-101004-01

13

NS2 Configuration Guide

Honeywell Access Systems

RS-232 Short Haul Modem Connection


One NS2 panel for each loop.
RS232 Cable PC (DB-9) DTE MODEM DCE
(Null) 2 (RX) 3 (TX) 7 (GND) (Straight) 2 (TX) or 3 (RX) 7 (GND)

RS-232, 50 Ft. Max.


SHM-B-ASYNC Short Haul Modem

2 TX 3 RX 5 Comm

NStar Server

DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600 Baud Rate) S8-S10: OFF

5279.9 Feet

NS2 Panel

CBL50

EG It is recommended to earth ground (EG) each NS2 enclosure individually.


SHM-B-ASYNC Short Haul Modem

RS232 Cable

MODEM DCE
(Null) 2 (RX) 3 (TX) 7 (GND)

(RS-232 50 Ft. Max.)


Male 9 Pin Male 25 Pin

PC (DB-9)
2 TX 3 RX 5 Comm

(Straight) 2 (TX) 3 (RX) or 7 (GND)

DTE

14

7-101004-01

Honeywell Access Systems

NS2 Configuration Guide

M-9600 Dial-up Modem, RS-485 Connection


Thirty-one NS2 panels for each drop line.

M-9600-2 Straight Thru Cable (9-25 Pin)

NStar Server

Female 9 Pin (RX) 2 (TX) 3 (Comm) 5

Male 25 Pin 3 (RX) 2 (TX) 7 (Comm)

Analog Phone Line Dedicated analog phone line recommended M-9600-2

Refer to 485-PCI / NS2 Panel Connection Detail diagram.

N-485-HUB-2

RS-232 (50 Ft.)

RS-485 (4,000 Ft.)

DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL)

NS2 Panel EG EG EG

NS2 Panel

See RS-485 Cable note.

Only Earth Ground (EG) one side of cable.

EG

It is recommended to earth ground (EG) each NS2 enclosure individually. DB 9 / DB 25 Connectors Female Male
RS-485 Cable NS2 Panel NS2 Panel RS-485 TB9-1 (RS485+) TB9-1 (RS485+) Red/White TB9-2 (RS485-) Black/Green TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)

7-101004-01

15

NS2 Configuration Guide

Honeywell Access Systems

M-56K Dial-up Modem, RS-485 Connection


Thirty-one NS2 panels for each drop line.

M-56K FAX/MODEM

COM Port

Straight Thru Cable


Local DIP Switch Settings (1, 3, 5, 8 ON) (2, 4, 6, 7 OFF)

NStar Server

Female 9 Pin (RX) 2 (TX) 3 (Comm) 5

Male 25 Pin 3 (RX) 2 (TX) 7 (Comm)

Analog Phone Line Dedicated analog phone line recommended

Refer to 485-PCI/ NS2 Panel Connection Detail diagram.

N-485-HUB-2

RS-232 (50 Ft.)

M-56K FAX/MODEM Remote DIP Switch Settings (1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)

RS-485 (4,000 Ft.)

DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL)

NS2 Panel

NS2 Panel

See RS-485 Cable note.

EG

EG
Only Earth Ground (EG) one side of cable.

EG

EG

It is recommended to earth ground (EG) each NS2 Enclosure individually. DB 9 / DB 25 Connectors Female Male
RS-485 Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)

16

7-101004-01

Honeywell Access Systems

NS2 Configuration Guide

Fiber Converter to RS-485 Connection


Thirty-one NS2 panels for each drop line.

Refer to 485-PCI/NS2 Panel Connection Detail diagram.

RS-485 (4000 Ft. Max.)

COM Port

RS-232 (50 Ft. Max.)

N-485-PCI-2

NStar Server NS2 Panel


S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak) S7: ON S8: OFF (19,200 Baud Rate)

FC485 RS-485 Fiber Converter


RXD PWR TXD RS-485 Comm. RS-485 Positive(+) RS-485 Negitive (-)

EG

DIP Switch Settings

NS2 Panel
TB9-3 (RS485 Comm) TB9-1 (RS485 +) TB9-2 (RS485 -) RS-485 Drain Wire Floating

FC485 RS-485 Fiber Converter


RXD PWR TXD RS-485 Comm. RS-485 Positive(+) RS-485 Negitive (-)

EG

N-485-PCI-2 DIP Switch Settings


S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL) (485 Common) (RED/WHITE) (BLACK/GREEN) RS-485 Drain Wire to earth ground Fiber RXD Fiber TXD

Fiber RXD Fiber TXD

Fiber Wire 10,000 Ft.


FC485 RS-485 Fiber Converter
RXD PWR TXD RS-485 Comm. RS-485 Positive(+) RS-485 Negitive (-) RS-485 Drain not connected here (connected at panel side)

Fiber Wire 10,000 Ft.


FC485 RS-485 Fiber Converter
RS-485 Drain not connected here (floating) RXD PWR TXD RS-485 Comm. RS-485 Positive(+) RS-485 Negitive (-)

NS2 Panel
TB9-3 (RS485 Comm) TB9-1 (RS485 +) TB9-2 (RS485 -)

NS2 Panel
TB9-3 (RS485 Comm) TB9-1 (RS485 +) TB9-2 (RS485 -)

Fiber RXD Fiber TXD

Fiber RXD Fiber TXD

NS2 Panel EG
It is recommended to earth ground (EG) each NS2 enclosure individually.

EG

NS2 Panel

See RS-485 Cable note.

EG EG
DIP Switch Settings
S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL)

RS-485 Cable FC485 RS-485 Positive (+) RS-485 Negative (-) RS-485 Common RS-485 Drain not connected NS2 Panel TB9-1 (RS485+) TB9-2 (RS485-) TB9-3 (RS485 COM) RS-485 Drain wire grounded NS2 Panel TB9-1 (RS485+) TB9-2 (RS485-) TB9-3 (RS485 COM) RS-485 Drain wire grounded

4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)

7-101004-01

17

NS2 Configuration Guide

Honeywell Access Systems

485-PCI/NS2 Panel Connection Detail

DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate)

485 Interface Connection Types


RS-485 N-485-PCI-2 N-485-HUB-2 N-485-PCI-2L NS2 Panel COM Port M-56K Modem LANSRL100 or LANSRLU1

To Serial Connection

GROUND SHIELD

See 485 Interface connection note.

DO NOT CONNECT or GROUND SHIELD

NS2 - TB9

NS2 - TB9

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: ON (485 EOL)

DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL)

B GRE EN LACK

RED

DO NOT CONNECT SHIELD

WHITE

X
Shield
485 Common

Ground only one side of cable shield

485 + 485 -

ON MM CO

4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN).

18

7-101004-01

Honeywell Access Systems

NS2 Configuration Guide

Frequently Asked Questions


Question: What pre-packaged kits are available? Honeywell Access has made the NS2 available in pre-packaged kits to make ordering easier.
Part No. NSSKR NSSK NSEKR NSEK Kit Description Starter kit with readers. Starter kit. Expansion kit with readers. Expansion kit. Contents Software, panel, 2 readers, accessories. Software, panel, accessories. Panel, 2 readers, accessories. Panel, accessories.

Question: Question: Question: Question: Question:

How many access points can I control with the NStar access control system? NStar software will support up to 128 access points. System expansion is via RS-485 or TCP/IP. How does the NStar software communicate to the NS2 panel? NS2 panels communicate using either RS-485 or RS-232 protocol. Can I upgrade my NStar software to WIN-PAK 2.0? Not at this time. Future releases may allow upgrade capabilities. Does Nstar software and hardware support the Northern AEP-3 or AEP-5 relay output boards? Neither the NS2 panel nor the NStar software supports the AEP-3 or AEP-5 board. What are the minimum PC requirements to run the NStar software?

Pentium II 400 MHz CPU 256 Megabytes of RAM (512 megabytes recommended) 20 Gigabyte hard drive 2 serial communication ports Backup device (Tape Drive, DVD/CD burner, Network backup utility) Microsoft Windows XP Pro; Windows 2000 Pro / Server (SP4)

Question:

Which video Capture Card can be used with the NStar software? Honeywell Access Systems recommends the PB-VC-15 or higher capture card. Call Honey Access Systems for more details. What localized language support does the NStar software offer? The initial release of NStar will be available only in English. Future plans are to release Spanish, Portuguese and French localized versions. What database engine does the Nstar software use? Microsoft Data Engine (MSDE) Does the NStar software or hardware support USB ports for communications? Please contact Honeywell Access Systems for further details. What is the maximum distance I can run the RS-232 connection? The industry standard for RS-232 is limited to 50 feet. Can the NS2 panel be mounted in a 19" rack to save on installation space? Yes, the NS2 panel is designed to fit into a 19" rack mount enclosure.

Question:

Question: Question: Question: Question:

7-101004-01

19

Honeywell Access Systems

NS2 Configuration Guide

Question:

Can the NS2 panel run in a LAN/WAN environment? Yes, each NS2 panel can be fitted with NSLAN1 interface board to allow a single direct TCP/IP connection (64 max), or up to 31 panels can be connected using the 485-PCI-2L and a LANSRL100 or NLANSRLU1 (64 max). Does the NS2 panel support Anti-Passback? Yes. What is the Xport expansion port used for? The XPort expansion port allows for future expansion to other devices as well as the NS2MEM. What is the NS2MEM used for? The NS2MEM module is a "Plug and Play" memory board that attaches to the "Xport" and allows memory expansion of up to 10,000 cards and 100,000 buffers. The NS2MEM module is ONLY SUPPORTED WITH NS2 FIRMWARE VERSION 1.03.09 OR HIGHER.

Question: Question: Question:

Question:

How do I upgrade the NS2 Firmware? The NS2 panel uses FLASH memory. This means never having to replace a firmware chip to take advantage of system upgrades or new features. See Honeywell Access Systems website (www.honeywellaccess.com) for further details and downloads. How do I default the NS2 panel? 1. Change all of the NS2 Panel DIP switches to OFF (address Zero)
2. 3. 4. 5. 6.

Question:

Power down NS2 panel by removing backup battery then removing AC power for 10 seconds. Restore power to the NS2 Panel by reconnecting AC power then backup battery to reset the panel. Power down again by removing backup battery then removing AC power. Reset the DIP switches with correct panel address, and power back up the panel. Re-initialize panel through the Nstar software to download current data.

Default LED conditions for the NS2 panel after default are: run LED blinking green and power LED solid green.
NOTE: NOTE: Using firmware version 1.01.1 & 1.02.01: By default the run LED is blinking and power LED is solid. When there is information in the NS2 panel(s), after a full initialization of the NS2 panel, C1 & C2 will flash red. Only One NS2 panel at a time should be defaulted.

Question:

How do I control the reader LEDs on the NS2 Panel? In the NStar software, output 5 controls the LED on reader 1, while output 6 controls the LED on reader 2. By default Outputs 5 and 6 are set for a two-second pulse time. It is recommended that any time zone assigned to the door lock output also be assigned to the corresponding reader LED output so the LED will follow the correct time schedule. The configurations described in this document have not been reviewed by Underwriters Laboratories.

Honeywell Access Systems


135 West Forest Hill Avenue, Oak Creek, WI 53154 PH: 414-769-5980 FX: 414-766-1798 www.honeywellaccess.com Copyright 2004. Honeywell International. All rights reserved. 20

Specifications subject to change without notice. 7-101004-01