TEMPERATURE CONTROLLER User's Manual

RESTRICTIONS ON USE
When using this product in applications that require particular safety or when using this product in important facilities, please pay attention to the safety of the overall system and equipment. Install failsafe mechanisms, perform redundancy checks and periodic inspections and adopt other appropriate safety measures when it is necessary. AT-502

AT02 SERIES PID

Names and Functions of Parts

Upper Display
o

LEDs
AT: Lit when the auto tuning is ON. OUT: Lit when the control output is ON. ALM: Lit when the alarm output is ON. LOCK: Lit when the key is locked.

PV

Displays PV values (current temperature, etc.) or setup items.

SV
AT OUT ALM LOCK

Lower Display
Displays SV values (set temperature, etc.) and other parameter values.

SET
ATTENTION !
1.Please read the SAFETY PRECAUTION section on reverse side before use of this product. 2.Please read this user's manual before use for proper operation. 3.Please safe guard this user's manual.

Key :
Used to change numeric values.

Key :
Switches the display. Hold down for 3 seconds to switch modes.

Key :
Used to shift setup items or parameter digits.

Function Setting
Warning! Please make sure the power is off, before making any changes on the DIP switch.
ON 1 2 3 4 5 6

User Level Setting


1 Power ON
PV
o

PID Control Setting


Ensure the DIP switch is set to PID control mode before proceed further.
1 Start with

DIP Switch 1
O

The initial screen is displayed for about 3 seconds.

SV
AT OUT ALM LOCK

operation mode.

K Type J Type

0~1200 C 0~500 C
O

ON OFF OFF ON ON OFF ON OFF ON 2 The IC version

PV

Current PV value Current SV value

SV PV
o

Input type

R Type PT-100

0~1700 C
O O

is displayed for about 6 seconds.

tic IC version 2 Press

AT

OUT

ALM

LOCK

Reserved

-50~400 C OFF ON ON
OFF ON OFF ON

SV
AT OUT ALM LOCK

ON/OFF CONTROL

Control Mode

key for 3 seconds to the parameter mode.

PV

LVL uSr

PID CONTROL RELAY

3 The operation

SV PV
o

Output

mode is displayed.

Current PV value Current SV value 3 Press

AT

OUT

ALM

LOCK

DC 24V(for SSR driven)

SV
AT OUT ALM LOCK

List of Alarm Mode :

1 2 3 4 5 6 7 8 9 10 11 12

Deviation High Alarm Deviation Low Alarm Process High Alarm Process Low Alarm Deviation High/Low Alarm Band Alarm Deviation High Alarm (Standby) Deviation Low Alarm (Standby) Process High Alarm (Standby) Process Low Alarm (Standby) Deviation High/Low Alarm (Standby) Band Alarm (Standby)

4 Press

key for 3 seconds to the Alarm range setting mode.

key once and key once to the PID level.

PV

LVL Pid

SV
AT OUT ALM LOCK

PV

AS1: Alarm range setting

SV
AT OUT ALM LOCK

Temperature range varies with Input type


At: Auto Tunning YES / no

4 Press

key for 3 seconds to the P mode.

PV

P1: Proportional band (P)

5 Press

key once to the Auto Tunning switch mode

SV PV
o

0.1~300.0 C
OUT ALM LOCK

AT

SV
AT OUT ALM LOCK

5 Press

key once to the I mode.

PV

i1: Integral time (I) 0~7200sec (Set 0 for P Control)

6 Press

key once to the PV Offset mode.

SV PV
o

PoF: PV Offset

AT

OUT

ALM

LOCK

SV
AT OUT ALM LOCK

-200.0~200.0 C

6 Press

key once to the D mode.

PV

Key Lock Setting


PV
o

7 Press

key once to the SV Offset mode.

SV PV
o

SoF: SV Offset

d1: Derivative time (D) 0~1800sec (Set 0 for P Control)

AT

OUT

ALM

LOCK

SV
AT OUT ALM LOCK

Under uSr level, press key for 3 seconds to enter Key Lock mode. Set Lock mumber according to the level of protection.
8 Press

SV
AT OUT ALM LOCK

-200.0~200.0 C

7 Press

key once to the operation mode.

key once to the Relay output cycle mode.

PV

Ct1: Output cycle 1 0~65sec

SV
AT OUT ALM LOCK

PV

Current PV value Current SV value 8 Press

List of Key Lock Mode : usr Pid SEt ArG Others 0022 0 111 11 2 2
Symbol : Can display and can be set : Can't display nor can't be set
PV
o

SV
AT OUT ALM LOCK

SV Lock Setting
C

key once to the SSR output cycle mode.

PV

Ct2: Output cycle 2 0~65sec

SV
AT OUT ALM LOCK

SV
AT OUT ALM LOCK

Under operation mode, press key for 3 seconds to lock the SV value. And press key for 3 seconds again to unlock the SV value.

9 Press

key for 3 seconds to the operation mode.

ON/OFF Control Setting


Ensure the DIP switch is set to ON/OFF control mode before proceed further.
1 Start with 1 Start with

Set Level Setting


operation mode.
PV
o

Argument Level Setting


Current PV value Current SV value

This is used to display or hide arguments under user level. Arguments can be arranged in any order, but may not repeated.
1 Start with

SV PV
o

operation mode.

Current PV value Current SV value 2 Press

AT

OUT

ALM

LOCK

operation mode.

PV

Current PV value Current SV value

SV
AT OUT ALM LOCK

key for 3 seconds to the parameter mode.

SV PV
o

LVL uSr 2 Press

AT

OUT

ALM

LOCK

2 Press

key for 3 seconds to the parameter mode.

SV PV
o

LVL uSr 3 Press

AT

OUT

ALM

LOCK

key for 3 seconds to the parameter mode.

PV

LVL uSr

SV
AT OUT ALM LOCK

3 Press

key once and key once to the PID level.

key once and key twice to the SET level.

SV PV
o

LVL SEt 3 Press

AT

OUT

ALM

LOCK

SV
AT OUT ALM LOCK

PV

LVL Pid 4 Press

SV
AT OUT ALM LOCK

key for 3 seconds to the Alarm mode.

key once and key three times to the ARG level.

PV

LVL ArG

SV
AT OUT ALM LOCK

PV

AF1: Alarm 1~12 See List of Alarm Mode. AH1: Alarm Hysteresis 4 Press

4 Press

key for 3 seconds to the Hysteresis mode.

SV PV
o

SV
AT OUT ALM LOCK

HSt: Hysteresis ON/OFF 0.0~200.0 C


O

AT

OUT

ALM

LOCK

key for 3 seconds to the 1-2 mode.

PV

1-2 select 1: non, AS1, At, PoF, SoF

5 Press

5 Press

key for 3 seconds to the operation mode.

key once to the Alarm Hysteresis mode.

SV PV
o

AT

OUT

ALM

LOCK

SV
AT OUT ALM LOCK

-200.0~200.0 C

5 Press

key once to the 1-3 mode.

PV

1-3 select 1: non, AS1, At, PoF, SoF

6 Press

SV Value Setting
1 Start with

key once to the Heater / Cooling switch mode.

SV PV
o

SV
AT OUT ALM LOCK

Act: Heater/Cooling switch Ht / CL

AT

OUT

ALM

LOCK

6 Press

operation mode.

PV

Current PV value Current SV value 7 Press

key once to the 1-4 mode.

PV

1-4 select 1: non, AS1, At, PoF, SoF

SV
AT OUT ALM LOCK

2 Press

key once to the SV value change mode.

PV

key once to the Decimal point position switch mode.

SV PV
o

SV
AT OUT ALM LOCK

dP: Decimal point position switch 0 / 0.0

AT

OUT

ALM

LOCK

7 Press

Current PV value Current SV value 8 Press

key once to the 1-5 mode.

PV

1-5 select 1: non, AS1, At, PoF, SoF

SV
AT OUT ALM LOCK

key once to the Low Set Point mode.

SV PV
o

LSP: Low Set Point

AT

OUT

ALM

LOCK

3 Press

SV PV
o

key for change value and press key for change to the next digit and so on. 4 Press key once to the operation mode.

Current PV value Current SV value 9 Press

AT

OUT

ALM

LOCK

Temperature range varies with Input type


HSP: High Set Point

8 Press

key for 3 seconds to the operation mode.

SV
AT OUT ALM LOCK

key once to the High Set Point mode.

PV

SV
AT OUT ALM LOCK

Temperature range varies with Input type

10 Press

key for 3 seconds to the operation mode.

TERMINAL LAYOUT
AT-502
100~240 VAC 50/60 Hz 12 11 1 2
NO

DIMENSIONS(mm)
A B
Device

AT-402 / 602 / 902


1 2
NO

a b Panel Cutout

AT02 series AT-402

A 48 48 96 72 96

B 96 48 48 72 96

a
45.5 +0.5 -0

b
91 +0.5 -0

11 12 13 14 15 16 17 18 19 20 SSR

100~240 VAC 50/60 Hz


COM

6 7 8 9 10 14 13

AT-502 AT-602 AT-702 AT-902

45.5 +0.5 45.5 +0.5 -0 -0 91 +0.5 -0 67.5 91


+0.5 -0

ALM

COM

3 4 5 6 7 8 9 10

45.5 +0.5 -0 67.5 +0.5 -0 91 +0.5 -0

3 4 5

A B B

OUT

NC

OUT 100~240 VAC 50/60 Hz


COM

NC

+0.5 -0

SSR

A B

ALM

SAFETY PRECAUTION
This manual uses the following symbols to ensure safe operation of this controller.

AT-702
1 2
NO

WARNING Warnings are indicated when mishandling this controller might result in death or serious injury to user. CAUTION
Cautions are indicated when mishandling this controller might result in minor injury to the user, or only physical damage to the controller.

8 9 10 11 12 13 14

A B B

WARNING
Note this incorrect wiring of this controller can damage it and lead to other hazards. Make sure the controller has been correctly wired before turning the power ON. Before wiring, or removing / mounting the controller, be sure to turn the power OFF. Failure to do so might cause electric shock. Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock. Do not disassemble the controller. Doing so might cause electric shock or faulty operation.

3 4 5 6 7

OUT ALM

NC

CAUTION
Use the controller within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation. Do not block ventilation holes. Doing so might cause fire or faulty operation. Do not allow lead clippings, chips or water to enter the controller case. Doing so might cause fire or faulty operation.

SSR

ANLY ELECTRONICS CO., LTD.


http://www.anly.com.tw

M-AT02-F-C
Printed in Taiwan