You are on page 1of 11

ASHIDA Numerical 3OC + 1EF Protection Relay

Type: ADR141C
( AD I T Y AS e r i e s ) (Preliminary)

Protection Features:
4 Element (3 Phase + EF) Non Directional Over current IDMT/DMT. Selection of Curve: Five selectable curve (Normal Inverse1 (C1), Normal Inverse2, (C2) Very inverse (C3), Extremely inverse (C4), Long time inverse (C5)) and Define Time (C6) Instantaneous Over-Current Protection with adjustable timer. Breaker Failure detection In-built CB Trip Circuit Supervision function during pre closing and post closing of CB. On site CT Secondary selection 1A or 5A. Internal calculation of zero seq. current (3Io) for Earth fault Wide range Power supply input 18V to 250V AC/DC Cold Load Pickup

Relay Design Features: 16 x2 LCD Backlit display for Parameter and setting display Online display of CB status and other digital and logical status. Continuous monitoring of modules internal hardware and alarm generation in case of failure of any critical components. 4 Digital Output contacts for local alarm as Trip 2 dedicated status input for Trip Circuit Monitoring 5 nos of Fault data stored with keypad interface and time stamping. Description: ADR141C is second generation Numerical 3OC + 1EF Over Current Relay. It consist all the

necessary protection and monitoring functions required for Normal feeder It consist of

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.:ADR141C Issue: 05 07.03.2011 Page 1 / 9

ASHIDA Numerical 3OC + 1EF Protection Relay

Type: ADR141C
( AD I T Y AS e r i e s ) (Preliminary)

1. High Speed Digital DSP Controller 2. Analog Measuring Module 3. Power supply Module 4. Digital Input output module. The High speed Digital Signal Controller continuously monitors phase, E/F current along with different optical isolated status

station battery. The power supply module is design using very advance PWM controller which allow very wide input supply variation i.e. 18V to 250VAC/DC covering 24Vdc, 30Vdc, 110Vdc and 220Vdc station battery

requirement. The relay is having total 4 nos of high intensity dual LED for easy identification of type of fault for easy user interface. All LEDs and control output R1 to R4 are fully programmable via keypad interface Main Functions The ADR141C are having following protection functions. 1. Non Directional phase Over current

connections. The high-speed micro-controller samples these current signals through a A/D converter. The Digital Signal performs

powerful Numerical Algorithms to find out RMS of fundamental & harmonic contents of the current then this value is used for protection and metering function. All measurement is tuned to fundamental frequency i.e 50Hz, thus relay remain stable during distorted waveform generated electronics loco-motive. All these measure values are then used for different protection function such as IDMT/DMT Over current protection, Instantaneous Over current protection, Earth Fault protection, etc. These measured values are also displayed on large 16 x 2 LCD display for metering purpose. The DSC also monitors different digital input

element. (Ip>, and Ip>> ) 2. Non Directional 3Io (Internally derived EF) (3Io> and 3Io>>). 3. Trip Circuit Super vision. 4. Breaker Failure Detection. 5. Monitoring Functions. Each of these functions are independently programmable and can be enable or disable by user depending upon requirement. Over Current & EF Element: The ADR141C is member of Ashida Numerical Relay family design for protection general feeder. The relay has one stage of IDMT/DMT setting and one stage of instantaneous setting. (Ip>, IP>>, 3Io>, 3Io>>). All major international IDMT curves are available. Range for first stage is 10% to 200% and 50% to 3000% for instantaneous stage for phase and 3Io.

through optical isolator and perform some monitoring function such trip circuit supervision, and control potential free contact for control CB and generate ALARM and Tele-signalling The power supply module is basically DC DC converted designed using modern PWM based Switching mode technique to convert station battery supply to the 12V and 24Vdc low voltage supply for relay electronics and control circuit. It also provides necessary isolation from

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.:ADR141C Issue: 05 07.03.2011 Page 2 / 9

ASHIDA Numerical 3OC + 1EF Protection Relay

Type: ADR141C
( AD I T Y AS e r i e s ) (Preliminary)

Although the curves tend towards infinite when the current approaches Is (general threshold), the minimum guaranteed value of the operating

B+

TCCOM

1 6 2

To Relay CPU

CB NO B-

S4

current for all the curves with the inverse time characteristic is 1.1Is (with a tolerance of 0.05Is).
TC CB NC

S3

6 2

To Relay CPU

Fig. Trip Circuit Logic

Relay monitor Trip coil continuity through CB Inverse Time Curves:The each stage thresholds for phase (earth) over current can be selected with an Inverse Definite Minimum Time (IDMT) characteristic. The time delay is calculated with a NO during close condition and through CB NC during Trip condition. If any discontinuity observed it generate Alarm signal. The output can be assigned to any of 4 relay RL1 to RL4, The Trip circuit supervision logic set reset PROTH (Protection healthy) bit, it normally ON and become OFF at following condition
b

mathematical formula

t=

K * a
I Iref

When DC supply is not sufficient (DC fail) When CB NO and CB NC both active or

Curve Type C1 C2 C3 C4 C5 C6

Description Standard Inverse_1 Standard Inverse_2 Very Inverse Extremely inverse Long Time Inverse Define Time

a 0.14 0.06 13.5 80 120 -

b 0.02 0.02 1 2 1 -

both inactive. CB NO as will as CB NC are both close or open. Relay detects any internal hard ware Error. Breaker Failure Detection:Normally after tripping current should become Zero within 100 200ms time depend upon type of fault and breaker mechanism. After Fault ADR141C trigger internal timer (settable from 50ms to 800m) if fault is not cleared during

Trip circuit Supervision:The ADR141C is having 2 separate digital optocoupler status input which can be used to continuously monitor continuity of trip-circuit. The general scheme is as shown in fig. 4.

this time then relay declare as Breaker fail (LBB function) and set BF bit. This bit can be assigned to any of the output relay.

Cold Load pickup:When the Circuit breaker is closed on load, A load current take sudden inrush current. This inrush current may be more than 4 to 5 times of

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.:ADR141C Issue: 05 07.03.2011 Page 3 / 9

ASHIDA Numerical 3OC + 1EF Protection Relay

Type: ADR141C
( AD I T Y AS e r i e s ) (Preliminary)

rated load current. The duration can be as high as 200ms. Due to this inrush current many times relay get operate which is undesirable. General practice is to keep normal setting to such high value so that it will not mal operate at initial closing which result increase in fault clearance time. To avoid such problem relay is equipped with special features known as clod load pickup. Whenever a circuit breaker is turn on relay sense through CB auxiliary contact and start internal timer known as CL timer. During this time it takes separate set of setting, so that relay will not mal operate on inrush current

Programmable DI/DO and LED:The ADR141C has 4 digital outputs, 2 optoisolated input and 8 general purpose LEDs. These can be programmed by local key board. Any logical of physical status can be assigned to any relay contact The logic of digital status input as well as logical status can be formed and assigned to any of the relay output. The RL1 relay is by default assign to TRIPING CB.

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.:ADR141C Issue: 05 07.03.2011 Page 4 / 9

ASHIDA Numerical 3OC + 1EF Protection Relay

Type: ADR141C
( AD I T Y AS e r i e s ) (Preliminary)

While Ordering Specify the following Information for ADR141C Relay


Definition of Model No of Aditya Series of Relays

AM XXXXX X X XX X
Reserved for Future Use Auxiliary Supply PT Secondary 0 = NO PT 01 = 18 52 V dc 02 = 77 250 V dc 03 = 24 V dc 04 = 30 V dc 05 = 48 V dc 06 = 18 250 V dc

CT Secondary 1 = 1 Amp. 2 = 5 Amp. 3 = 1 Amp. / 5 Amp. Selectable

AM

XXX

XX Over Current Earth Fault Relay

For Adity-V2 series start from 201. For V1 series refer respective document 201 201 201 01 02 03 Obsolete Version Relay with standard Back Connection (not Recommended) Relay with Ring Type Back Connections CSE H 150 CSF H 136 CSF H 136 3 3 3

Ordering information: A D R 1 4 1 C A M X X X X X X X X X X

Example AD R 1 4 1 C AM - 2 0 1 - 0 2 - 3 - 1 - 0 6 - 0 T yp e : A D R 1 4 1 C St. Back terminal layout C a b i n e t T yp e : C S F - 1 5 0 H Auxiliary Supply: 18-250Vdc C T s e c : 1 Amp. / 5 Amp selectable

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.:ADR141C Issue: 05 07.03.2011 Page 5 / 9

ASHIDA Numerical 3OC + 1EF Protection Relay

Type: ADR141C
( AD I T Y AS e r i e s ) (Preliminary)

Technical Specifications: General specifications


Sr. No. I. II. III. IV. V. VI. VII. VIII. IX. X. Specification Current Input Aux. Supply VA burden on CT VA burden on Aux. Operating Temp. range Continuous carrying capacity Pick up Reset Value Output Contact Contact Rating Particulars : Suitable for CT secondary 5Amp. Or 1Amp site selectable : 18 - 250VDC. : Less than 0.2VA : Less than 10 Watts : -10 deg. To + 65 deg. : 2 x of rated for CT and 1.5 x of rated for PT : Within 1.1 times of set value. : 95% to 90% of pick up. : 4 Trip duty user assignable : Continuous: 5A : Make & carry for 0.5 sec : 30A : Make carry for 3 sec : 15A XI. XII. Opto Isolated input Thermal With stand for CT : 1 for CB NO & 1 for CB NC : 20 x of rated for 3.0 sec.

General Settings
XIII. General setting : New PassWord : Unit Id : CT Sec : CT Primary : Test Block : Trip Ckt. :BF Enable : BF Delay 0 99 in steps of 1 0 250 in steps of 1 1A or 5A 10 - 2000in steps of 10 01: YES, 02: NO 01: YES, 02: NO 01: YES, 02: NO 50-800 mS steps of 50ms

Relay Settings
XIV. Phase Section (Ip) : IP> Settings : IP> Time Multiplier (TMS) : IP> Curve (Operating Time) : IP> C6 Delay : IP>> Settings : IP>> Delay XV. Earth Fault Section (3Io) : 3Io> Settings : 3Io> Time Multiplier (TMS) : IE> Curve (Operating Time) : 3IO> C6 Delay : 3IO>> Settings 10% 250% in steps of 1%. x0.01 x1.00 in steps of 0.01 C1 C6 ( IDMT curve C1 C5 or Define Time C6 ) 0 99.9 Sec in steps of 0.1Sec. 00% 3000% insteps of 50% 00 means block 0 2.00 Sec in steps of 0.01Sec. 10% 250% insteps of 1% x0.01 x1.00 in step of 0.01. C1 C6 ( IDMT curve C1 C5 or Define Time C6 ) 0 99.9 Sec in steps of 0.1Sec. 00% 3000% insteps of 50% 00 means block

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.:ADR141C Issue: 05 07.03.2011 Page 6 / 9

ASHIDA Numerical 3OC + 1EF Protection Relay

Type: ADR141C
( AD I T Y AS e r i e s ) (Preliminary)

: 3IO>> Delay

0 2.00 Sec in steps of 0.01Sec.

Cold Load settings


XVI. Phase Section (Ip) :CL Enable : CL Timer : IP> Settings : IP> Time Multiplier (TMS) : IP> Curve (Operating Time) : IP> C6 Delay : IP>> Settings : IP>> Delay XVII. Earth Fault Section (3Io) : 3Io> Settings : 3Io> Time Multiplier (TMS) : IE> Curve (Operating Time) : 3IO> C6 Delay : 3IO>> Settings : 3IO>> Delay 01: YES, 02: NO 0-2.00S in steps of 0.01 sec 10% 250% in steps of 1%. x0.01 x1.00 in steps of 0.01 C1 C6 ( IDMT curve C1 C5 or Define Time C6 ) 0 99.9 Sec in steps of 0.1Sec. 00% 3000% insteps of 50% 00 means block 0 2.00 Sec in steps of 0.01Sec. 10% 250% insteps of 1% x0.01 x1.00 in step of 0.01. C1 C6 ( IDMT curve C1 C5 or Define Time C6 ) 0 99.9 Sec in steps of 0.1Sec. 00% 3000% insteps of 50% 00 means block 0 2.00 Sec in steps of 0.01Sec.

Operational Indicators (Flags) 4 user assignable bicolour output LED Default assignment XVIII.
LED1 - PROT.H /ON : Green LED indicates Relay OK (Protection Healthy) : Red LED indicates Fault in following conditions. 1. Problem in relay Hardware. 2. Trip Circuit Fault LED 2 - PICK-UP LED 3 - FAULT LED 4 - TRIP : Red LED indicate Start of timer Self Reset (SR) Type : Red LED indicate Relay Operated Flag (HR) : Red LED indicates Output TRIP relay contact closer (SR) Type : For Typical External connection : For Cabinet Type - ADV02703 - MAC01501 (CSF)

XIX.

Drawing References

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.:ADR141C Issue: 05 07.03.2011 Page 7 / 9

ASHIDA Numerical 3OC + 1EF Protection Relay

Type: ADR141C
( AD I T Y AS e r i e s ) (Preliminary)

The Relay Confirm to following standard Sr. No. Title Standard no. Electromagnetic Compatibility Type Test: 1. High Frequency Test : IEC 60255-22-1, class III : Frequency : 1MHz Damped Oscillatory : Longitudinal :5 KV (peak) : Duration: sec duration 2 sec. : Between input current Terminal 2. Electrostatic : IEC 60255-22-2 Class III and IEC 61000-4-2 class III. Discharge Direct : Contact discharge: 6kV, Application : Air discharge: 8KV : Polarity: both +ve and Ve polarities. 3. Indirect Application : IEC-61000-4-2, Class-III 4. Fast Transient Disturbance Surge Immunity Test 5. : IEC 60255-22-4 and IEC 61000-4-4, class A : 1.2KV; 5/50ns; 5KHz burst duration = 15ms. : Repetition rate 300ms; Both polarities; Ri = 50; duration 1 min. : IEC 60255-22-5 / IEC 61000-4-6 class 4 : Differential Mode = 2kV : Common Mode = 4kV : 1.2/50uS , 5 surges of each polarity : IEC-61000-4-8, Class-V : IEC- 60255-22-3 : EN-61000-4-3 : Frequency 80MHz 1GHz : IEC 60255-22-6 / IEC 61000-4-6: 1996. : Freq. 150kHz 80MHz, Amplitude 10 V, Modulation 80% AM @ 1 KHz : IEC 60255-11 : IEC 60255-25 : IEC 60255-5. class III : At 2.5kV 50Hz between all terminal connected together and earth for 1 minutes : IEC 60255-5. class III : Test voltage: 5KV (peak) 1.2 / 50us, : Energy :0.5 J, : Polarity : + ve and Ve : Nos. of impulses : 3 positive and 3 negative impulse : Duration between Impulses : 5 sec.

6. 7.

Power Frequency Magnetic Field Test Radiated Electromagnetic Field Disturbance Conducted Disturbance Induced By Radio Frequency Field AC Ripple In DC Supply Test Radiated Emission

8.

9. 10.

Insulation Tests: 11. High Voltage Test

12.

Impulse Voltage Test

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.:ADR141C Issue: 05 07.03.2011 Page 8 / 9

ASHIDA Numerical 3OC + 1EF Protection Relay

Type: ADR141C
( AD I T Y AS e r i e s ) (Preliminary)

Environmental tests: 13. Cold test Storage test 14. Dry heat test Damp heat test, 15. steady state 16. Damp heat test, cyclic Mechanical tests 17. 18. Vibration Bump Test

: IEC 60068-2-1 : IEC 60068-2-2 : IEC 60068-2-3 : IEC 60068-2-30 : IEC 60255-21-1 class 1 : Frequency Range = 10Hz 150Hz , acceleration. = 1gn (9.8 m/s2) : Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis. : IEC 60255-21-2 Class-1 : 1000 bumps of 10gn peak acceleration and 16ms pulse duration in each of the two opposite direction per axis as per IEC 60255-21-2 class 1 No. of axes . 3. : IEC 60255-21-2 Clas-1 : 3 shocks of 15gn peak acceleration and 11ms pulse in each of two opposite direction . No. of axis : 3 : IEC 60255-21-3 : In single axis sine sweep in X-axis sweep (@a sweep rate of 1 octave/minute) vibration in the frequency range (5-40 Hz) at amplitude of 3.5mm or 1.0gn (whichever is less) : In single axis sine sweep in Y-axis - sweep (@a sweep rate of 1 octave/minute) vibration in the frequency range (5-40 Hz) at amplitude of 1.5mm or 0.5gn (whichever is less)

19.

Shock Withstand

20.

Seismic Test

Revision Note
Rev. No. 01 02 03 04 05 Date 15.08.09 01.01.10 04.02.10 16.03.10 07.03.11 Description Original specifications Photograph of Relay updated Addition of cold load pick up. Back terminal connections changed ADV02702 Back terminal connections changed ADV02703

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.:ADR141C Issue: 05 07.03.2011 Page 9 / 9