OVERVIEW
Dr.M.S.R.MURTY
drmsrmurty@yahoo.com
GOVERNING SYSTEM
OVERVIEW
TOPICS
Excitation
Controller
TURBINE GEN
f Voltage sensor
V & Comparator
Steam valve
fref
Controller Vref
Frequency sensor
& Comparator P + jQ
Speed Excitation
TURBO GENERATOR : Governing & Control
System System
LFC AVR
S. H. PRESS
STEAM
E–H
CONTROL MW
SYSTEM
SPEED
G
ST
Boiler
PROCESSING
AND
AMPLIFYING ○ G
ST
SPEED
SENSING
C
• Sensing : - Mechanical (Fly ball type)
- Hydraulic (Pump)
- Electric (toothed Wheel
pick up, MW Transducer)
• Processing : - Hydro-mechanical
- Electro-hydraulic
- Digital Electro-hydraulic
• At steady state :
• Turbine Torque (Pm) = Load Torque( (Pel)
• During transient :
Speed = ∫((Pm – Pel) / Ta ) dt
STEAM GOV.
SYSTEM
SV
POWER
CV
SPEED
ST ○ GRID
G
Protection
System SP : SET POINT
CV : CONTROL VALVE
Measured
value
Transducer
Or Sensor
Speed, MW,
Pressure
Operating Modes:
Isolated : S Open
Interconnected : S Closed or grid connected
ELECTRONIC CONTROLLER
Speed
Ref: SPEED
CONTROLLER
Speed
PI TO Hyd
Amplifier
SELECTION E
LOGIC H
Load
LOAD
Ref:
CONTROLLER
Load PDP
X K P + Ki Y
s
Output
PI
(Y)
Load
Controller
t Output PID
Output (Y)
(Y)
X K P + Ki + Kd s Y
PD s
t
Output t
(Y) PDP
K( 1+ sTv)
(1+ sT)
Speed
K Controller
t
Tuning Of Speed Controller
• K( 1+ VsTs.s)
KV
(1+ Ts.s) s s
Ks
• Vs : Higher value helps in
stabilizing Sec
• Ts : Minimum value
necessary
• Ks : Fixed by droop
25 (4%)
or 20 ( 5%).
Speed Regulation Or Droop
Speed Valve Steam Turbine
Change Opening Flow Power
Change Change Change
= (Load)
Speed Or
Frequency
52 Hz 104 %
50 Hz 100 %
0 50 100
Load
%
Speed Controller Set Point
1.005 0.
20
Load rejection
nr 1 To
performance is
….. Selecti
- -on influenced by set
Logic point
ns
1.0
MW To Valve
Opening
ref + Load Controller
(PI)
-
MW
Speed Controller : Ready to take over when large load changes occur
Load Controller : Slower response than Speed Controller
SC O/P
Speed
0.1
+
0.1
S.C Σ
LC O / P 0.2
Valve
0.3 Opening
M M Command
A I
0.2
X 0.2 N
L.C
0.2
MW
SELECTION LOGIC
P ref
VL
P el
KPL
+
--
-- + SELECTION
TO
EHC
1
T IL S
KGL From
Frequency SC
Influence
Load Controller:
--- Has influence only in interconnected operation
--- Combination of KPL and TIL is necessary for proper generation
increase / decrease.
--- Small value of feed forward ( VL ) ensures prompt response.
--- Influence of frequency on gen. can be provided to suit grid.
Governor Dead Band
Valve
Opening
Frequency or Speed
Dead Band Or
insensitivity
Steam
HPCV
HPT
IPT
LPT
IPCV
Condenser
RH Reheate
r
IP CONTROL ACTION
• When Speed increases HPCV starts Closing
Immediately
• IPCV starts closing after about 103 % speed rise
and closes completely at about 106 %
• IPCV action reduces transient speed rise
E HG
M VALVE
I OPENING
COMMAND
N
MHG Hydraulic
Minimum
Mechanical – Hydraulic
Controller
UNIT DEMAND CONTROL SYSTEM INTERFACE WITH
GOVERNING SYSTEM
LPT
HPT
G
SPEED
LOAD GOV,
Extraction SYSTEM LPCV
Steam
Pressure CONDENSER
TO PROCESS
HPT
IPT
LPT
N
EXTRACTION 1 EXTRACTION 2
CONDENSER
Stream
Generator
SG
Turbine
Stream
N
SG
Hrader
Process Process Process Process
H
E
A
D N
E
R
SPEED
CONTROLLER
LOAD
CONTROLLER
PRESSURE
CONTROLLER
VALVE
OPENING SPEED
TURBINE
GOVERNOR SYSTEM MW
PRESSURE
SPEED
MW
PRESSURE
Governing System Overview
Summary
• Important for startup, synchronization and
loading
• Stable and secure operation
• Electro hydraulic turbine control with
Speed, load and Pressure controller
• Proper tuning of control parameters is
essential
• Droop (4 to 5 %) helps in stabilization
• Dead band or insensitivity should be
minimum
• Additional mechanism: Load shedding
relay
• Automatic Load frequency Control acts
through Governing system