Professional Documents
Culture Documents
Semester A 2011/12
Raymond Boyd
Subjects Covered
Objectives of Ventilation Infiltration Natural Ventilation Mechanical Ventilation and Air Conditioning Air Supply Systems Air Extraction Systems All-Air Systems Air and Water Systems All-Water and Packaged Systems Local Extraction Ventilation Energy Efficiency and System Selection
Semester A 2011/12
Raymond Boyd
Objectives of Ventilation
Dilute contamination to a level which is safe and acceptable Limiting level of carbon dioxide for 8hr occupation is 0.5% Usual clean air requirement 2.4 litres/sec/person Odour removal Dust & other contaminant removal Humidity control
Relative humidity < 30% - risk of drying of mucous membranes Relative humidity > 70% (with high temperature) interferes with perspiration and feels clammy
Semester A 2011/12
Raymond Boyd
Infiltration
Infiltration is the fortuitous leakage of air through a building due to imperfections in the structure -
(CIBSE, 2006)
Semester A 2011/12
Infiltration by wind
Wind direction
+ ve
- ve
High pressure
ve = pressure
Low pressure
Raymond Boyd 5
Semester A 2011/12
Air entering is heated, becomes less dense, and rises. Outside pressure is higher than inside.
Semester A 2011/12
Raymond Boyd
Infiltration Routes
Cracks around service entries Porous material Around door and window frames Timber floors Cavity wall to floor connections Cavity wall to dry liner connections Loft hatch Flues and chimneys Around panel walling elements
Semester A 2011/12
Raymond Boyd
{ach = air changes per hour = volume flow rate (m3/hr)/ volume of space (m3)}
Good sealing technique can take this to 0.2 ach At < 0.5 ach, ventilation must be designed-in Infiltration heat loss can be comparable with fabric losses permitted in building regulations
Raymond Boyd 8
Semester A 2011/12
Natural Ventilation at The Environmental Office: Building Research Establishment (BRE) Watford
Semester A 2011/12
Raymond Boyd
Natural Ventilation
Exploits wind and stack effects Design with natural cooling Uses Cooling stacks Vent louvres Windows Hollow floor design May be Passive Active
10
Semester A 2011/12
Raymond Boyd
The office plan with its glazed facades exploits natural daylight and cross ventilation via the BMS
Semester A 2011/12 Raymond Boyd 11
Natural ventilation cannot give required environmental control throughout the building. Zone control is required. There is a substantial cooling load. There are process or health and safety ventilation requirements
Raymond Boyd 12
Semester A 2011/12
Semester A 2011/12
Raymond Boyd
13
Some buildings are supply only, others extraction only Most commercial buildings will have both supply and extraction
Raymond Boyd 14
Semester A 2011/12
boiler
Semester A 2011/12
Radiators or convectors
Raymond Boyd 15
natural ventilation but adding cooling in the most sensitive area using a split system
Radiators or convectors
16
natural ventilation but provide heating and cooling throughout using a variable refrigerant volume system (vrv)
predominantly natural ventilation but provide heating and cooling throughout using a vrv system, with mechanical ventilation in the core.
AHU
This may sometimes be supply-only: supply and extract shown in the drawing.
Raymond Boyd
18
Chiller condenser
AHU
Boiler supplies DHW, AHU and fan-coil units Chiller supplies AHU and fan-coil units (piping omitted for clarity)
Semester A 2011/12 Raymond Boyd 19
Semester A 2011/12
Boiler supplies DHW, AHU Chiller supplies AHU (piping omitted for clarity)
Raymond Boyd
20
The only medium providing cooling and humidity control is air. All cooling, filtration, de-humidification, humidification is done in central plant (air handling unit AHU), and air is ducted through the building.
Semester A 2011/12
Raymond Boyd
21
Heating can be done either in the central plant, or at zone re-heaters. Can be
Distribution can be
Semester A 2011/12
Raymond Boyd
22
Semester A 2011/12
Raymond Boyd
23
Semester A 2011/12
Raymond Boyd
24
Typical AHU
University Facilities Management
Semester A 2011/12
Raymond Boyd
25
Disadvantages
Low operating cost possible Heat recovery possible Quiet operation Ease of maintenance Simple to design Responsive to different zone loads
Space ducts are large Balancing & commissioning can be difficult Design co-ordination is vital
Semester A 2011/12
Raymond Boyd
26
Occupied Space
Occupied Space
Semester A 2011/12
27
+ Occupied Space
+ Occupied Space
Semester A 2011/12
28
Air-and-Water Systems
Both air and water are distributed to provide heating and cooling. The central air handling plant usually meets the requirements for fresh, clean air and humidity control.
Semester A 2011/12
Raymond Boyd
29
Air-and-Water Systems
Induction Primary air fan-coil systems Various piping schemes are possible, e.g. 2, 3 or 4 pipe schemes
Semester A 2011/12
Raymond Boyd
30
Primary air Supply from AHU Water supply and return from boilers and chillers
Heating/cooling coil
Raymond Boyd 31
Semester A 2011/12
mixing
Semester A 2011/12
Raymond Boyd
32
Semester A 2011/12
Raymond Boyd
33
Outdoor air Water supply and return from boilers and chillers
Semester A 2011/12 Raymond Boyd
fan
34
All-Water Systems
Not really air-conditioning, as no humidity control. Chilled and hot water supplies total thermal load. Ventilation is provided by outdoor air Similar to fan-convector for heating a naturally-ventilated building
Raymond Boyd 35
Semester A 2011/12
Semester A 2011/12
Raymond Boyd
36
Often referred to as HVAC Usually only heating or cooling plant Dont provide humidity control Operate a refrigeration cycle, extracting heat in the evaporator, and releasing it in the condenser.
Semester A 2011/12
Raymond Boyd
37
The cold side of the air conditioner contains the evaporator and a fan that blows air over the chilled coils and into the room. The hot side contains the compressor, condenser and another fan to vent hot air coming off the compressed refrigerant to the outdoors.
fan evaporator
Refrigerant pipework
condenser
Liquid stage
Semester A 2011/12
compressor
38
Semester A 2011/12
Raymond Boyd
39
Typical applications small/medium commercial or similar buildings Used where natural ventilation + heating and/or cooling fails to give sufficiently uniform control Cheaper to install Relatively coarse control of conditions Not easy to exploit energy recovery techniques
Semester A 2011/12
Raymond Boyd
40
Supply-only Systems
Filtered and heated or cooled outdoor air is supplied. High level vents or wall grilles allow air to escape from the pressurised space. Use where contaminants from outside air need to be kept out of the process. Use where there are no obvious process heat (or cooling) sources. Dont use where the process generates moisture, as it tends to drive the moisture into interstices in the structure
Semester A 2011/12
Raymond Boyd
41
Extraction-only Systems
A fan draws air through vents and grilles into the building Use where process materials need to be contained (can be combined with Local Exhaust Ventilation for capture). Use with processes that generate heat or fume, and capture close to source. Use with conventional convectors or radiators for heating Can be used with heat recovery systems, either air-to-air or air to preheat water.
Semester A 2011/12
Raymond Boyd
42
Used in addition to other ventilation systems Designed to remove contaminants Standard HSG 37 to comply with COSHH regulations Effectiveness depends on
Semester A 2011/12
Raymond Boyd
43
vent
Semester A 2011/12
Raymond Boyd
44
water heating
8 12
%, 78
space heating
10
48
20
space cooling
Semester A 2011/12
Raymond Boyd
45
domestic
(Nicholls, 2002)
Semester A 2011/12
46
(Nicholls, 2002)
domestic naturally air conditioned ventilated office office
Raymond Boyd 47
Semester A 2011/12
Semester A 2011/12
Raymond Boyd
48
Openable windows Extraction for moisture and odour Combine with heat recovery where practicable
Semester A 2011/12
Raymond Boyd
49
CIBSE, 2006, Guide A, Environmental Design 7th edition (also 6th edition 1998), London, The Chartered Institution of Building Services Engineers Nicholls R., 2002, Low Energy Design, Oldham, Action Energy (Interface Publishing), ISBN 09539409-2-6 Department of Trade and Industry, 1998 : Energy Consumption Guide 19: Energy Use in Offices,London, dti CIBSE, 1998, Guide F: CIBSE Energy Efficiency Guide, London, The Chartered Institution of Building Services Engineers HMG, 2002, The Building Regulations Part L Conservation of Fuel and Power, London, HMSO
Semester A 2011/12
Raymond Boyd
50