You are on page 1of 19

DEPARTMENT OF TECHNICAL EDUCATION

ANDHRA PRADESH
Name : Sri.E. BABU
Designation : Lecturer
Branch: : Electronics and Instrumentation Engg.
Institute : S.G.P.R. Govt. Polytechnic, Kurnool.
Year/Sem : V Semester
Subject : Process control
Subject code : AEI-504.
Topic : Controller principles.
Duration : 50 mts.
Sub Topic : Two position mode controller output
for fixed error input
Teaching Aids : Diagrams
AEI504.29 1
Recap

In the previous class we have discussed about

• Construction of Error detector using op-amp

AEI504.29 2
Objectives

On completion of this period, you would be able to


know:

• Two position controller mode output for fixed error


input
• Neutral zone
• Example of liquid level control system

AEI504.29 3
Two position mode controller

• This is a discontinuous controller

• This is a ON/OFF controller


• Output equation for different conditions
p=
{ 0% for ep < 0
100% for ep > 0

AEI504.29 4
Two position mode controller

• This relation shows that when the measured value is less


than set point

• Full controller output results when it is more than the set


point

• The controller output is zero when it is less than the set


point

AEI504.29 5
Neutral zone

• In practical implementation of the two position controller

• There is an overlap as ep increases through zero or decreases


through zero

• In this span , no change in controller output occurs fig.1

AEI504.29 6
Two position mode controller

Fig.1
AEI504.29 7
Neutral zone

• The controller output changes to 100% when the error changes

above ep

• The controller output changes to 0% when the error changes


below ep

AEI504.29 8
Neutral zone

• The range 2Δ ep is called as the neutral zone

• This is also called as differential gap

• This is purposefully designed above a certain level

• This prevents excessive cycling

• This is a desirable hysteresis in a system

AEI504.29 9
Example of Liquid level control system

• Finding neutral zone for following specifications

• Displacement of 2 to 3 m converted into 4 to 20 mA control


signal

• A relay serves as the two position controller to open or close

inlet valve

• The relay open 10mA and closes at 12mA

AEI504.29 10
Example of Liquid level control system

• The relation between level and a current is

• H = K I + H0

• We can write two equations as follows

• 2m = K (4 mA) + H0

AEI504.29 11
Example of Liquid level control system

• 3m = K (20 mA) + H0

• Solving these equations

• We get K= 0.0625 m/ mA and H0 = 1.75 m

AEI504.29 12
• The relay closes at 12mA , which is a high level HH

• HH = (0.0625 m / mA) (12 mA) + 1.75 m= 2.5 m

• The relay opens at 10mA , which is a low level HL

• HL = (0.0625 m / mA) (10 mA) + 1.75 m= 2.375 m

AEI504.29 13
Summary

• Output of two position controller mode for fixed error

• Neutral zone

• Example of liquid level control system

AEI504.29 14
QUIZ

1. The controller output for the error within the neutral


zone

a. 0%
b. 100%
c. No change
d. 50%

AEI504.29 15
2. The controller output for the error above the neutral zone

a. 0%
b. 100%
c. No change
d. None

AEI504.29 16
3. The controller output for the error below the neutral zone

a. 100%
b. 0%
c. 50%
d. None

AEI504.29 17
4. The two position controller is suitable for

a. Systems with slow process rates

b. Systems with medium speed

c. Systems with high speed

d. None

AEI504.29 18
Frequently asked Questions in Examinations

• Describe the two position controller mode for fixed error

input

• Define the differential gap

AEI504.29 19