You are on page 1of 31

Supplementary Training Modules on Good Manufacturing Practice Heating, Ventilation and AirConditioning (HVAC)

Part 1 (b): Introduction and overview


WHO Technical Report Series, No. 937, 2006. Annex 2
HVAC | Slide 1 of 31 May 2006

HVAC
Objectives
To continue from Part 1(a), now focus on:  Air filtration  The role of HVAC in dust control  HVAC system design and its components (part 2)  Commissioning, qualification and maintenance (part 3)

HVAC

Slide 2 of 31

May 2006

HVAC
Air Filtration
 Degree of filtration is important to prevent contamination  Type of filters to be used dependent on the quality of ambient air, return air and air change rates  Manufacturer to determine, select and prove appropriate filters for use considering level of ambient air contamination, national requirements, product specific requirements

4.2.1, 4.2.3

HVAC

Slide 3 of 31

May 2006

HVAC
Levels of protection and recommended filtration
Level of protection
Level 1 Level 2 and 3

Recommended filtration
Primary filters, e.g. EN779 G4* Production area with 100% outside air: Primary plus secondary filter (e.g. EN779 G4 plus F8 filters) Production area with recirculated plus ambient air with a risk of cross-contamination: Primary plus secondary plus tertiary filter (e.g. EN779 G4 plus F8 plus EN1822 H13 filters)
4.2.1

Level 2 and 3

*Filter class should be referenced to the standard test method

HVAC

Slide 4 of 31

May 2006

HVAC
Contamination should be prevented through appropriate:
 Materials for components and construction  Design and appropriate access to dampers, filters and other components  Personnel operations  Airflow direction  Air distribution component design and installation and location  Type of diffusers (non-induction type recommended)  Air exhaust (normally from a low level)
4.2.4 4.2.10

HVAC

Slide 5 of 31

May 2006

HVAC

HVAC

Slide 6 of 31

May 2006

HVAC
Airflow patterns
Filtered air entering a production room or covering a process can be
 

turbulent, or unidirectional (laminar) GMP aspect economical aspect

Other technologies: barrier technology/isolator technology.

HVAC

Slide 7 of 31

May 2006

HVAC
Airflow patterns
Turbulent
dilution of dirty air

Unidirectional/laminar
displacement of dirty air

HVAC

Slide 8 of 31

May 2006

HVAC
Airflow patterns
Prefilter

AHU

Main filter

Turbulent
HVAC | Slide 9 of 31 May 2006

Unidirectional

Turbulent

HVAC
Airflow patterns (4)
Workbench (vertical) Cabin/booth Ceiling

HVAC

Slide 10 of 31

May 2006

HVAC
Unidirectional airflow (UDAF):
Provided where needed over product or material to prevent contamination, or to protect operator

UDAF in weighing areas


 The aim is to provide dust containment  Airflow velocity should not affect balance  Position of material, balance, operator determined and validated no obstruction of airflow or risk
4.3.1 4.3.10

HVAC

Slide 11 of 31

May 2006

HVAC

Annex 5, 7.

HVAC

Slide 12 of 31

May 2006

HVAC

Annex 5, 7.

HVAC

Slide 13 of 31

May 2006

HVAC
Infiltration
 Facilities normally under positive pressure to the outside  Prevent infiltration of unfiltered, contaminated air from outside  Some cases - negative pressure (e.g. penicillin manufacture). Special precautions to be taken
4.4.1 4.4.4

HVAC

Slide 14 of 31

May 2006

HVAC
Cross-contamination
 General aspects and concepts  Displacement concept low pressure differential, high airflow  Pressure differential concept high pressure differential, low airflow  Physical barrier concept
4.5

HVAC

Slide 15 of 31

May 2006

HVAC
General aspects
 Multiproduct OSD manufacturing, prevent movement of dust between areas where different products are processed  Directional air movement and pressure cascade can be helpful dust containment  Normally, corridor at higher pressure than cubicles, cubicles at higher pressure than atmosphere
4.5.1 4.5.3

HVAC

Slide 16 of 31

May 2006

HVAC
Containment concepts
 Pressure cascade regime influenced by:
Product and product group, e.g. highly potent products (in some cases, pressure cascade regime negative to atmosphere) Processing methods

 Building structure should be considered including airtight ceilings and walls, close fitting doors, sealed light fittings
4.5.4 4.5.9

HVAC

Slide 17 of 31

May 2006

HVAC
Displacement concept
 Air supplied to the corridor, through the doors (grilles) to the cubicles  Air extracted at the back of the cubicle  Velocity high enough to prevent turbulence in doorway  Requires large air quantities (Not preferred method)
4.5.10 4.5.12

HVAC

Slide 18 of 31

May 2006

HVAC
Pressure differential concept
 Concept can include high pressure differential, low airflow, and airlocks in the design  Airlock types include: Cascade, sink and bubble type  Sufficient pressure differential required to ensure containment and prevent flow reversal but not so high as to create turbulence  Consider effect of other items such as equipment and extraction systems in cubicles  Operating limits and tolerances
HVAC | Slide 19 of 31 May 2006

4.5.13 4.5.18, 4.5.22

HVAC
Pressure differential concept (2)
 Calibrated monitoring devices, set to alarm system  Monitoring and recording of results  Doors open to higher pressure  Dust extraction system design
Interlocked with air-handling system No airflow between rooms linked to same system Room pressure imbalance 4.5.19 4.5.26
May 2006

HVAC

Slide 20 of 31

HVAC
Pressure cascade solids Protection from cross-contamination
R oom 1
15P a

R oom 2
15P a

R oom 3
15P a

Air Lock

Air Lock Air Loc k


E

30P a

0P a

Pa ssa ge

15P a

N ot : D i ecton of door openi r atve t r e r i ng el i o oom pr sur es e


HVAC | Slide 21 of 31 May 2006

HVAC
Physical barrier concept
 In some cases, impervious barriers are used to prevent cross-contamination  Spot ventilation  Capture hoods

4.5.27 4.5.28

HVAC

Slide 22 of 31

May 2006

HVAC
Temperature and relative humidity (RH)
 Controlled, monitored and recorded where relevant  Materials and product requirements, operator comfort  Minimum and maximum limits  Premises design appropriate, e.g. low humidity areas, well sealed and airlocks where necessary  HVAC design also prevent moisture migration
4.6.1. 4.6.6

HVAC

Slide 23 of 31

May 2006

HVAC
Temperature and relative humidity (RH) (2)
 Remove moisture, or add moisture as necessary  Dehumidification
Refrigerated dehumidifiers with cooling media Chemical dehumidifiers

 Humidifiers should not be sources of contamination


Use of pure steam or clean steam No chemicals added to boiler system if these can have a detrimental effect on product (e.g. some corrosion inhibitors/chelating agents)
4.6.7. 4.6.11
HVAC | Slide 24 of 31 May 2006

HVAC
Temperature and relative humidity (RH) (3)
Humidification systems: Design should be such that the system does not become the source of contamination:  No accumulation of condensate  Avoid evaporative systems, atomizers, water-mist sprays  Suitable duct material, insulation of cold surfaces  Air filters not immediately downstream of humidifiers  Chemical driers used if not sources of contamination
4.6.12. 4.6.18
HVAC | Slide 25 of 31 May 2006

HVAC
Dust Control
 Dust and vapour removed at source  Point of use extraction fixed points or movable hood plus general directional airflow in room  Ensure sufficient transfer velocity to prevent dust settling in ducting  Risk analysis airflow direction, hazards, operator
5.1. 5.7

HVAC

Slide 26 of 31

May 2006

HVAC
Dust Control (2)
 Normally air supplied through ceiling diffusers, and air extracted from low level aids flushing effect  Extraction of vapours consider density of vapour  Handling harmful products additional steps needed
e.g. barrier technology, glove boxes totally enclosed garments with air-breathing systems

 Fresh air rate supply


comfort, odour and fume removal, leakage, pressure control, etc.
5.8. 5.14

HVAC

Slide 27 of 31

May 2006

HVAC
Protection of the environment (Exhaust air dust)
 Exhaust air from equipment and some areas of production carry heavy loads of dust (e.g. FBD, coating, weighing)  Filtration needed to prevent ambient contamination  Not highly potent material
EN779 F9 filter recommended

 Harmful substances (e.g. hormones)


EN1822 H12 (HEPA) filter recommended In some cases two banks of HEPA filters Safe change filter housings ("bag-in bag-out" filters)
6.1.1 6.1.5
HVAC | Slide 28 of 31 May 2006

HVAC
Protection of the environment (Exhaust air dust) (2)
 Filter banks provided with pressure differential indication gauges  Limits indicated, results monitored at regular intervals
Manual, Building Management Systems, Building Automated Systems, System Control and Data Acquisition systems

 Automated systems provided with alarm or similar system to indicate OOS


6.1.6 6.1.10

HVAC

Slide 29 of 31

May 2006

HVAC
Protection of the environment (Exhaust air dust) (3)
 Reverse pulse dust collectors
Should be equipped with cartridge filters with compressed air lance, Continuous operation no interruption of airflow

 Dust collectors with mechanical shakers


Used in a manner not to become source of contamination Switched off at times resulting in loss of airflow, and disruption of pressure cascade

 Wet scrubbers
Use suitable drainage system for dust slurry
6.1.11 6.1.15

 Determine exhaust air quality to verify filtration efficiency


HVAC | Slide 30 of 31 May 2006

HVAC
Protection of the environment (Fume removal)
 Appropriate design, installation, and operation of fume, dust, effluent control  Wet scrubbers
Added chemicals for increased adsorption efficiency

 Deep bed scrubbers


Activated carbon or chemical adsorption granular media Specific to type of effluent Type and volume prepared
6.2.1 6.2.5

HVAC

Slide 31 of 31

May 2006

You might also like